Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance C 36 DUGGAL COLONY KHANPUR DEVLI ROAD DELHI 110062 | SOUTH | DELHI | 110062 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Admitted-Finance | Admitted-Finance |
Tender Value
₹17.9 L
EMD Value
₹35,900
Closing Date
29 Apr 2022, 2:30 pmClosed
Executive Engineer (E)
Executive Engineer-I, DAMB, 9 Institutional Area, Pankha Road, Janak Puri, New Delhi-110058.
Supply, Installation ,testing and commissioning of LED 120 watt LED street light fitting for replacement of conventional fittings on existing bracket in block no. 1 to 4 and replacement of old feeder pillars at Fruit and Vegetable market Gazipur
2022_DAMB_220699_1
25(22)/300/2021/DAMB/Engg
Open Tender
Electrical Works
Supply
60 days
Fruit and Vegetable market Gazipur Delhi
Please refer Tender documents.
7 documents required · 7 mandatory
₹0
₹35,900
9 Jun 2022
19 Apr 2022
29 Apr 2022
19 Apr 2022
29 Apr 2022
19 Apr 2022
Amount
Supply, Installation ,testing & commissioning of highly efficient LED street light made of pressure die cast aluminum housing with <3W LEDs lens & toughened glass. IP66 Flood Light fittings suitable for existing bracket lights & pole Street lights as per list of approved brands & technical specification attached with five years unconditional replacement guarantee for following LED light fixtures, equivalent to 120 W Model No-(HLSLD-06-120WWL-RL) Make -Halonix .
(i) 120 watt LED street light fittings
Providing the copper wire connections from pole box to Led lights including thimbling complete etc as required .
(i) 3x2.5 mm copper wire
Dismantling of existing 250 watt HPMV fittings /fixtures, etc. as required from existing bracket lights on block's parapet .
Supplying, fabricating, installation, testing and commissioning of electric feeder pillar weather proof (IP-66) made of MS sheet 14SWG size of 1.17 Sq mtr or (1300mmx900mmx350mm) dust protected dully powder coated in inclusive of 200 Amp bus bar, common neutral link, dinbar, earth bar for mounted MCB and MCCB datable gland knock out plate and based on 25x25x5mm thick angle iron fram with 600mm legs from surface to fix on reinforced cement concrete base made out of RCC pillers and well finished plastered base by cement etc as required. 1.Incommer MCCB 200 Amp 04 pole 415 v, 01 nos 2.Outgoing MCB TPN, 63Amp, 08 Nos 3.Indicator R,Y,B
Supplying and fixing of PVC junction box (sintex) size of (250x250x150) mm with 04 no bus bar strip 100amp and clamp 02nos with nut bolt as per required.
Supplying ,fixing 2.5 mtr long 50 mm G I pipe 'C' class (JINDAL HISAR)bracket powder coated with enamel cream finished paint welded with base plate (250mmx250mmx6 mm) and fastener (75mmX8mm), drilling hole etc compleate as per site requirement.
Supplying of 4x16 Sq mm power cable aluminum conductor Armored PVC insulated/ Sheathed, XLPE 1.1kv grade as per required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of size UP to 35sqmm (clamped with 1mm thick saddle) on wall surface as required.
Supplying & Fixing of 125 Amp 50 kA MCCB in suitable powder coated, enamel painted enclosure /MS box water proof IP66 with opening space for MCCB nob familier with cable connections in both side including suitable nuts & bolts,Spreader Terminal kit, gland & fasteners complete etc as requir
Supplying, fabricating, installation, testing and commissioning of electric feeder pillar weather proof (IP-66) made of MS sheet 14SWG size of 1.98 Sq mtr or (1500mmx1200mmx450mm) dust protected dully powder coated in inclusive of 400 Amp bus bar, common neutral link, din bar, earth bar for mounted MCB and MCCB datable gland knock out plate including internal aluminums bus bar, cable ally, solid connections with intermediate sections for suitable housing for required MCCB's MCB's and other accessories and based on 50mmx50mmx6mm thick angle iron frame with 600mm legs from surface to fix on reinforced cement concrete base made out of RCC pillars and well finished plastered base by cement etc as required. 1.Incommer MCCB 400 Amp, 4 pole, 50 kA Model no. IHLLNFB40400-LN Frame Make- Havells- 01 nos 2.Outgoing MCCB 100 Amp, 4 pole, 36 kA Model no. IHA13EB40100-LN Frame Make- Havells- 06 Nos 3. Outgoing MCB, FP, 63 Amp,10KA, Model no.- DHMGCFPF063,Make- Havells-06Nos. 4. Outgoing MCB, DP, 63 Amp,10KA, Model no.- DHMGCDPF063,Make- Havells 5. Indicator R,Y,B -03 Nos. 6. VOLT.SEL SW. C/G-01No.
Supplying and making end termination with brass compression gland and aluminum lugs for 4X16 Sq mm size of PVC insulated and PVC sheathed / XLPE aluminum conductor cable of 1.1kV grade as required.
Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
Part - B (Dismantled/Retrieved item) Following items are likely to be retrieved during replacement of HPSV fixtures with LED based fittings. The recovery at the quoted rate shall be made from contractor bill as buy back items.
Retrived old HPSV/HPMV lights fixtures 250 watt with contral gear box , it may be noted that lamps /chocks in working condition shall not be given to contractor
ztp corporation
CHAUHAN AND ASSOCIATES
Rajesh Electrical Works
ANU ENGINEERING CORPORATION
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .