Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹40.6 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹55.8 L+₹13.8 L (32.8%)Rejected-Finance | L2 | Rejected-Finance L2 | |
| 3 | L3₹70.2 L+₹28.2 L (67.2%)Rejected-Finance | L3 | Rejected-Finance L3 |
Tender Value
₹45.1 L
EMD Value
₹90,120
Closing Date
9 Mar 2022, 6:00 pmClosed
GE Jaipur
Garrison Engineer, Military Engineer Services, Khatipura road, Jaipur 302012
PROVN OF WATER SUPPLY PIPE LINE FROM HQ SWC BOOSTER PH TO JAT OHT AND SPL REPAIR TO EXTERNAL ELECTRIC NETWORK AT MH AT JAIPUR MIL STN
2022_MES_507132_1
GE/J-56/2021-22
Open Tender
Civil Works
Item Rate
180 days
Jaipur
As per NIT
5 documents required · 5 mandatory
₹500
GE Jaipur
₹90,120
Yes
30 Mar 2022
10 Feb 2022
11 Mar 2022
10 Feb 2022
9 Mar 2022
24 Feb 2022
10 Feb 2022 - 23 Feb 2022
Amount
S&F 1100 volt grade heavy duty XLPE cable with PVC insulated aluminum conductor served with inner sheathing of PVC tape armoured with galvanized steel strip or wire and overall PVC sheathed of size 400 Sqmm nominal cross section 3.5 core laid in trenches, fixed to pole or passing through pipes including all necessary clamps, nuts, bolts washers complete all as specified and directed.
All as per Item No. 1 above but of size 300 Sqmm nominal cross section 3.5 core.
All as per Item No. 1 above but of size 240 Sqmm nominal cross section 3.5 core.
All as per Item No. 1 above but of size 185 Sqmm nominal cross section 3.5 core
All as per Item No. 1 above but of size 95 Sqmm nominal cross section 3.5 core
All as per Item No. 1 above but of size 50 Sqmm nominal cross section 3.5 core
All as per Item No. 1 above but of size 6 Sqmm nominal cross section 2 core
S&F galvanised mild steel tubes "light grade " of 100 mm bore (ISI marked) with all fitting( ISI marked) and fixed to walls and ceilings or laid in floors/ trenches and under road, complete all as specified and directed.
All as per Item No 8 above but 80 mm size.
All as per Item No 8 above but 40 mm size.
Excavation in trenches not exceeding 1.5 m wide and n.exc. 1.5 m deep for foundation of poles/stay/cable etc including getting out in any type of soil complete all as specified and directed
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in hard and dense soil
Removing excavated material n.exc. 50m and depositing where directed at a level n.exc. 1.5 m above the starting point.
M&L for sand cushioning to cable with dry fine sand in trenches 8 cm below the cable and 15 cm above the cable after laying including gently punning around cable complete all as specified in SSR Part-I and directed.
M&L for bricks well burnt sub class 'B' laid in trenches flat with width equal to length of brick for cable protection laid across the cable complete all as specified and directed.
M&L for cable jointing kit for upto 1.1 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size :-
10 sqmm 2 core
16 sqmm 4 core
25 sqmm 4 core
50 sqmm 3.5 core
70 to 120 sqmm 3.5 core
240 to 300 sqmm 3.5 core
400 sqmm 3.5 core
Taking out old u/s XLPE cables of following sizes:- 6 sqmm 2 core, 1.1 KV
16 to 50 sqmm 4 core, 1.1 KV
95 to 400 sqmm 3.5 core, 1.1 KV
Taking down old u/s GI protection pipe of sizes 40 to 100 mm bore.
Labour & tools for horizontal boring for fixing GI pipe up to 100 mm through road / path / floor for passing UG cables as required.
S&F in repair MCCB 125 amp, 4 pole, 16 KA (Ics=100% Icu) thermally adjustable between 70% to 100% with spreader links on both sides as per Legrand cat ref no. 420016 or equivalent as approved by GE.
S&F in repair MCCB 160 amp, 4 pole, 16 KA (Ics=100% Icu) thermally adjustable between 70% to 100% with spreader links on both sides as per Legrand cat ref no. 420017 or equivalent as approved by GE.
S&F in repair MCCB 250 amp, 4 pole, 24 KA (Ics=100% Icu) thermally adjustable between 70% to 100% with spreader links on both sides as per Legrand cat ref no. 420219 or equivalent as approved by GE.
S&F in repair MCCB 63 amp, 4 pole, Icu 16 KA (Ics=100% Icu), electronic release and adjustable between 40% to 100% with spreader links on both sides as per Legrand cat ref no. 420013 or equivalent as approved by GE.
S&F in repair MCCB 400 amp, 4 pole, Icu 36 KA (Ics=100% Icu), electronic release and adjustable between 40% to 100% with spreader links on both sides as per Legrand cat ref no. 422063 or equivalent as approved by GE.
M&L for pipe in pipe chemical earthing with GI pipe electrode 3.0 m long having outer pipe dia 80 mm & inner pipe dia 50 mm duly filled with highly conductive and anti corrosive compound of required quantity having chemical composition Bentonite 40%, copper sulphate 20%, Gypsum 5%, Graphite 10%, Alum 5%, Zinc sulphate 10%, Aluminium sulphate 10% burried in ground by digging a bore of 150 mm dia surrounded by soil friendly backfill compound non soluble in water including connection with galvanised earth strip 32 x 6 mm, including excavation & earth work in any type of soil & PCC (1:3:6) type C-1 pit, RCC 1:2:4 type B-1, 40 mm thick cover reinforced with 8 mm dia MS bars 3 Nos both ways with lifting hook made out of 8 mm dia bar and testing on completion to achieve value not more than 2.0 ohm complete. (Note - GI strip size 32x6 mm upto 7.5 m included in the item).
Servicing/repairing of AMF system built in with DG set of any capacity including cleaning resetting / adjustment of relays, calibration of time delay relays, checking and replacing u/s diodes, resistors etc as required.
Supply and fix 4 pole Power contactor MCX 43, 240 V ,400 Amp alongwith complete new wiring in existing panel .
Taking out old XLPE cables of size 95 to 300 sq mm and rerouting the same within MH after disconnected from panel/pole including fresh connection in panel with suitable size of lugs,nut, bolts . Note excavation,returing filling shall be measured separetely.
Supplying, installation, testing & commissioning in renewal CPRI approved outdoor cubical type MV feeder pillar box suitable for 415V, 3 phase, 4 wire 50 Hz, AC supply system with short circuit withstand capacity 35 MVA for 1 second, IP 54 protection, fabricated in compartmentalized design from stainless steel sheet (SS 316) 2.0 mm thick totally enclosed, dust, weather & vermin proof, having TPN copper bus bars of rating 1.5 times that of controlling MCCB supported on 'F' class SMC insulators, bottom base channel of MS section not less than 75 mm x 40 mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25 mm x 5 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switchgears with required size copper bus bars and control wiring with minimum 1.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates including digital multi functional meter to measure voltage, current, PF & frequency and mounted on by making suitable PCC foundation, necessary inter connection including following controls :- Incoming:- One number MCCB 320 amp, 4 pole, Ics 36 KA, 415 volts, 50 Hz with electronic release adjustable between 40% to 100% against overload setting as per Legrand cat ref no. 422062 or equivalent as approved by GE Outgoing:- (i) Two numbers MCCB 100 amp, 3 pole, Ics 16 KA, 415 volts, 50 Hz, thermally adjustable between 70% to 100% against overload setting as per Legrand cat ref no. 420005 or equivalent as approved by GE (ii) Four numbers MCCB 63 amp, 3 pole, Ics 16 KA, 415 volts, 50 Hz, thermally adjustable between 70% to 100% against overload setting as per Legrand cat ref no. 420003 or equivalent as approved by GE
All as per item No 29 above but with following controls: Incoming:- One number MCCB 320 amp, 4 pole, Ics 50 KA, 415 volts, 50 Hz with electronic release adjustable between 40% to 100% against overload setting as per Legrand cat ref no. 422020 or equivalent in Schneider or Hager as approved. Outgoing:- (i) Ono numbers MCCB 200 amp, 3 pole, Ics 36 KA, 415 volts, 50 Hz, thermally adjustable between 70% to 100% against overload setting as per Legrand cat ref no. 420238 or equivalent in Schneider or Hager as approved. (ii)Three numbers MCCB 63 amp, 3 pole, Ics 16 KA, 415 volts, 50 Hz, thermally adjustable between 70% to 100% against overload setting as per Legrand cat ref no. 420003 or equivalent as approved by GE.
All as per item No 29 above but with following controls: Incoming:- One number MCCB 400 amp, 4 pole, Ics 50 KA, 415 volts, 50 Hz with electronic release adjustable between 40% to 100% against overload setting as per Legrand cat ref no. 422020 or equivalent in Schneider or Hager as approved. Outgoing:- (i) three numbers MCCB 200 amp, 3 pole, Ics 36 KA, 415 volts, 50 Hz, thermally adjustable between 70% to 100% against overload setting as per Legrand cat ref no. 420238 or equivalent in Schneider or Hager as approved. (ii)Two numbers MCCB 63 amp, 3 pole, Ics 16 KA, 415 volts, 50 Hz, thermally adjustable between 70% to 100% against overload setting as per Legrand cat ref no. 420003 or equivalent as approved by GE.
S&F thermoplastic, IP65 cable junction box of size 200 x 160 x 98 mm with metric knockouts on all sides for cable entry or Secure duly fitted with followings:- (a) DIN Rail (35 mm) - 1 No (b) ELMEX or equivalent make connector of 10 sqmm - 4 Nos (c) ELMEX or equivalent make end plate - 1 No (d) ELMEX or equivalent make end clamps - 2 Nos (e) MCB SP 6 amp, 10 KA, 'C' series - 1 No
S&F bollard LED garden light 8 watt 1 Mtr hight complete with required earth work, including fasteners, nuts, bolts, washers, copper connecting cable & PCC (1:2:4) type B 1 using 20 mm graded stone aggregate (size 0.40 m x 0.30 m x 0.45 m) complete. Make Haveels Cat part No: CONENXGBLS8WLED857PSYMTOPCM or equivalent as approved by GE.
M&L for submain wiring alongwith earth continuity conductor with PVC insulated FRLS multistranded copper conductor cable (Phase - Red, Neutral - Black, Earth - Green) drawing into and including concealed rigid non metallic PVC conduit, medium grade, ISI marked ivory colour along with accessories including taking down old of following nominal sizes :-
(a) 2x4 sqmm + 1x4 sqmm earth wire in 20 mm dia conduit.
(b) 2x6 sqmm + 1x6 sqmm earth wire in 25 mm dia conduit.
(b) 2x10 sqmm + 1x10 sqmm earth wire in 50 mm dia conduit.
(a) 4x4 sqmm + 1x4 sqmm earth wire in 50 mm dia conduit.
(b) 4x6 sqmm + 1x6 sqmm earth wire in 50 mm dia conduit.
(b) 4x10 sqmm + 1x10 sqmm earth wire in 50 mm dia conduit.
(e) 4x16 sqmm + 1x16 sqmm earth wire in 50 mm dia conduit.
S&F MCB distribution board, tripple pole and neutral (VTPN) powder coated CRCA steel sheet suitable for MCCB incomer upto 160 amp, 4 way, 415 volts, degree of protection IP 43 - IK- 09 with reversible double door, recess mounted, having 250 amp insulated tinned copper bus bar, neutral busbar, earth bar, din bar, detachable gland plate, interconnection, earthing connection, blanking plates in unused spaces as required. Make- Legrand cat ref no 507745 or equivalent as approved by GE. Note for MCBs & MCB DBs:- MCCBs, MCBs & MCB DBs shall be of the same make.
S&F MCBs of 'C' series having breaking capacity 10 KA, ISI marked including required wiring connections with copper lugs of suitable size provided in MCB DBs of following ratings:-
Single pole 6 to 32 amp. Make - Legrand cat ref no 408587 to 408595 or equivalent in Schneider or equivalent as approved by GE
Double pole 10 to 32 amp. Make - Legrand cat ref no 408631 to 408636 or equivalent in Schneider or equivalent as approved by GE
Double pole, 40 to 63 amp. Make - Legrand cat ref no 408637 to 408639 or equivalent in Schneider or equivalent as approved by GE
Four pole 40 to 63 amp. Make - Legrand cat ref no 408700 to 408702 or equivalent as approved by GE
M&L for brick work with sub-class 'B' bricks, straight or curved on plan to any radius in half brick thick walls built in cement mortar 1:4 and plastering 10 mm thick in CM 1:4 and 2 coats of white / colour washing to match the surface complete.
S& F in repair integral LED flood light 100 W 3000 K (WW) warm white with driver inside a PDC housing philips Cat part No CVP 182 LED 100 W CW FG S1 PSU GR or equivalent as approved by GE
M&L for cross arms, bracings, supports, clamp and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat one under coat and one finishing coat of paint complete.
M&L for spreading 40 mm graded stone aggregate deposited, spread and levelled in layers not exceeding 15 cm thick through out the sub station open areas complete.
Taking down any type HPSV fittings and Supply, installation, testing and commissioning of integral driver LED street light with a nominal system lumen output of 7200 lumens and a minimum system efficacy of 90 lumen/watt. The luminaire shall have rated system lifetime of 50,000 burning hours before reaching at L70. The luminaire should have cool white colour temperature (CCT > 5000K) and a CRI >70. The luminaire shall meet IP 66 rating & IK05 rating with THD < 20% and PF > 0.9. The luminaire housing should be made of pressure die cast aluminium with a flat glass optical cover. The total power consumption should not exceed 72W including driver. Make - Philips Greenline cat ref BRP410 LED CW 072 MR FG S1 PSU GR or equivalent as approved by GE
Renewal of street light bracket made of GI pipe light grade bend in shape of 40 mm dia, 1.5 m long and clamped with 2 pairs of 40 x 6 mm flat iron clamps, nuts / bolts / washers & painted with 2 coats of aluminium paint over a coat of red oxide primer on clamps complete.
Painting of street light poles 8.5 m / 9.0 long including street light brackets/clamps etc with best quality aluminium paint, making alternate black & white colour bands of 30 cms width upto a height of 1.5 m from pole coping with synthetic enamelled paint and writing pole numbers in black colour on yellow base complete.
M&L for retro reflective installation sign board of size 1.20 m x 0.90 m made of 18 gauge thick stainless steel sheet framed with 25 mm dia stainless steel pipe having front side entire surface fully bonded with retro reflective sheeting of high intensity prismatic grade having pressure sensitive adhesive, background in blue colour and writing matter in white colour tape mentioning text to be provided by department including fixing arrangement with two post of 50 mm dia round stainless pipe each 3.0 m long and erecting in PCC (1:3:6) with 40 mm nominal size stone aggregate flush with GL after below 0.50 m below GL complete.
M&L for of bus bar chamber pedestal type of size 75 cm x 60 cm x 40 cm out door dust & vermin proof front opening made out of 2.0mm thick MS sheet duly painted and consisting with aluminium bus bar 3 phase and neutral 4 Nos 400 Amp fixed on insulators and one MCCB TPN 200 Amp, 25 KA rupturing capacity including necessary fixed in PCC 1:3:6 using 20 mm graded stone aggregate including danger plate etc complete.
M&L for steel tubular swaged pole 8.5m long type 410 SP-22 with cast iron or welded MS base plate including nuts/ bolts/washers etc conforming to IS-2713 (Part I to III) of 1980 and comprising of (a) Excavation in post holes in any type of soil not exceeding 0.5 cum each, getting out returning filling in and ramming earth in layers not exceeding 25 cm watering and disposal of surplus soil to a distance not exceeding 50 m and making good surface. (b) PCC (1:4:8) type D-2 using 40 mm graded store aggregate in base (0.60 m dia x 0.15 m height). (c) PCC (1:3:6) type C-2 using 40mm graded stone aggregade in foundation filling (0.60 m dia x 1.5 m height). (d) PCC (1:2:4) type C-2 using 40mm graded stone aggregade in foundation filling (0.60 m dia x 0.45 m height). (e) Pole cap 0.30 m long externally fitted on pole top duly welded with a light grade ISI marked 40 mm GI pipe bracket 1.5 m long for mounting street light fitting.
Supply only ACB 800 Amp 415 Volt 50/60 Hz, Icu 50 Ka and lcs : 100 % Icu, neutral overload protection safety interlock and drawout type. Make L&T Cat part No CN-CS 800 SI
M&L Machine pressed precast cocrete interlocking paver block any shape and size confirming to IS 15658-2006 of 80 mm thickness, M-40 Grade, with grey cement over and including 25mm thick sand cusion complete all as directed.
Supplying, laying, jointing and testing ductile iron pressure pipe centrifugally cast ISI marked with socket and spigot ends with jointing materials conforming to IS 8329/2000 standard length , of k7 specification with out zinc coating laid in trenches, under floor,road etc of following sizes :-
100 mm bore
150 mm bore
M & L for sluice valves of undermentioned type,size and class with cast iron body with forged brass spindle, non rising type and cast iron wheel head, both ends flanged, IS-14846 marked comlete with neoprene rubber gasket , nuts,bolts & washers etc of suitable size complete all as specified and directed including taking down the old sluice valve :-
100 mm bore, class PN 1.0
150 mm bore, class PN 1.0
Construction to brick masonary valve pit/ chamber of size 900x900x900mm (internal dimensions and including necessary excavation and earth work, PCC, plaster in CM 1:6 on inside and out side (above ground ), angle iron frame 40x40x5mm size including fabrication work, hold fast, MS sheet cover 3mm thick, duly painted with one coat of black bituminous paint of approved quality, handle and locking arrangements complete all as specified and directed
Supply and fixing in repair MS saddle piece made out of MS flat iron 50x6mm complete with GI socket welded it on one FI strip suitably positioned at the centre of pipe complete with MS nuts, bolts, washers (02 Nos) and rubber packing for branch connection complete for following sizes of pipe :-
100mm bore.
150mm bore.
Material and labour for cutting of bituminous road or any type of floor for laying of pipe not exceeding 1.5 mtr deep including refilling /with material and watering well ramming/compacting and making good with PCC 1:2:4 type B-1, 10 cm thick complete all as specified and directed by Engr-in charge
M&L ductile iron fittings, IS-1538 marked viz bends, tapers, reducers, tee pieces (single or double branch) any type, angle / radius and straight connecting pieces suitable for size of pipe upto 150 mm bore, complete all as specified and directed.
Cutting of CI/DI pipes in position for insertion of new tees, branches etc of size 100 mm bore.
Cutting of CI/DI pipes in position for insertion of new tees, branches etc of size 150 mm bore.
M&L for gun metal gate valve/forged valve with iron wheel head, screwed both ends for jointing iron pipes, non rising, forged brass spindle class-1, IS-778 marked of following sizes including taking down old unsv :- 15 mm bore
20 mm bore
25 mm bore
50 mm bore
M&L for galvanised steel tubes "medium grade " with all fitting (ISI marked) and fixed complete to walls and ceilings or laid in floors/trenches and under road, complete all as specified and directed of the following sizes :-
M&L for PCC (1:3:6) type C2 (using 40 mm graded aggregate) for making platform in foundation etc including necessory form work, compaction etc all as specfied and directed by Engineer-in-Charge.
Replacement of existing U/S level indicator for OH water tank/Underground sump . S&F electronic water level indicator operating on magnetic float system to indicate 4 levels of water in 6 mtr deep water tank including wiring from single phase power point complete with rain water guard on mounting housing recommended by manufature cable top to grround of tank (Approx 40 mtr) complete all as specified and directed Make delta Modle No DOP-B07S411 or new upgraded DOP-107CV or equivalent as approved by GE
Schedule of Credit
S.R.Enterprises
M/S Anil Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .