Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹35.4 LAccepted-AOC | L1 | Accepted-AOC Lowest bid | |
| 2 | L2₹35.8 L+₹47,206.20 (1.34%)Accepted-AOC | L2 | Accepted-AOC Other than lowest bid | |
| 3 | L3₹43.4 L+₹8.1 L (22.8%)Accepted-AOC | L3 | Accepted-AOC Other than lowest bid |
Tender Value
Refer Docs
EMD Value
₹40.4 L
Closing Date
23 Sept 2024, 6:00 pmClosed
GE 874 EWS
GE 874 EWS C/O 56 APO
PROVN OF DG SETS AND SEPTIC TANK UNDER AOR OF GE 874 EWS
2024_MES_666096_2
GE 874/EWS-50/2024-25
Open Tender
Civil Works
Works
90 days
Kupwara
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE 874 EWS C/O 56 APO
₹40.4 L
26 Oct 2024
2 Sept 2024
25 Sept 2024
2 Sept 2024
23 Sept 2024
10 Sept 2024
Amount
Excavating over areas, exc 1.5 m deep and getting out soft soil complete all as specified and directed.
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out soft/loose soil complete all as specified and directed.
M & L for PCC 1:3:6 Cement concrete type C-2 (using 40 mm graded stone aggregate) in foundations, filling and mass concrete complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25cm in hard/dense soil complete all as specified and directed.
Removing excavated material (soil) n. exc 50m and deposited where directed at a level n exc. 1.5m above the starting point complete all as specified and directed.
M & L for brickwork with subclass ‘B’ bricks, straight or curved on plan exc 6m mean radius built in in CM 1 :4 complete all as specified and directed.
M & L for Rendering 15 mm thick on fair faces of brick work or concrete surfaces rendering is to be finished even and smooth (without using extra lime or cement) as specified
M & L for PCC 1:3:6 type C1 (using 20 mm graded crushed stone aggregate) in lintels upto 1.5m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs not provided for, water troughs and the like including weathering, slightly rounded or chamfered angles and throating complete all as specified and directed.
M & L for cement concrete 1: 3: 6 type C-2 in surface channels using 40 mm graded stone aggregate and drains including extra for forming fair finished drain or channel 30 cm inner girth in cement concrete, using extra cement, including forms, moulds, mitred/stopped ends etc. complete all as specified and directed.
M & L for precast cement concrete 1:2:4 type B -1 using ( 20 mm Graded crushed stone aggregate) in landings, cover slabs (for man holes etc.) chullah hoods, chajjas, water troughs, mangers, shelves and similar articles with plain faces complete all as specified and directed.
M & L for RCC 1:1.5:3 type A-1 (using 20 mm graded crushed stone aggregate) Slabs supported on walls, beams and columns in floors, roofs, landings, balconies, canopies, deck slabs and in shelves and the like complete all as specified and directed.
M & L for RCC 1:1.5:3 type A-1 (using 20 mm graded crushed stone aggregate) Slabs supported on walls beams and columns in floors, roofs, landings, balconies, canopies, deck slabs and in shelves and the like complete all as specified and directed.
M & L for rough finished flat formwork to edges of concrete flats, treads, breaks in floors, window cills, concrete railings, openings in concrete walls, floor and roofs n exc 20 cm wide and sides of RCC/ PCC bands in walls, horizontal or sloping and similar work exc 10cm but n exc 20cm wide complete all as specified and directed.
M & L for MS TMT bars Mild steel bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed.
M & L for cement concrete bed (1:4: 8) type D-2 (using 40 mm graded stone aggregate) to drain pipes including packing under, and haunching against the sides of pipes after they are laid and tested; in for 150 mm dia SGSW pipe complete all as specified and directed.
M & L for 150 mm dia Salt -glazed stoneware drain pipes laid in trenches and jointed complete all as specified and directed.
M & L for cutting into existing manholes for using 150 mm dia of pipe internal dia connecting new drains, making good to pipe and rendering, cutting out existing benching for and forming branch channel (1/2 round or 3/4 section) in cement concrete 1:2:4 type B-l smooth finished, and reforming benching as required complete all as specified and directed.
PVC (SWR) using 75 mm dia pipes single socketed in any length with rubber ring joints fixed to walls complete all as specified and directed.
S & F 75 mm bore PVC (SWR) vent cowl complete all as specified and directed.
M&L for construction of Soakage well, of size 2.4 m dia at bottom and 3 m total depth complete all as specified and shown on drawing No. CESZ-TD-/2015 sheet No 1/3 & 3/3 dated 22 Feb 2015 (Revised dt 21 Mar 2015) and specified in particular specifications.
Supply, installation, commissioning and testing of 20 KVA Liquid (Water) Cooled silent DG Set ( CPCB IV + NORMS COMPLIANCE or Latest CPCB Norms) comprising of Liquid Cooled Diesel Engine Model developing 25.5 BHP @1500 RPM 20 KVA Alternator rated at Three Phase, 415 Volts, 50 Hz, 0.8 PF @ 1500 RPM both mounted and aligned on a common MS Base frame complete with MS fuel Tank, Manual Control Panel, Residential exhaust silencer, AVM pads fitted on base frame, 01 Nos 12 Volts DC Battery, battery leads, 1st fill of Lube oil all housed ,switch gear for automatic starting on main failure, in sound proof acoustic enclosure protected with asbestos rope independently supported from engine to outside power house up to 1 mtr, AVM pads foundations as per manufacturer design battery start with suitable size of cable for connecting up to panel board . DG Set should be capable of operating in temperature range (-25* C to + 35*C) fitted with Cold starting kit with and including the following for each DG set.
(A) Prime mover Vertical diesel engine of suitable capacity water cooled closed circuit as per BS-649 or IS-10002 direct injection type turbo charged electric starting system having rated speed 1500 RPM. The DG Set shall be capable of running 24hrs continuously with 10% over loading for one hrs continuously in every 12 hrs as per BS -649. Engine shall be equipped with all standard fitting and mounted on common base frame with following fittings. (a) RPM cum hour meter (b) Battery charging Ammeter ( c) ignition key and starting with push button switch (d)Lubricating Oil pressure gauge (e) Electronic governor controlling Oil temperature gauge (g) 12/24 Volts starting equipment comprising of the following fittings (i)12/24 V Battery (ii)Battery charging alternator (iii) Self-starting of suitable capacity (iv) Battery leads of copper cable with brass thimbles and terminals. (v)starting gear engine.
(B) Alternator. Alternator rating 20 KVA,3 phase,4wire,415 Volts 50C/S supply Derated at site condition i.e 1800 mtr above MSL 0.8 Pf running @ 1500 RPM self-excited, self-regulated, mounted on strong fabricated steel frame, suitable for mounting on a permanent foundation to be coupled with above engine. The alternator shall be confirming to BS-2613 or IS -4722.
(D) Other fittings (i) Battery charger having electric circuit consisting of triodes , capacitor and resistances etc. The battery charger should be able to charge the battery at all times whenever the electric supply given to battery charger through control panel or electric power point.
(ii) In built Fuel tank of suitable capacity as per manufacturers instructions capable for12 hrs running of DG Set inside the canopy base with all connecting pipes up to fuel pump and including oil level indicating gauge drain air vent plug etc. (Note: The rates of this items including the commissioning & testing complete (POL for DG Set testing will be issued by concern unit)
M & L for Earthing complete with galvanised steel earth plate electrode of size 60×60cm×6mm thick surrounded by mixture of charcoal and salt in alternate layers, buried directly in ground vertically in a pit of depth not less than 2.25 metres deep below ground level with top edge of the plate not less' than 1.5 metres below normal ground level, connected to equipment by using GI strips of size 32 x 6mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron all as shown in electrical plate No.5 of MES schedule and connected to earthing test point all as specified and directed including earth pit of size 30cm x 30cm x 45 cm made of PCC 1:3:6 and PCC 1:2:4 cover, funnel, GI Tubing etc & testing on completion all as specified. Note :- The unit rate includes the cost of excavation & earth work in any type of soil, charcoal and salt in alternate layers, 20mm bore GI Pipe (med grade) for watering 40mm GI protection pipe (light grade) funnel, wire mesh, lugs, PCC 1:2:4 type B1 chamber in cement concrete 50mm thick precast RCC M-25 (design mix) cover duly reinforced with XPM (weight not less than 3kg/sqm) and CI frame etc and including provision of test point, connecting to test point and testing on completion etc complete all as specified. The unit rate also includes earthing lead and protection pipe up to 7.5mtr from top of earth plate.
Supply and Laying, jointing and testing XLPE insulated armoured heavy duty electric cable with aluminium conductor ,1100 volts grade, cross section area 50 Sqmm 3.5/4 core complete laid in trenches, ducts or fix to pipe, on walls, poles complete all as specified and directed. Note: - (a) Earth work shall be measured and paid separately.
Supply and laying dry river sand for cable cushioning in trenches to required width at bottom and top of cable including spreading levelling watering and consolidation complete all as specified and directed. Note: -Punned thickness only shall be measured and paid.
Supply and laying old size brick covering with width equal to length of brick as the mechanical protection to cable with well burnt sub class 'B' laid in trenches flat complete all as specified and directed.
Supply and fixing tubes light grade GI tubing 80 mm dia with all fitting laid in trenches complete all as specified and directed.
Supply, installing, testing and commissioning, factory made and tested (prototype having been CPRI type test certified), LT Panel, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated copper bus bars of Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, externally powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, with double door shutter and locking arrangement (including provision of 65mm Godrej (Freedom) lock with 2 keys, internal wiring 2.5 Sqmm with PVC insulated, solid copper conductor, FRLS cables, IS-694 marked of adequate size including the provision of space to accommodate the under mentioned items. The scope of work includes the following:-
(a) Incoming
(i) MCCB 4 pole, 415 volts AC grade, 63 Amps rating and 36 KA rupturing capacity complete - 01 Nos.
(ii) Voltmeter 0-500 volts, square, 144 mm, digital type - 01 No
(iii) Ammeter size 144 mm, square dial, digital type, - 01 No
(iv) LED Indicating lamps: 01 set of three
(vi) Secure 3 Phase, 1 Element, 4 Wire 440 V Digital Power Factor Meter .01 Nos
(vii) Change over 63 A 4 Pole: 01 Nos
(viii) Current & Potential Transformer as per manufacturer design: 01 Nos
(b) Outgoing
(i) MCCB 4 pole, 415 volts AC grade, 40 Amps rating and 25 KA rupturing capacity complete - 02 Nos.
(c) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45cm above the nearest road level.
M & L for excavating in post holes (or similar holes) each n exc 0.5 cu. m, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm
M & L for Cement concrete in foundations, filling and mass concrete as type C-2 1:3:6 40mm graded aggregate complete all as specified and directed.
S & F Second class soft-wood in scantling complete all as specified and directed.
M & L for Pre- painted galvatume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self-tapping screws complete all as specified and directed.
Supplying, installing, commissioning and testing of diesel engine driven generating set with canopy as per , central pollution control board norms,(CPCB IV+ NORMS COMPLAINCE ) developing 10.74 BHP @1500 RPM , 230 Volts 1 phase, 50Hz 0.8 p.f @ 1500 RPM supply complete with suitable for giving an output of 7.5 KVA conforming to IS-1601 ,between temperature range - 15°C to +38°C (at Kupwara area of J&K ), Humidity 60% water/air cooled , A-I governing system with & alternator of suitable capacity and RPM coupled with each other & capable of taking 10% over load for one hour on every 12 hours and aligned on a common MS base frame,1 No 12 Volts DC Battery, Battery leads, 1st fill of lube oil all housed in sound proof acoustic enclosure complete all as specified and directed.
Supply and Laying, jointing and testing XLPE insulated armoured heavy duty electric cable with aluminium conductor ,1100 volts grade, cross section area 10 Sqmm 2 core complete laid in trenches, ducts or fix to pipe, on walls, poles complete all as specified and directed.
Supply and fix Manual operating ON LOAD change over switch 415 V in sheet steel enclosures 4 pole of capacity up to 63 Amps complete all as specified and directed.
m/s mohd saleem and co (BID ID -3096397)
M/S MOHD MAQBOOL RATHER (BID ID -3096950)
Bidder Name
M/S ABDUL AZIZ MIR
m/s mohd saleem and co
M/S MOHD MAQBOOL RATHER
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .