| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.2 LAccepted-AOC NEAR AVON PUBLIC SCHOOL DABHANW POST DANDI NAINI PRAYAGRAJ 211008 | PRAYAGRAJ | PRAYAGRAJ | UTTAR PRADESH | 211008 | ₹13.2 L Quoted ₹13.7 L | L1 | Accepted-AOC Lowest tenderer |
| 2 | L2₹15.3 L+₹1.6 L (11.6%)Rejected-Finance | ₹15.3 L+₹1.6 L (11.6%) | L2 | Rejected-Finance Other than lowest quoted tenderer |
| 3 | L3₹15.7 L+₹2.1 L (15.0%)Rejected-Finance | ₹15.7 L+₹2.1 L (15.0%) | L3 | Rejected-Finance Other than lowest quoted tenderer |
| 4 | L4₹20.6 L+₹6.9 L (50.7%)Rejected-Finance | ₹20.6 L+₹6.9 L (50.7%) | L4 | Rejected-Finance Other than lowest quoted tenderer |
Tender Value
₹25.0 L
EMD Value
₹49,980
Closing Date
9 Mar 2024, 6:00 pmClosed
HQ CWE Prayagraj
HQ CWE New Cantt Prayagraj
REPAIR/ MAINT OF SUBSTATION EQPTS PANEL AND REPAIR AND MAINT OF VACCUM CIRCUIT BREAKERS, RELAYS, MEASURING METERS, PREVENTING ROUTINE MAINT OF CAPACITOR BANK, APFC PANELS ELECTRIC SUPPLY INSTALLATION AT NEW CANTT UNDER GE (WEST) PRAYAGRAJ.
2024_MES_641871_1
81824/W/E8
Open Tender
Civil Works
Item Rate
180 days
Prayagraj
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE (West) Prayagraj
₹49,980
Yes
24 Jun 2024
10 Feb 2024
16 Mar 2024
11 Feb 2024
9 Mar 2024
24 Feb 2024
Amount
M&L for quaterly inspection/servicing /testing by HT expert of 11 Nos. SF 6 Breaker/VCB of line circuit breaker, control panel including CT, PT and relays in control panel of Indoor type SF 6 Gas Circuit Breaker/VCB of capacity upto 800 Amps and rating 36 KV complete as details mentioned as under:- (a) Details of servicing of breaker :- (i) Checking of Closing/Tripping coil assembly (ii) Adjustment of mechanism if required. (iii) Clean the circuit breaker to remove dust and dirt. (iv) Apply a small amount of oil to rotary sections, sliding surfaces, pins, coupling section, etc.use grease for the operating shaft and bearings, and machine oil for other parts. (v) Check for rust and wear. (vi) Checking of spring charge mechanism (vii) Visual check for rust and deformation. (viii) Check for loosened bolts and nuts, broken spring washers and snap pins etc. (ix) Check for loosened connections, rust, damaged lead wires. (x) Checking of control circuit & tighten the connections if any. (xi) Check close & trip coil. (xii) Replacement of Dashpot/shock absorbers . (xiii) Replacement of carbon brush of spring charging motor (xiv) Cleaning of porcelain bushing (xv) Checking of limit switch
(b) The following test shall be carried out:- (i) Primary Injection Test of outdoor CT / PT (ii) Closing & Opening Timing Test for all three poles. (iii) IR Test with megger in open and closed condition. (iv) Contact resistance test for all three poles (v) Closing coil resistance (vi) Tripping coil resistance. (c) Testing of following relays of control panel with Secondary Injection Kit ,checking and programming of relay :- (i) Over current and earth fault relay (ii) Line diffrential relay (d) Testing of followig Aux relay:- (i) DC Supply supervision relay. (ii) Trip Circuit suprvision relay (ii) SF 6 gas pressure low. (iii) PT Fuse failure relay (iv) Master trip relay (v) Under voltage relay (vi) Over voltage relay Note:- (i) Test report shall be laminated to control panel of respective breaker. (ii) The wk shall be carried out from auth Rep/ Engineer of CG/ABB. (iii) Caliberation of relays to be done from qulified engineer of CG/ABB. (iv) The parts shall be replace under relevant item of supply only.
Supply only bushbar spout for crompton make trolly mechanism 11 KV VCB, complete all as specified & directed.
Supply only charging gear for crompton make trolly mechanism 11 KV VCB, complete all as specified & directed.
Supply only operating mechanism for breaker 11 KV VCB complete all as specified & directed. Make. ABB/CG.
Supply only teflon hexagonal interlocking bush complete interlocking with strip complete all as specified & directed.
Supply only on Push button complete all as specified & directed.
Supply only OFF push button complete all as specified & directed.
Supply only ON/OFF Indicator complete all as specified & directed.
Supply only OFF load isolator with earth switch mechanism complete all as specified & directed.
Supply only Z type lever of OFF push button complete all as specified & directed.
Supply only Z type lever of ON push button complete all as specified & directed.
Supply only trip coil only Y1 control volt 24 VDC complete all as specified & directed.
Supply only close coil only Y2 control volt 24 VDC complete all as specified & directed.
Supply only spring charging motor with gear 24 VDC complete all as specified & directed.
Supply only standerd spring charging motorised kit for V module complete all as specified & directed.
Supply only bus bar bottle of vaccum circuit breaker complete all as specified & directed.
M&L (in replacement) Current transformer, indoor comprising of 3 Nos single phase resin cast CTs of 300-150/5+5 amps ratio, PS class, with suitable VA burden and accuracy suitable for protection & metering of 11 KV VCB panel complete ass as specified & directed.
M&L (in replacement) PT : three Nos single phase potential transformer of ratio 11 KV/ 110 volts, class 1, suitable for VA bourden mounted on extended frame of VCB including mounting structure complete all as specified and directed. Note : (i) All the instruments, primary and secondary injection kit and T&P required for the above job shall be arranged by the contractor at site and cost of the deemed to be included in the above rate. (ii) The above checking, inspection, installation and testing work shall be performed by HT expert/Engineer.
Dismantling & taking out defective LT PVC/XLPE cable from trenches with cutting and removing defective parts and supply & making cable joint using straight through joint heat shrink type ad making connection of LT cables, megering & re-storation of electric supply complete including jointing material for the following sizes of cable :- Joint make - Reychem
25 Sqmm 3.5 core to 70 Sqmm, 3.5 core.
95 Sqmm 3.5 core to 240 Sqmm, 3.5 core.
S&F (in replacemement) following items in the existin out door/indoor LT panels MCCB Microprocessor release and connetion with using aluminum lugs/ferruls incl disconnection & connection of cable and making necessary alteration in panel/door using welding wk and cutting as required for proper fixing & connection complete all as specified and directed as below :- (Note :- Make of MCCB/MCB : Schneider/L&T/ABB).
MCCB 3 pole 100 amps rating, 16 KA breaking capacity, with separator at both side.
MCCB 4 pole 150/160 amps rating, 36 KA Adjustable type breaking capacity, with separator at both side.
MCCB 4 pole 200 amps rating, 36 KA Adjustable type breaking capacity, with separator at both side.
MCCB 4 pole 250 amps rating, 36 KA Adjustable type breaking capacity with spreader at both side.
MCCB 4 pole 315 amps rating, 36 KA Adjustable type breaking capacity with spreader at both side.
MCCB 4 pole 400 amps rating, 50 KA Microprocessor release breaking capacity with spreader at bothe side.
Supply, fixing ( in replacement ), connecting to electrical system & testing of Busbar panel board ,cubical type for out door use, made out of 3.15 mm thick CRCA sheet factory made, totally enclosed of size not less that 900x600x500mm and supported with 4 Nos MS Angle legs , duly painted with two coats of powder coated paint over one coat of red oxide primer effectively PVC gaket and sealed mounted on PCC blocks double door type with locking arragnedment with handle at front and openable at front & back bothe side with required hinges heavy duty, compartemtalised suitably including provision for tapping incoming & outgoing electric connections with suitable size of aluminium lugs glands and comprising of the following accessories :- (a) High conductivity aluminium busbar (Set of 4 strips), 4 Nos TPN of 400 amps rating (RYB) for phase and 1 No for neutral mounted on DMC support with heat shrink sleeve-1 Set. , (b) Phase indication lamp, LED type(set of 3) -1 Set (c) Ammeter anolog type having measuring range (0-300) Amps with CTs etc including rotary switch to measure load of each phase : L&T/Seimens. (d) Replacement of volt meter having measuring range (0-500) volt with rotary switch to measure voltage of phase R.Y.B make : L&T/AE. (e) Grouting of panel including earth work as required PCC (1:3:6) type D-2 using 20 mm gradeded stone & plastering with (1:4 ) cement sand etc complete. (f) MCCB 4 Pole 250 Amp 415 volt thermal adjustable ,type with 25 KA breaking capacity & spreader both side as Incomming cotrol device : 01 Nos. (Schnieder/Havells/L&T/ABB)
M&L (in repair) cable jointing kit for 11 KV cable for end termination heat shrink type joint with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size:-
Size 50 sqmm to 95 sqmm, Indoor type.
Size 120 sqmm to 185 sqmm, Indoor type.
Size 240 sqmm to 300 sqmm, Indoor type.
Size 50 sqmm to 95 sqmm, outdoor type.
Size 120 sqmm to 185 sqmm, outdoor type.
M&L (in repair) cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable including necessary excavation and retuening filling work complete all as specified & directed of following size :-
size 50 sqmm to 95 sqmm
size 120 sqmm to 185 sqmm
Indoor type 250 KVAR APFC panel.
Indoor type 200 KVAR APFC panel.
Indoor type 150 KVAR APFC panel.
Indoor type 100 KVAR APFC panel.
Supply, installation, testing & commissioning vertical/horizontal type (in replacement) of Gang operated air break switch with drop out fuse unit complete with 12 nos insulator , HT 11 KV triple pole, 200 amps capacity current rating complete with drop out fibre glass tube fuse, mechanically operated mechanism from ground level consisting of operating rod of 25 mm bore medium grade GI pipe of suitable length with locking arrengment, flat iron clamp 50mm x 6mm including MS channel of suitable size and length for fixing GOD including bolts, nuts and washers incl jumper connection with copper flexible designed jumper complete all as specified and directed. Make: Pactil/Jaipuria
M&L for earthing complete with galvanised steel earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25m deep below GL with top edge of plate not less than 1.50 m below normal ground level) connected to galavanised earth lead strip 32mm x6 mm (7.5m) as means of bolts, nuts, check nuts and washer besides brazing at all joints as shown on drawings and including excavation, earth work, GI pipe (ISI mark) light grade 40mm bore for protection of GI strip from earth electrode to and including the earth test point, supplying and laying charcoal dust, common salt, PCC 1:3:6, type C-1 (using 20mm graded crushed stone aggregate) chamber and mild steel angle iron frame 40x 40 x 3 mm and 40 mm thick pre-cast RCC cover 1:2:4, type B-1 (using 20mm graded crushed stone aggregate) reinforced with 8 mm dia TMT bars @ 75 mm C/C both ways with mild steel handle 12 mm dia, PGI funnel and wire mesh, 20 mm dia GI pipe light grade (ISI marked) for watering all as shown in electrical plate No 3 of SSR Part-I and connected to earth test point including testing & taking down of old/ ineffective earthing complete all as specified and directed. (Note:- The rates quoted shall also deemed to include the cost of Earth test point and earth wire and protection pipe upto 7.5 meter beyond the earth plates electrode)
Supply , fixing (in replacements) and commissioning microprocessor based Air Circuit Breaker draw out type 4 pole 1000 Amp 50 KA breaking capacity , having Icu=Ics=Icw (1sec) in existing LT panel fixed at site , including necessary cutting , welding of panel for accommodate the ACB suitable for easy operation in LT panel , complete all as specified and directed. Make: Schneider/Legrand/ ABB
S&F (in replacemement) of onload /offload Changeover rotary handle type in the existing out door/indoor LT panels/wall and connetion with using aluminum lugs/ferruls incl disconnection & connection of cable and making necessary alteration in panel/door/wall using cutting/ chasing as required for proper fixing & connection complete all as specified and directed by Engineer-in-Charge. Make:- Havells/L&T/C&S/Sneider)
S&F On Load Change over switch of 400 Amp, 4 Pole
S&F On Load Change over switch of 600 Amp, 4 Pole
S&F Off Load Change over switch of 1000 Amp, 4 Pole
Titco Electricals
B S ENGINEERS AND ASSOCIATES
ASIA ENGINEERING WORKS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .