Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Fee/PreQual/Technical | Admitted-Fee/PreQual/Technical |
| 2 | Admitted-Fee/PreQual/Technical 302 MILINDA MANOR 2 RNT MARG INDORE INDORE MADHYA PRADESH 452001 | INDORE | MADHYA PRADESH | 452001 | Admitted-Fee/PreQual/Technical |
| 3 | Admitted-Fee/PreQual/Technical D 4 276 KH NO 424 FIRST FLOOR BHAGEL SADAN BANK COLONY ROAD MANDOLI EXTN NEAR JAIL BOUNDARY DELHI 110093 | DELHI | DELHI | DELHI | 110093 | Admitted-Fee/PreQual/Technical |
Tender Value
₹3.9 Cr
EMD Value
₹7.8 L
Closing Date
28 Aug 2026, 5:00 pmClosed
MS KGS 1and2
Kaiga Generating Station NPCIL Kaiga 581400
Supply, Removal and Installation of Thermal Insulations on Pipes, Equipments and Supports. Supply, Fabrication and Installation of GI ducts. Radiological Shielding of hot spots at Kaiga Generating Station 1and2
2026_NPCIL_286608_1
CPPP/2026/123
Open Tender
Miscellaneous Works
Item Rate
730 days
Kaiga Site
Refer NIT
4 documents required · 4 mandatory
₹0
₹7.8 L
In charge, CandMM-(WG) Kaiga Site
31 Aug 2026
7 Aug 2026
31 Aug 2026
7 Aug 2026
28 Aug 2026
18 Aug 2026
7 Aug 2026 - 14 Aug 2026
17 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Providing and fixing cold insulation on pipes, ducts and equipment using SE(Self extinguisher) type polysterene pipe sections/slabs confirming to IS 4671/3346 of minimum density 16Kg/m3 and for supports 22Kg/m3, hot bitumen 85/25 grade, covering with cement sand plaster including all necessary fittings and fixtures etc.,as directed by the engineer. 25 mm thick with cement sand plaster in controlled areas. | - | SQM | 930 | - |
| 2 | Providing and fixing cold insulation on pipes, ducts and equipment using SE(Self extinguisher) type polysterene pipe sections/slabs confirming to IS 4671/3346 of minimum density 16kg/m3 and for supports 22kg/m3, hot bitumen 85/25 grade, covering with cement sand plaster including all necessary fittings and fixtures etc.,as directed by the engineer: 50 mm thick with cement sand plaster in controlled areas. | - | SQM | 1,118 | - |
| 3 | Providing and fixing cold insulation on pipes, ducts and equipment using SE(Self extinguisher) type polysterene pipe sections/slabs confirming to IS 4671/3346 of minimum density 16kg/m3 and for supports 22kg/m3, hot bitumen 85/25 grade, covering with cement sand plaster including all necessary fittings and fixtures etc.,as directed by the engineer. 100 mm thick with cement sand plaster in controlled areas. | - | SQM | 1,515 | - |
| 4 | Providing and fixing cold insulation on pipes, ducts and equipment using SE(Self extinguisher) type polysterene pipe sections/slabs confirming to IS 4671/3346 of minimum density 16kg/m3 and for supports 22kg/m3, hot bitumen 85/25 grade, including all necessary fittings and fixtures etc.,as directed by the engineer. 50 mm thick without cladding in controlled areas. | - | SQM | 612 | - |
| 5 | Removal of old aluminium sheets without damaging the sheet numbering,storing and sorting at a proper place for easy retrival including all necessary tools, tackles, labour etc., in controlled areas. | - | SQM | 163 | - |
| 6 | Removal of old rockwool matteress/performed sections without damaging the wool storing and sorting at a proper place including all necessary tools,tackles,labour etc., in controlled areas. | - | SQM | 201 | - |
| 7 | Removal of cold insulation as directed by engineer, collecting in to bags, getting it surveyed from HPU and disposing as directed by the engineer. | - | SQM | 201 | - |
| 8 | Refixing of old LRB mattress /sections of various thickness packed and fully encased on both sides with new close twill weave glass clothe (fire proof 7 mil thick) and providing necessary mesh,binding wires/bands and all ancillaries etc., as directed by the EIC in controlled areas. | - | SQM | 374 | - |
| 9 | Refixing of old LRB mattress /sections by providing necessary binding wires, bands, mesh etc.,as directed by the EIC in controlled areas. | - | SQM | 164 | - |
| 10 | Refixing of old aluminim sheets including removing graffite /damaged portion of sheets, providing necessary screws,bands etc., complete | - | SQM | 124 | - |
stage.html
html • 0.02 MB
tech_bid_open.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 2.33 MB
Tendernotice_2.pdf
PDF • 31.37 MB
Tendernotice_3.pdf
PDF • 4.17 MB
RevisedTenderdocument.pdf
Tender Documents • 31.35 MB
RevisedNIT.pdf
Tender Documents • 2.31 MB
BOQ_334523.xls
BOQ • 0.39 MB
Additionaldocument.pdf
Additional Documents • 4.15 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .