Tender Value
₹1.8 Cr
EMD Value
₹3.7 L
Closing Date
21 Feb 2026, 2:00 pmClosed
General Manager, Zone-1, Prayagraj.
General Manager, Zone-1, U. P. Projects Corporation Ltd. 230 /1A, Mehdaury, Telirayganj District-Prayagraj.
Construction of New Ward of 30 Beds on the First Floor in the obstetrics and Gynecology department in the Swaroop Rani Nehru Hospital campus affiliated to the Government Medical College, Prayagraj (U.P.)
2026_UPPRC_1116223_1
97/UPPCL/GM-1/2025-26/E-TENDER Dated-04.02.2026
Open Tender
Civil Works - Buildings
365 days
District-Prayagraj (U.P.)
Please refer Tender documents.
2 documents required · 2 mandatory
₹17,700
₹3.7 L
20 Mar 2026
16 Feb 2026
21 Feb 2026
16 Feb 2026
21 Feb 2026
16 Feb 2026
Construction of New Ward of 30 Beds on the First Floor in the obstetrics and Gynecology department in the Swaroop Rani Nehru Hospital campus affiliated to the Government Medical College, Prayagraj (U.P.)
(A) CIVIL WORK
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. All works above plinth level upto floor V level. Concrete of M30 grade with minimum cement content of 350 kg /cum
Centering and shuttering including strutting, propping etc. and removal of form for :
Suspended floors, roofs, landings, balconies and access platform
Lintels, beams, plinth beams, girders, bressumers and cantilevers
Add for using extra cement in the items of design mix over and above the specified cement content therein. In SUPERSTRUCTURE
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level & above plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. IN SUPERSTRUCTURE
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand)
Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level. in all shapes and sizes in : Cement mortar 1:4 (1 cement : 4 coarse sand)
Providing and fixing ISi marked oxidised M.S. sliding door bolts with nuts and screws etc. complete (Copper oxidised as per IS 1378)
Providing and fixing ISi marked oxidised M.S. tower bolt black finish, (Barrel type) with necessary screws etc. complete (Copper oxidised as per IS 1378)
Providing and fixing ISi marked oxidised M.S. handles conforming to IS:4992 with necessary screws etc. complete (Copper oxidised as per IS 1378)
Providing and fixing carbon steel galvanised ( minimum coating 5 micron) dash fastener of 10 mm dia double threaded 6.8 grade (yield strength 480 N/mm2), counter sunk head, comprising of 10 mm dia polyamide PA 6 grade sleeve, including drilling of hole in frame , concrete/ masonry, etc. as per direction of Engineer-in-charge.
Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and with decorative both side high pressure laminated sheet of plain / wood grain in gloss / matt / suede finish with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approved quality of 1.0 mm thick including 32x5 mm teak wood lipping on edges of shutters. 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws
Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and with decorative ONE side high pressure laminated sheet of plain / wood grain in gloss / matt / suede finish with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approved quality of 1.0 mm thick including 32x5 mm teak wood lipping on edges of shutters. 35 mm thick single leaves
Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length (hold fast lugs or dash fastener shall be paid for separately).
Ventilator Casement window single panel with or without fixed panel with S.S. 304 friction hinges as per size and weight of sash, single point locking zinc alloy (zamak) powder coated handles.Using R2 series with frame (39 mm & above) x (39 mm & above) & sash /mullion (39 mm & above) x (60 mm & above). (Height upto 1.2 metre)
Providing and fixing M.S. Tubular frames for doors, windows, ventilators and cupboard with rectangular/ L-Type sections, made of 1.60 mm thick M.S. Sheet, joints mitred, welded and grinded finish, with profiles of required size, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer. Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block 15x10x10 cm of C.C. 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)
Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all necessary fittings complete, including applying a priming coat of approved steel primer.Using M.S. angels 40x40x6 mm for diagonal braces
Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-incharge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.).
Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured).
Providing and fixing fly proof galvanised M.S. wire gauze to windows and clerestory windows using galvanised M.S. wire gage with average width of aperture 1.4 mm in both directions with wire of dia. 0.63 mm.With 12 mm mild steel U beading.
Providing and laying "brick coba" 12 mm thick laid with M-150 class brick bat coba 7.50 cm thick with gap of 15 mm to each other, over 20 mm thick base of cement mortar 1:4 cement and coarse sand mixed with water proofing compound spreading cement slurry mixed with aerelic cement concrete water proofing compound filled gaps of coba & top of coba mortar mixed with water proofing compound in 1:4 cement and coarse sand mortar finfished smooth & top mashed false square 30 x 30 cm and side wall parapet shall be monotythic plaster wall upto 30 cm higher and junction and corner shall be rounded by brick ballast cement and coarse sand masonary coba with top finished plaster mixed with acetic water proofing compound @ 2% by weight & including S/o all material, labour, T&P etc complete for proper completion of work.
12 mm cement plaster of mix : 1:6 (1 cement: 6 coarse sand)
Making grooves 10 to 12 mm wide x 8 mm deep in plaster the all or in ceiling vertically of horizontally as required.
Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections.
Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only . Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily. Glazed Vitrified tiles Matt/Antiskid finish of size: Size of Tile 600 x 1200 mm
Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), Jointing with grey cement slurry @ 3.3 kg/sqm including pointing the joints with white cement and matching pigment etc., complete.
Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
62 mm thick cement concrete flooring with concrete hardener topping, under layer 50 mm thick cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1 :2 (1 cement hardener mix : 2 graded stone aggregate, 6 mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacture's specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete.
Distempering with oil bound distemper of approved brand and manufacture and of required shade on undecorated wall surface to give an even shade over and including a priming coat with cement primer of approved brand and manufacture such as Berger, J&N Shalimar, Asian Paints after thoroughly brushing the sufface free from mortar dropping and other forein matter and also including prepairing the surface even with Plaster of Paris or approved synthetic material and sand papered smooth including cost of all material
Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete
Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade : New work (Two or more coats applied @ 1.43 ltr/ 10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm)
Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete
Painting two coats over priming coat on steel & other metal surfaces up to 10 cm width or sq,mt in areas with superior synthetic enamel such as Luxol-3 Hi-gloss apcolite superlac, Dulux specified finishing to give an even shade & incl. cleaning the surface of all dirt, dust & other foreighn matter sand preparing and knotting incl. cost of all etc. required for proper completion of work.
Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete.
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 110 mm diameter
Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion.
Coupler 110 mm
Bend 87.5° 110 mm bend
Shoe (Plain) 110 mm Shoe
Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. 110 mm
Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams.
Furniture work
LIFT CONSTRUCTION WORK
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. All kinds of soil
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 and for all lift.
Excavating, supplying, stacking and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in foundation trenches, plinth, sides offoundation etc. complete for all lift.
Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete.
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources)
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. All works upto plinth level. Concrete of M30 grade with minimum cement content of 350 kg /cum
Centering and shuttering including strutting, propping etc. and removal of form for :
Foundations, footings, bases of columns, etc. for mass concrete
Lintels, beams, plinth beams, girders, bressumers and cantilevers
Columns, Pillars, Piers, Abutments, Posts and Struts
Add for using extra cement in the items of design mix over and above the specified cement content therein.
Diluting and injecting chemical emulsion for Pre-CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) : Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor : With Chlorpyriphos/Lindane E.C. 20% with 1% concentration
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level & above plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. In SUBSTRUCTURE
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand)
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. All works above plinth level upto floor V level. Concrete of M30 grade with minimum cement content of 350 kg /cum
Centering and shuttering including strutting, propping etc. and removal of form for :
Lintels, beams, plinth beams, girders, bressumers and cantilevers
Columns, Pillars, Piers, Abutments, Posts and Struts
Add for using extra cement in the items of design mix over and above the specified cement content therein. In SUPERSTRUCTURE
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level & above plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. IN SUPERSTRUCTURE
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand)
Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level. in all shapes and sizes in : Cement mortar 1:4 (1 cement : 4 coarse sand)
Providing and laying in situ seven course water proofing treatment with APP (Atactic Polypropylene) modified Polymeric memberane over roof consisting of first coat of bitumen primer @ 0.40 litre per sqm, 2nd, 4th & 6th courses of bonding material @ 1.20 kg/sqm, which shall consist of blown type bitumen of grade 85/25 conforming to IS : 702, 3rd and 5th layers of roofing membrane APP modified Polymeric membrane 2.0 mm thick of 3.00 Kg/sqm weight consisting of five layers prefabricated with centre core as 100 micron HMHDPE film sandwiched on both sides with polymeric mix and the polymeric mix is protected on both side with 20 micron HMHDPE film. 7th, the top most layer shall be finished with brick tiles of class designation 10 grouted with cement mortar 1:3 (1 cement : 3 fine sand) mixed with 2% integral water proofing compound by weight of cement over a 12 mm layer of cement mortar 1:3 ( 1 cement : 3 fine sand) and finished neat (item of laying brick tiles shall be paid for separately).
12 mm cement plaster of mix : 1:6 (1 cement: 6 coarse sand)
Distempering with oil bound distemper of approved brand and manufacture and of required shade on undecorated wall surface to give an even shade over and including a priming coat with cement primer of approved brand and manufacture such as Berger, J&N Shalimar, Asian Paints after thoroughly brushing the sufface free from mortar dropping and other forein matter and also including prepairing the surface even with Plaster of Paris or approved synthetic material and sand papered smooth including cost of all material
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade : New work (Two or more coats applied @ 1.43 ltr/ 10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm)
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete.
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 110 mm diameter
Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion.
Coupler 110 mm
Bend 87.5° 110 mm bend
Shoe (Plain) 110 mm Shoe
Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. 110 mm
Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams.
(B) PLUMBING WORK
SUB HEAD-I-SANITARY INSTALLATIONS
Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required : W.C. pan with ISI marked white solid plastic seat and lid
Providing & fixing toilet paper holder C.P. brass
Providing and fixing 8 mm dia C.P. / S.S. Jet with flexible tube upto 1 metre long with S.S. triangular plate to Eureopean type W.C. of quality and make as approved by Engineer - in - charge.
Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require: White Vitreous China Wash basin size 630x450 mm with a single 15 mm C.P. brass pillar tap
Providing and fixing CP Brass 32mm size Bottle Trap of approved quality & make and as per the direction of Engineer-in-charge.
Providing and fixing PTMT towel ring trapezoidal shape 215 mm long, 200 mm wide with minimum distances of 37 mm from wall face with concealed fittings arrangement of approved quality and colour, weighing not less than 88 gms.
Providing and fixing C.P. brass shower rose with 15 or 20 mm inlet : 100 mm diameter
Providing and fixing CP Brass Single lever telephonic wall mixer of quality & make as approved by Engineer in charge. 15 mm nominal dia
Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. 600 mm long towel rail with total length of 645 mm, width 78 mm and effective height of 88 mm, weighing not less than 190 gms.
Providing and fixing PTMT soap Dish Holder having length of 138mm, breadth 102mm, height of 75mm with concealed fitting arrangements, weighing not less than 106 gms.
Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS 8931 (including angle valve for WC flushing cistern, jet & kitchen sink) 15 mm nominal bore
Providing and fixing uplasticised PVC connection pipe with brass unions : 45 cm length 15 mm nominal bore
Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.
Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 : 15mm nominal bore
Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms. 15mm nominal bore
Providing and fixing white vitreous china flat back half stall urinal of size 580x380x350 mm with white PVC automatic flushing cistern, with fittings, standard size C.P. brass flush pipe, spreaders with unions and clamps (all in C.P. brass) with waste fitting as per IS : 2556, C.I. trap with outlet grating and other couplings in C.P. brass, including painting of fittings and cutting and making good the walls and floors wherever required : Range of three half stall urinals with 10 litre P.V.C. automatic flushing cistern
SUB HEAD-II-WATER SUPPLY
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge..Internal work - Exposed on wall
15 mm dia nominal bore
20 mm dia nominal bore
25 mm dia nominal bore
32 mm dia nominal bore
40 mm dia nominal bore
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc.
15 mm dia nominal bore
20 mm dia nominal bore
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. External work
40 mm dia, nominal bore
50 mm dia, nominal bore
65 mm dia, nominal bore
Providing and fixing of gun metal gate valve with CI wheel of approved quality (screwed ends)
25mm dia, nominal bore
32 mm dia, nominal bore
40 mm dia, nominal bore
Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank.
SUB HEAD : III - ROOFING
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS :13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 110 mm dia (for rain water)
Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion.
Single Push Fit Coupler 110 mm dia
Single tee with door 110x110x110 mm
Plain bend 87.5 deg 110 mm dia
Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. 110 mm dia
Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete.
SUB HEAD : IV - INTERNAL DRAINAGE
Providing, fixing, jointing and testing, uPVC SWR pipes, - type B conforming to IS : 13592 to wall, ceiling and floor, approved quality, complete, for soil, waste & rain water drain including pushfit jointing with seal ring. (i) Single socketed pipes. Soil, Waste & Rain water Pipe
160 mm (For Rain Water)
Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for unplasticised Rigid PVC pipes including jointing with seal ring leaving 10 mm gap for thermal expansion.
Bend without door (87.5°)
110mm bend
75 mm bend
Bend without door (45°)
Y' Fitting without door
Reduced 'Y' Fitting without door 100mm x 75mm
Single Tee without door
Single Tee with door 110mm
Reduced Tee with door 110mm x 75mm
Coupler
Clean Out Plug (COP) 110mm
Vent Cowl 110mm
Providing, fixing, jointing and testing, unplasticized PVC pipes - 10 kg/cm2 confirming to IS : 4985 to wall, ceiling and floor, approved quality, complete, for waste water drain including jointing with rubbering/solvent/solution and airtight joints, etc.
For Wash basin & Urinal 32mm dia. pipe
Elbow (90°) 32mm
Elbow (45°) 32mm
Providing, fixing, jointing and testing , of PVC Multi Floor Trap with jali of minimum 50 mm water seal, making necessary cutting in slab or floors and making good including supports with cement concrete 1:3:6 complete as approved by Engineer-in-Charge. 110mm x 75mm x 50mm/40mm (Toilet)
Providing, fixing, jointing and testing , of PVC Nahani Trap without jali of minimum 50 mm water seal, making necessary cutting in slab or floors and making good including supports with cement concrete 1:3:6 complete as approved by Engineer-in-Charge. 110mm x 75mm (Toilet)
(C) ELECTRICAL WORK
Point Wiring
Wiring point for Light with 1.5sq. mm. FR PVC insulated multistrand single core copper cable in PVC conduit with 1.5 sq.mm. FR PVC-insulated multistrand Copper conductor cable as earth wire drawn in side the conduit. Add for light/fans with moduler type switch.
Wiring point for two ways light point with 1.5 sq.mm FRLSH PVC insulated multistrand single core copper conductor cable in Surface/Recessed medium class PVC conduit 2 way modular switch modular plate suitable G.I. Box and earthing the point with 1.5 seq mm FRLS PVC insulated Copper conductor Single core cable etc. as required.
Wiring point for Fan/light duty exhaust fan with 1.5sq. mm. FR PVC insulated multistrand single core copper cable in PVC conduit with 1.5 sq. mm. FR PVC-insulated multistrand Copper conductor cable as earth wire drawn in side the conduit. Add for light/fans with moduler type switch.
Wiring point for plug with 1.5 sq.mm FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduit pipe Partly concealed in the wall and partly Laid in slab along with the reinforcement before concreting ,complete with 1.5sqmm. FRLSH PVC insulated multistrand single core copper conductor cable as earth continuity wire , GP box, piano type switch & socket etc.complete in all respect,as directed, including matching colour wash.
Wiring point for call bell with 1.5 sq.mm FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduit pipe Partly concealed in the wall and partly Laid in slab along with the reinforcement before concreting ,complete with 1.5sqmm. FRLSH PVC insulated multistrand single core copper conductor cable as earth continuity wire GP box and piano type bell push switch or two pin socket etc.complete in all respect,as directed, including matching colour wash.
Wiring point for Exhaust fan with 1.5 sq.mm FRLSH PVC insulated multistrand single core copper conductor cable in heavy gauge PVC conduit pipe Partly concealed in the wall and partly Laid in slab along with the reinforcement before concreting complete with 1.5sqmm. FRLSH PVC insulated multistrand single core copper conductor cable as earth continuity wire , GP box and 15 amp piano type switch & ceiling rose /angle/batten holder on 3mm thick , phenolic laminated backelite sheet etc.complete in all respect,as directed, including matching colour wash.
Supply fixing & concealing of PVC conduit in the wall including cutting of brick laying of conduit & fixing it with MS hooks & then plastering.with cement, sand,mortar finished to the level,with matching colour wash including cost of proper thrading of conduit and providing necessary socket ,bend & chucknuts,as directed by engineer incharge with the supply of material labour and T&P required for proper completion of work.
Size 20 mm dia 16SWG (2 mm)thick
Size 25 mm dia 16SWG (2 mm)thick
Size 32 mm dia 16SWG (2 mm)thick
Add for plug point with moduler type switch in place of piano type switch.
Add for call bell point with moduler type switch in place of piano type switch.
Submains
Supply & wiring of submains with 2 nos.1.5 sq.mm FRLSH PVC insulated 1100 V grade multistrand single core copper conductor cable in 20 mm dia heavy gauge PVC conduit partly concealed in wall and partly laid in slab along with the reinforcement before concreting, with 1 no. 1.5 sqmm. FRLSH PVC insulated multistrand copper conductor cable as earth continuity wire including matching colour wash etc.complete in all respect.
Supply & wiring of submains with 2 nos.2.5 sq.mm FRLSH PVC insulated 1100 V grade multistrand single core copper conductor cable in 20 mm dia heavy gauge PVC conduit partly concealed in wall and partly laid in slabalong with the reinforcement before concreting, with 1 no. 1.5 sqmm. FRLSH PVC insulated multistrand copper conductor cable as earth continuity wire including matching colour wash etc.complete in all respect.
Supply & wiring of submains with 2 nos.4 sq.mm FRLSH PVC insulated 1100 V grade multistrand single core copper conductor cable in 20 mm dia heavy guage PVC conduit partly concealed in wall and partly laid in slab along with the reinforcement before concreting, with 1 no. 2.5 sqmm. FRLSH PVC insulated multistrand copper conductor cable as earth continuity wire including matching colour wash etc.complete in all respect.
Supply & wiring of submains with 2 nos.6 sq.mm FRLSH PVC insulated 1100 V grade multistrand single core copper conductor cable in 25 mm dia heavy gauge PVC conduit partly concealed in wall and partly laid in slab along with the reinforcement before concreting, with 1 no. 4 sqmm. FRLSH PVC insulated multistrand copper conductor cable as earth continuity wire including matching colour wash etc.complete in all respect.
Supply & wiring of submains with 2 nos.10 sq.mm FRLSH PVC insulated 1100 V grade multistrand single core copper conductor cable in 25 mm dia heavy gauge PVC conduit partly concealed in wall and partly laid in slab along with the reinforcement before concreting, with 1 no. 6 sqmm. FRLSH PVC insulated multistrand copper conductor cable as earth continuity wire including matching colour wash etc.complete in all respect.
Supply & wiring of submains with 2 nos.16 sq.mm FRLSH PVC insulated 1100 V grade multistrand single core copper conductor cable in 32 mm dia heavy gauge PVC conduit partly concealed in wall and partly laid in slab along with the reinforcement before concreting, with 1 no. 10 sqmm. FRLSH PVC insulated multistrand copper conductor cable as earth continuity wire including matching colour wash etc.complete in all respect.
Supply & wiring of submains with 4 nos. 6 sq.mm FRLSH PVC insulated 1100 V grade multistrand single core copper conductor cable in 32 mm dia heavy guage PVC conduit partly concealed in wall and partly laid in slab along with the reinforcement before concreting, with 2 no. 4 sqmm. FRLSH PVC insulated multistrand copper conductor cable as earth continuity wire including maching colour wash etc.complete in all respect.
Supply & wiring of submains with 4 nos.10 sq.mm FRLSH PVC insulated 1100 V grade multistrand single core copper conductor cable in 40 mm dia heavy guage PVC conduit partly concealed in wall and partly laid in slab along with the reinforcement before concreting, with 2 no. 6 sqmm. FRLSH PVC insulated multistrand copper conductor cable as earth continuity wire including matching colour wash etc.complete in all respect.
Supply & wiring of submains with 4 nos.16 sq.mm FRLSH PVC insulated 1100 V grade multistrand single core copper conductor cable in 50 mm dia heavy guage PVC conduit partly concealed in wall and partly laid in slab along with the reinforcement before concreting, with 2 no. 10 sqmm. FRLSH PVC insulated multistrand copper conductor cable as earth continuity wire including matching colour wash etc.complete in all respect.
Switches
Supply and fixing of 63 amp DP 30 mA ELCB/ RCCB of Din Rail mounting in DB complete in all respect with connections as required.
Supply & fixing and making connection of 63 amp. 4P 30 mA ELCB/ RCCB of Din Rail mounting in complete in all respect as per direction and satisfaction to the Engineer in Charge.
Light & Fan Fixture
Supply & fixing of Batton/Angle holder including making connection etc. as required.
Supply and fixing of recess mounting round 15 to 18 Watt LED Down lighiter having powder coated die cast aluminium housing with heat shink,diffuser/reflector and driver set. Complete in all respect. CAT. - AAA
Supply and fixing of 2'x2' 36 W to 46 W indoor recess/surface mounting LED Square Fitting for Armstrong Ceiling having powder coated CRCA housing body diffuser of special polycarbonate material and driver set Complete in all respect. CAT. - AAA
Supply and fixing of LED Tube Light with Metal heavy duty Box type batten Light fitting 1X22 watt suitable for upto 1X22 watt LED Polycarbonate tube light complete Including tube suitable for both surface & suspended complete in all respect.CAT. - AAA
Supply of ceilling fans with fan motor of A.C. Permanent insulation, capacitor rating conforming BEE 5 Star rating and IS:374/79 and also comply with IS:1709/1984 with latest amendment. The rated voltage 220/240 volts,50 Hz, 1-Ph AC the fan assemble should consists of down rod blades, shackle canopies etc and with double ball bearing system. BEE 5 Star rated-1200 mm sweep
Supply & Fixing of Factory made 12 to 20 Watt LED Bulb fitting,cool day light,(65000 K temp.) suitable for Batton/Angle holder including making connection.Complete in all respect.
Supply & Fixing of AC 230mm Sweep, 230/250 Volts, 50 Hz exhaust fan (Light Duty) with blades,cover etc. complete as required
Supply and fixing of call bell of approved make on polished MDFEG / Teak ply board including making connections etc.complete in all respect.
Cables
Supplying and laying of aluminium conductor PVC insulated armoured served sheathed cable 1100 volts grade at the depth of 750 mm bellow ground level over a cushion of 75 mm thick sand all around and protected with burnt bricks on side and on top .On surface the cable run shall be fixed on MS clamps etc.of suitable size or as directed by the Engineer-Incharge ,complete in all respect.The armouring of the cable shall be properly connected with the earth conductor by clamps etc.Following size 120 sq mm x 3-1/2core
Supply and fixing of brass nickle plated compression gland for pvc insulated & armoured served sheaththed ,underground cable including rubber ring etc. complete in all respect. Thearmouring of the cable shall be properly connected with the earth as per direction of engineer -incharge.for cable size 120 sq mm x 3-1/2core
Supply and fixing of plain or pin type copper tin plated cable socket (lug) to cable leads for pvc insulated & armoured cable insulating with tape and making connection. complete in all respect as per direction of engineer -incharge. for cable size 120 sq mm
Earthing System
Supply and burying of 600mm x 600mm x 6mm G.I. plate vertically for earthing with its top at least 3 metres below ground level complete with 20mm dia G.I. pipe and funnel for watering and one earthing lead of one no. 8 to 10 SWG GI wire in 15mm dia G.I. pipe up to switch board (from appron to switch board the cost of G.I. pipe and G.I. wire will be extra) 30cm square C.I. frame with hinged cover masonry housing alternate layers of charcoal/coke and salt at least 150mm thick alround etc. as per directions of Engineer-in-charge complete in all respects as per drawing (This will apply for earthing of poles also).
Supply and laying of 25mm x 3 mm G.I. strip from earth electrode directly in the ground as required complete in all respects.
Supply and fixing of two number 8 SWG G.I. wire in 15mm dia. G.I. pipe for earthing, laid in ground or in wall duly concealed including the cost of cement, sand, labour, T&P other material required for proper completion of work as directed at side.
Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required. 50 mm dia
SUB FLOOR PANELS 1
INCOMER (I1) :
160A FP 25kA Adjustable Thermal(O/C) & Adjustable Magnetic(S/C) Based MCCB with Extended RHOM, Spreaded Terminals, Shunt Trip. 1 No.
R,Y,B LED Indication Lamps. (1 set)
6Amps SP "C' Curve MCB for Control Circuit. (3 Nos.)
96Sq.mm, Digital Multi Data Meter. (1 No.)
160A/5A Class 1 5VA Resin Cast CT's. (3 Nos.)
(0.3-12A), 96Sq.mm, Digital Earth Leakage Relay with CBCT. (1 No.)
MAIN BUSBAR
200A TPN Aluminium Bus Bar With Heat Shrinkable Sleeves of Size 80x10x1 Run for Each Phase & Neutral.
OUTGOING FEEDERS(F1) :
40A TPN 10KA "C' Curve MCB. (10 nos.)
32A TPN 10KA "C' Curve MCB. (2 Nos.)
DBs & MCBs
Supply and fixing of 240 volts C Curve 6-32 amp SP miniature circuit breaker (10 K A ) in existing MCB, DB complete with connections as required. CAT A
Supply and fixing of 240 volts C Curve 40-63amp DP miniature circuit breaker (10 K A ) in existing MCB, DB complete with connections as required. CAT A
Supply and fixing of 240 volts C Curve 63 amp 4P miniature circuit breaker (10 K A ) in existing MCB, DB complete with connections as required. CAT A
Supply and fixing of flush/surface mounting 4 ways SPN distribution boards (Legrand Lexic) without MCB with additional metal door complete in all respects. As directed by engineer incharge. CAT A
Supply and fixing of flush/surface mounting 6 ways SPN distribution boards (Legrand Lexic) without MCB with additional metal door complete in all respects. As directed by engineer incharge
Supply and fixing of flush/surface mounting 8 ways SPN distribution boards (Legrand Lexic) without MCB with additional metal door complete in all respects. As directed by engineer incharge. CAT A
Supply and fixing of flush/surface mounting 12 ways SPN distribution boards (Legrand Lexic) without MCB with additional metal door complete in all respects. As directed by engineer incharge. CAT A
Supply and fixing of flush/surface mounting 12 ways TPN distribution boards (Legrand Lexic) without MCB with additional metal door complete in all respects. As directed by engineer incharge. CAT A
Supply and fixing of flush/surface mounting 8 ways TPN distribution boards (Legrand Lexic) without MCB with additional metal door complete in all respects. As directed by engineer incharge. CAT A
Supply and fixing of flush/surface mounting 4 ways V TPN distribution board without MCB with additional metal door complete in all respects. As directed by engineer incharge. CAT A
Supply & Fixing of MCB blanking plate for DB.
Miscellaneous Items
Supply and Fixing of Danger Board fabricated from 10 gauge M.S. Sheet as per I.E. Rules
Erection and testing of ceiling fan and regulator for room height upto 3.5mts. including supply of 3mm thick G.I. down rod 19mm dia duly painted, complete in all respects.
Erection and testing of exhaust fan on the existing hole with suitable size rag bolt nut & washer etc. complete in all respects.
Supply and fixing of 16 gauge MS drum duly painted including making hole in the wall for exhaust fan and finshing propely complete in all respect.
Supply and Fixing of shock treatment chart.prescribed as per I.E. Rules.duly framed with glass and supported from back with hard board or shoft board with supply of all material ,labour,T&P for proper completion of work.
Supply and Laying of 1800*900*12mm thick chequerd rubber matting of tested quality. complete in all respect. as per I.E. Rules
Supply and fixing of power plug with 20A/250V flush type Moduler switch and 5 Pin 20A/250V flush type universal Moduler socket in suitable Conceled MS Box including supply of all material, labour,T&P etc.required for proper completion of work.
Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required. (for Air conditioning/Main incoming.)
Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet,with 4 pole and earth, metal enclosed plug top alongwith 30 A "C"curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing Telephone socket outlet modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
Supplying and fixing TV antenna socket outlet modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
Supplying and fixing Bell push outlet modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
Supply & Fixing of LAN socket outlet modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
Supply & Fixing of Moduler switch blanking plate for Moduler switch board.
Supply and fixing One/Two module G.I box awlong with moduler base with cover plate.
1 or 2 Module (75mmX75mm)
3 Module (100mmX75mm)
4 Module (125mmX75mm)
6 Module (200mmX75mm)
8 Module (125mmX125mm)
12 Module (200mmX150mm)
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 1 run of cable
Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required.
Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required. 2 Pair
Electronic Items
Supply fixing of electronic fan regulator 120-280 V. ISI marked, on the existing switch board including making connetion, required material, labour T/P etc for proper completion of work to the satisfaction of Engineer in charge of work.
Supply and fixing of Three phase multifunctional electronic energy meter 10 to 60 Amp. Capacity fitted in intergral box on wall complete in all respect.
(D) FIRE FIGHTING WORK
Fire Alarm System :
Supplying, installation, testing & commissioning of central graphical fire alarm management system to centrally monitor and operate the fire alarm system complete as required.
Supplying, installation, testing & commissioning of intelligent analog addressable photothermal (Smoke) detector complete with mounting base complete as required.
Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required.
Supplying, installation, testing & commissioning of fault isolator complete with base as required.
Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required.
Supplying, installation, testing & commissioning of addressable fire control module complete as required.
Supplying, installation, testing & commissioning of addressable manual call point complete as required.
Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required.
Supplying, installation, testing & commissioning of fire fighter telephone handset complete as required.
Supplying, installation, testing & commissioning of fire fighter phone jack complete as required.
Public Addressable System :
Supplying, installation, testing & commissioning of 6 inches dia, 2 watts, 70/100 volts ceiling speaker complete as required.
Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required.
Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required.
Fire Fighting System :
Providing & fixing carbon steel Fire Man Axe with rubber insulated handle tested to 20000 volts.
1200x900 mm (Indoor Cabinet) Only Frame
Providing and Fixing of Self illuminated /Auto Glow Exit Signs printed on photo-luminescent sheet containing self illuminated base chemical,of appropriate size not less than 400x150mm,suspended from ceilling or fixed to the walls with accessories as riquired and as directed at site.
Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required : Terrace Pump Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325. M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. 450 lpm at 35 m Head
Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. (Uderground) 150 mm. Dia
Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :
25 mm dia
32 mm dia
50 mm dia
80 mm dia
Supplying and fixing single headed Internal Hydrant Valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required : Single headed Stainless steel
Pipes & Accessories
Providing, fixing, testing & commissioning of flanged end Basket Strainer made from MS body with bottom and top removable flanges with nuts, bolts etc having filteration area at least 6 times the cross sectional area of the pipe. Make: Kalpana/Kartar/Sir/Advance. 200 mm dia
Providing, fixing, testing & commissioning of C.I. Butterfly valve conforming to IS : 13095 with flanges, nuts, bolts and washers complete for following sizes :- [PN 16 rating (16 kg/cm2 pressure rating)]. Make: Kalpana/Kartar/Firejeet.
80 mm dia
100 mm dia
Supply, Installation, Testing and Commissioning of Orifice Plate made of 6 mm.thick Stainless Steel with orifice of required size in between flange and Landing Valve & pipelines to reduce pressure to working pressure of 3.5 kg/sq.cm.2 complete as per specification as required.
Providing, fixing, testing & commissioning of C.I. dual plate Non-Return Valve [PN 1.6 Rating (16 kg/cm2 pressure rating)] complete with 2 nos. matching flanges, rubber insertion, with nuts, bolts and washers etc of following sizes . Make: Kalpana/Kartar/Firejeet.
80 mm dia
100 mm dia
FIRE HYDRANT SYSTEM (INTERNAL) :
Supplying and fixing 63 mm dia, 15 m long RRL Hose Pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : Make: Firejeet / Minimax / Newage. Stainless Steel (Grade 304)
Supplying & fixing 63 mm dia gun metal short Branch Pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : Stainless Steel (Grade 304)
Supplying and fixing First-Aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 30 m
Providing & fixing cast iron air release valve of 25 mm dia including 25 mm dia Ball valve with fittings etc. as per the requirement.
SPRINKLER SYSTEM:
Supplying and fixing of Fire Brigade Connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : 4 way - 150 mm dia M.S. Pipe
Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :
Pendent Sprinkler
Upright Sprinkler
Supplying, installation, testing & commissioning of Sprinkler Flexible Pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. 1000mm
Providing and Fixing M.S Structural Work fabricaed from standard sections e.g MS rounds, angles, channels including cutting to size, drilling, welding, fixing and welding to insert plates in RCC structural members as directed by Engineer-in-Charge including cutting and making good the walls and floors (For sprinkler Pipe support etc.).
Tie Road 10 mm
Angle Frame 35 / 40 mm x 5 mm
FIRE EXTINGUISHERS
Supply and fixing of fire extinguisher, ABC Type (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket,along with supply of all materials and labour for proper completion of work. 6.0 kg. capacity
Supply and fixing of C02 type fire extinguisher (ISI Marked IS : 2878 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. 4.5 kg. capacity
(E) LIFT WORK
20 PASSENGER LIFT (G+4)
Other Features
Battery Operated Emergency Light And Alarm Bell
Call Register Signal And Vf Door Operator
False Ceiling In Car
Vandal Proof S.S. Button With S.S. Cover
Firemans Switch
Infra Red Door Screen
Full Car Operating Panel
3 Way Intercom / Press And Speak Phone
Push Button - Orange L E D Illumination
Dot Matrix Led D & P Indicators In Car & Landings -Orange Colour
Automatic Rescue Device
Minor Builders Work
Scaffolding
Floor Annunciator With Music
Braille Buttons
Sill Support
Lift License
Overload Warning Indicator With Audio Announcement
Pit Ladder
Auto Light & Fan Switch Off (Pod)
Free Service For Five Years
Cable etc.
Supplying and laying of aluminium conductor PVC insulated armoured served sheathed cable 1100 volts grade at the depth of 750 mm bellow ground level over a cushion of 75 mm thick sand all around and protected with burnt bricks on side and on top .On surface the cable run shall be fixed on MS clamps etc.of suitable size or as directed by the Engineer-Incharge ,complete in all respect.The armouring of the cable shall be properly connected with the earth conductor by clamps etc.Following size 35 sq mm x 3-1/2core
Supply and fixing of brass nickle plated compression gland for pvc insulated & armoured served sheaththed ,underground cable including rubber ring etc. complete in all respect. Thearmouring of the cable shall be properly connected with the earth as per direction of engineer -incharge.for cable size 35 sq mm x 3-1/2core
Supply and fixing of plain or pin type copper tin plated cable socket (lug) to cable leads for pvc insulated & armoured cable insulating with tape and making connection. complete in all respect as per direction of engineer -incharge. for cable size 35 sq mm
Earthing
Supply and burying of Safe Earthing Electrod T-19 Zn-Zinc Coated,Length 3000mm,outer pipe 48.4mmx3.2mm,inner pipe 26.9mm x 2.6 mm,terminal Dia 12mm,coating 80-100 micron filled with crystalline conductive mixture (CCm) having anti corrosive & conductive property with 50 Kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square C.I. frame with hinged cover & masonary housing.(From electrode terminal to switch board,cost of 25x3 G.I. Strip will be extra) Make : As approved in U.P.P.W.D. & C.P.R.I. Certified.
Supply and laying of 25mm x 3 mm G.I. strip from earth electrode directly in the ground as required complete in all respects.
Supply and fixing of two number 8 SWG G.I. wire in 15mm dia. G.I. pipe for earthing, laid in ground or in wall duly concealed including the cost of cement, sand, labour, T&P other material required for proper completion of work as directed at side.
Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required. 100 mm dia
(F) SPLIT AC
Supply & installation of Split Direct Expansion Air-Conditioners Suitable for operation on A/C supply single phase 50 HZ 230 Volts with hermetically sealed compressor with air cooled condenser, motor capacitor and start run capacitor, relay and overload protector internal unit, with one indoor and one outdoor unit. The condenser unit will be placed outside the room on the terrace to avoid noise including standard length of suitable size copper tubing covered with insulation tube. (High Wall Chorded / Chordless) Suitable Capacity 3 Core sheathed / PVC copper cable and a battery operated wireless remote unit.
1 TR (BEE Star Rated : 5 Star, EER 3.4)
2 TR (BEE Star Rated : 5 Star, EER 3.4)
Digital Voltage AC Stabilizer for Upto 1.5, 2.0 Ton 15 Amp, 90 TO 300 VAC, 4- 6 Sec initial time delay.
GST Extra as applicable
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.41 MB
BIDDOC97.pdf
Tender Documents • 21.03 MB
BOQ_2072398.xls
BOQ • 0.77 MB
Download all tender documents and submit your bid