Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.1 LAccepted-AOC | ₹12.1 L Quoted ₹12.2 L | L1 | Accepted-AOC Lowest bidder |
| 2 | L2₹16.4 L+₹4.2 L (34.4%)Rejected-Finance 179 URBAN ESTATE RAM TIRATH ROAD NR GURUDAWARA DARSHAN SINGH AMRITSAR PUNJAB 143001 | AMRITSAR | PUNJAB | 143001 | ₹16.4 L+₹4.2 L (34.4%) | L2 | Rejected-Finance Other than lowest bidder |
Tender Value
Refer Docs
EMD Value
₹40,000
Closing Date
20 Jan 2021, 6:00 pmClosed
GE (AF) Jammu
Air Force Station Jammu
REPAIR/REPLACEMENT AND DAY TO DAY MAINT OF PERIMETRE SECURITY LIGHTS, STREET LIGHTS, BUILDING SECURITY LIGHTS POST TOP LANTERN,GARDEN LIGHTS HIGH MASTS AT AF STN JAMMU AND KALUCHAK
2020_MES_405427_1
CA NO GE/AFJ-41/2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (AF) Jammu
As tender documents and as per policy in vogue
8 documents required · 8 mandatory
₹500
Yes
₹40,000
Yes
15 Feb 2021
21 Dec 2020
22 Jan 2021
21 Dec 2020
20 Jan 2021
6 Jan 2021
Amount
Petroling And attending Day to day Street Light complaints and maint/repairs to street light/security lights of any type and capacity fixed at any height by replacing unserviceable parts including cleaning of perpex cover checking loose connection,power supply problem etc., detecting and repair of U/G cable fault etc as and when required round the clock complete all as directed at site on daily complaint basis. Note: 1. Due to security point minimum One electrician (Skilled) And One helper (Un skilled) shall be always present in the station daily round the clock . Note: 2: Complaints should be attended And Rectified within the same day failling which recovery at double the rate quted by the contractor against this items shall be affected from his becomming dues. Note 3. Repair/replacement of loose connection of particular fittings shall be mesured Including quted Rate the complaint received from users telephonically or as lodged in complaint register
Note 4:- Complaint attended in one day(24 hrs) will be treated as one job. Electrician and helper daily report to power house electrician should be technically qualified and shall have adequate knowledge of electrical system and maintenance/repair of street lights and Contractor has to provide them all the required electrical T & P ,Tourch and safety equipment like PVC globs, Safety Belts, Ladder, crash helmet, Minor Spares like , Insulation tapes, screws, ,Amp & Volts Meter short pieces of copper/Al conductor etc required for restoration of Light supply etc and necessary transport/Vehicle arrangement by the Contractor to attend the complaint within AF station at Jammu
Supply only Indus series Powder coated pressure die cast alluminium compact high power LED street light fittings with heat resistant toughned glass with lense having 45 Watt including making electric connections using two run of 1.5 sqmm single core unarmoured wire from junction box, fixed in repairs, complete all as specified and as directed by Engr-in-Charge. Note : (i) Any touch up of the existing surface due to changing of fittings shall be done by contractor with similar surface finish without extra cost to the department. Make: Cat Part No: BRTFG 45 Watt of Bajaj or equavalent to Havells/ Crompton
Supply only Indus series Powder coated pressure die cast alluminium compact high power LED street light fittings with heat resistant toughned glass with lense having 60 Watt including making electric connections using two run of 1.5 sqmm single core unarmoured wire from junction box, fixed in repairs, complete all as specified and as directed by Engr-in-Charge. Note : (i) Any touch up of the existing surface due to changing of fittings shall be done by contractor with similar surface finish without extra cost to the department. Make: Cat Part No: BRTFG 60 Watt of Bajaj or equavalent to Havells/ Crompton
Supply Only Indus series Powder coated pressure die cast alluminium compact high power LED street light fittings with heat resistant toughned glass with lens having 90 Watt with lens including making electric connections using two run of 1.5 sqmm single core unarmoured wire from junction box, fixed in repairs, complete all as specified and directed by Engr-in-Charge. Note : (i) Any touch up of the existing surface due to changing of fittings shall be done by contractor with similar surface finish without extra cost to the department. Make :Cat Part No: BRTFG90 Watt of Bajaj or equavalent to Philips/havells/ Crompton
Supply Only orion series pressure die cast alliminium housing complete with all accessories IP66 high power LED floodlight 100 Watt incl making electric connection using two run of 1.5 sqmm single core unarmoured wire from junction box, fixed in repairs, complete all as specified and directed by Engr-in-Charge. Note :(i) A certificate from the manufactures for warranty minimum upto 02 years shall be obtained and submitted to the AGE/GE (ii) Any touch up of the existing surface due to changing of fittings shall be done by contractor with similar surface finish without extra cost to the department. Make :Cat Part No: 169904 BJFL 100 Watt of Bajaj or equavalent to /havells/ Crompton
Supply Only orion series pressure die cast alliminium housing complete with all accessories IP66 high power Turbo LED floodlight 120 Watt incl making electric connection using two run of 1.5 sqmm single core unarmoured wire from junction box, fixed in repairs, complete all as specified and directed by Engr-in-Charge. Note : (i) Any touch up of the existing surface due to changing of fittings shall be done by contractor with similar surface finish without extra cost to the department. Make :Cat Part No: 169641 BJFL 120 Watt of Bajaj or equavalent to /havells/ Crompton
Supply Only decorative LED post top lantern 40 watts light fitting including lamp for 360 degree indirect light, resistant to impact and corrosion glare free and better informity IP 65 protection, M-Milky version and including necessary connection with suitable size cable, fixed in repairs, complete all as specified and directed by Engr-in-Charge. Note :(i) A certificate from the manufactures for warranty minimum upto 3 years shall be obtained and submitted to the AGE/GE (ii) Any touch up of the existing surface due to changing of fittings shall be done by contractor with similar surface finish without extra cost to the department. Make: Cat Part No: LPTO-40-CDL/M of Crompton or equavalent to Philips/Havells
Supply and fixing street light bracket 1.50 mtr long made out of 32 mm bore GI pipe, light grade, bend to shape, welding etc and fixing on existing LT pole with 50 x 6mm flat iron MS clamps including necessary nuts, bolts and washers etc and including painting two coats with synthetic enamel paint over a coat of red oxide primer after removal of galvanising with moderate solution complete all as specified and directed.
Supply Only LED aviation light including necessary connection with two run of 1.50 sqmm single core unarmoured copper cable from junction box, fixed in repairs, complete all as specified and directed by Engr-in-Charge. Note :(i) A certificate from the manufactures for warranty minimum upto 3 years shall be obtained and submitted to the AGE/GE (ii) Any touch up of the existing surface due to changing of fittings shall be done by contractor with similar surface finish without extra cost to the department. Make: Bajaj Cat Part No BGAV302LED or equavalent make of Crompton/Philips/Havells/C&S
Material and labour for repair to existing LED street light fitting 45 Watts to 60 Watts of any make including supply and replacement of driver, LED Strips PCB card and other minor allied items required at site to make the light fitting serviceable complete all as specified and directed by Engineer-in-Charge.
Material and labour for repair to existing LED street light fitting 90 Watts to 100 Watts of any make including supply and replacement of driver, LED Strips and other minor allied items required at site to make the light fitting serviceable complete all as specified and directed by Engineer-in-Charge.
Material and labour for repair to existing LED street light fitting 120 Watts to 150 Watts of any make including supply and replacement of driver, LED Strips and other minor allied items required at site to make the light fitting serviceable complete all as specified and directed by Engineer-in-Charge.
Labour only for taking down and lifting up high mast light fitting including replacing the unserviceable items to make the fitting serviceable , adjust/repair the timer, supply and fixing in replacement the contacts lifting mechanism with all accessories as required, complete all as directed by the Engineer-in-Charge. Note :- Spares like chokes, ignitor lamp & LED Drivers will be measured and paid separately)
Supply and fixing fixed in repairs cable Junction Boxes with terminals` IP 66 "halogen free and weather proof” for outdoor installation (with metric knockouts for cable entry - Black Colour) Cable Size 16/25 Sqmm, Box Dimensions-200 x160 x 98, Catalog No-KF 9255(hensel) complete taking out of loop of cable from ground by neccessary earth work all as spcefied and directed by Engr-in- charge. Make- Hensel/Dowells
Supply and fixing PVC cable end terminal box outdoor type, 140 x 140 X 95 mm, PVC door, Sintex type , provision for cable incoming and outgoing from bottom, comprising of one MCB SPN 6-32 Amps (of Make: Legrand/Schneider/L&T), cable glands suitable size and one porcelein connector four way complete fixed on wall/pole. Make- Sintex of equivalent.
Supply & Fixing PVC insulated sheathed service wire twin core 04 Sqmm aluminium multistranded conductor 1100 volts grade incl taking down old unserviceable one.
Supply & Fixing PVC insulated sheathed service wire twin core 10 Sqmm aluminium multistranded conductor 1100 volts grade incl taking down old unserviceable one.
Supply & Fixing PVC insulated sheathed service wire twin core 16 Sqmm aluminium multistranded conductor 1100 volts grade incl taking down old unserviceable one.
Supply & fixing Sub main wiring with two single core PVC insulated unshesthed cable copper conductor(FRLS-H) of size 2.5 sqmm multistranded and one run of 1.5 sqmm PVC insulated unsheathed copper conductor(FRLSH) as earth continuty conductor drawing in and including non-metalic PVC rigid conduit 25 mm dia ISI marked with all conduit accessories concealed in wall, cutting of chases in walls, floors, ceilings, beams etc and making good the disturbed surfaces as directed including taking down old unservicable wiring complete all as specified and directed. (Two run of single core cable and one run of earthing cable and one run of PVC conduit shall be measured as one length.)
Supply and fixing Rigid non-metallic PVC conduit 25mm dia (Heavy duty) in concealed exclusive of boxes (junction/terminal) but inclusive of all tees, bends,elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. including taking out old conduit complete all as specified and directed. Note: This item shall be measured and paid for the locations other than the locations measured under item No 23.00 here-in-before.
Supply Only LED bulb 7 watt, B22 Base (6500K) pin type lumino for normal batten holder/pendant holder complete all as specified and as directed. Make: Havells Cat Part No Havells Adore LED -7W or equivalent to Bajaj/Phillips/CG
Supply and Fixing MCCB 320 Amps 4 pole 25 KA with Sheet metal encloser with adjustable thermal and fixed magnetic setting, fixed in repairs complete all as specified and directed. Make: Indiasian Cat Part No 830387 or equivalent siemens/ Legrand/Havells.
Supply and Fixing MCCB 250 Amps 4 pole 25 KA with Sheet metal encloser with adjustable thermal and fixed magnetic setting, fixed in repairs complete all as specified and directed. Make: Indiasian Cat Part No 830297 or equivalent siemens/ Legrand/Havells.
Supply and Fixing MCCB 160 Amps 4 pole 25 KA with Sheet metal encloser with adjustable thermal and fixed magnetic setting, fixed in repairs complete all as specified and directed. Make: Indiasian Cat Part No 830295 or equivalent siemens/ Legrand/Havells.
Supply and Fixing MCCB 100 Amps 4 pole 25 KA with Sheet metal encloser with adjustable thermal and fixed magnetic setting, fixed in repairs complete all as specified and directed. Make: Indiasian Cat Part No 830272 or equivalent siemens/ Legrand/Havells.
Supply and Fixing MCB SPN 40 Amps C Curve 25 KA with Sheet metal encloser, complete all as specified and directed. Make: Indiasian Cat Part No 811240 or equivalent siemens/ Legrand/Havells.
Supply and Fixing MCB Single Pole Neutral 25 Amps C Curve 25 KA with Sheet metal encloser, complete all as specified and directed. Make: Indiasian Cat Part No 811150 or equivalent siemens/ Legrand/Havells.
Supply and Fixing Sheet metal encloser,DB Two Way complete all as specified and directed. Make: Indiasian Cat Part No 811980 or equivalent siemens/ Legrand/Havells.
Supply , installation , Commissiong & Testing of Street Light TIMELITE DISTRIBUTION BOARDS Timelite 40 amp 3 Pole Astronomical Time Swich suitable for 230 volt 3 phase 4 wire with locking arrangement including bottom and top detachable gland plate complete with suitable size of rust proof nuts, bolts, and washers etc.. complete Make: Indiasian HSN Code 8537 Cat Part No TL040ASO
Preparation of old painted surface of 11 Mtr. steel tubular poles above the top of PCC coping. Painting of pole from top of coping to a height of 1.5mtr (bottom portion of pole) with two coats of synthetic enamel paint (Make-DULUX/ Superlac (Shalimar)/ Apcolite (Asian)/ Nerolac/ Luxol (Berger) in black and yellow alternate strip and painting the rest portion of pole of (approx length 9 mtr) including painting of cross arms/clamps etc complete with two coats of synthetic enameal aluminium paint (Make-Asian (Apex)/ Berger (Weather Coat) /Shalimar (Ist quality)/ Nerolac (Ist India) and to the entire satisfaction of Engineer-in-Charge complete all as specified and directed
Preparation of old painted surface of 9 Mtr. steel tubular poles above the top of PCC coping. Painting of pole from top of coping to a height of 1.5mtr (bottom portion of pole) with two coats of synthetic enamel paint(Make-DULUX/Superlac(Shalimar)/ Apcolite (Asian)/ Nerolac/ Luxol (Berger) in black and yellow alternate strip and painting the rest portion of pole of (approx length 7 mtr)including painting of cross arms/clamps etc complete with two coats of synthetic enamel aluminium paint (Make-Asian (Apex) /Berger (Weather Coat) / Shalimar (Ist quality) /Nerolac (Ist India) and to the entire satisfaction of Engineer-in-Charge complete all as specified and directed
M & L for Preparation of old cement based painted surfaces of RCC pole 9 mtr by cleaning of deposited materials, and painting with one coat of exterior emulsion weather coat paint of approved make and colour complete all as specified and directed by Engineer-in-Charge
Material and labour for fault detection in damaged under ground cables using cable fault detector/locater, vehicle mounted to accuracy of 2 mitres for various locations inside Air Force Station for under ground cables of any size upto 240 sqmm including excavation and earthwork in any type of soil having trench size 4 x 2 x 0.60m to visually inspect/ repair the damaged cable when and whre detected complete all as specified and directed by Engineer-in-Charge. NOTE: cable fault shall be located with use of cable fault locator machine as and when required with minimum possible time to reduce the downtime. If fault is not attended/located within 24 hours, recovery will be made at Rs 4000.00/Day from the date of such occurance.
Cable jointing kit for 1100 Volts (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 4 core XLPE armoured aluminium conductor cable of size 10 sqmm to 35 sqmm fixed in repairs,complete all as specified and directed by Engineer-in-Charge. Make: 3M/Denson/M-Seal
Cable jointing kit for 1100 Volts (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 4 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm fixed in repairs,complete all as specified and directed by Engineer-in-Charge. Make: 3M/Denson/M-Seal
Cable jointing kit for 1100 Volts (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 4 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm fixed in repairs,complete all as specified and directed by Engineer-in-Charge. Make: 3M/Denson/M-Seal
Cable jointing kit for 1100 Volts (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 4 core XLPE armoured aluminium conductor cable of size 240 sqmm to 300 sqmm fixed in repairs,complete all as specified and directed by Engineer-in-Charge. Make: 3M/Denson/M-Seal
Supply , installation , Commissiong & Testing of LT feeder pillar compartmentalised design of size not less than 70 x 70 x 25 cm suitable for 440 volt 3 phase 4 wire system made out of 2.5 mm CRCA sheet powder coated having gasketed front two hinged doors with locking arrangement including bottom and top detachable gland plate complete with suitable size of rust proof nuts, bolts, and washers etc.. complete with mounting accessories including the following components :-(a) Four 30cms long Copper bus bar 400 Amp mounted on epoxy insulators provided with rust proof nuts bolts and washers (b) LED indicating lamps - 3 nos. (Red ,Yellow, Blue)
Cutting of tree branches of any girth along HT/ LT OH lines & street light pole at a distance not less than 2 meter on either side of the pole cleaning of bushes and shrubes of any type along entire RM of poles. Cleaning /prunning should be carried out as and when required during entire running period of contract or as and when directed by Engineer-in-Charge. A fine of one time quated rate per running meter will be deducted if the over growth is found along the pole all as directed by Engr-in- Charge.
Cleaning of under growth at substation . Cleaning should be carried out as & when required or when directed by Engr- in-Charge. Undergrowth at any point of time should not be more than 3 to 4 cm. A fine of Rs 1000.00 per month per substation will be deducted if undergrowth found grown beyond permissible height complete all as directed by Engr-in-Charge.
Material and labour for earth continuity conductor or main earthing lead using 4 mm dia galvanised iron or steel wire fixed to wall on batten or recess or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required including taking down old wire complete all as specified and directed by Engineer-in-Charge.
Material and labour for earth continuity conductor or main earthing lead using 25 x 4mm galvanised steel strip fixed to wall on batten or recess or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation, etc. as required including porcelain insulator saddle at the spacing nort exceeding 400mm including taking down old strip complete all as specified and directed by Engineer-in-Charge.
Material and labour for earth continuity conductor or main earthing lead using 32 x 6mm galvanised steel strip fixed to wall on batten or recess or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation, etc. as required including porcelain insulator saddle at the spacing nort exceeding 400mm including taking down old strip complete all as specified and directed by Engineer-in-Charge.
Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.0mm thick buried directly in ground, (Earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to and including 4 mm dia galvanised earth lead wire by means of bolts, nuts, check nuts and washers of galvanised standard iron or steel all as specified or indicated in electrical plate no 3 of MES Part-I, including testing on completion including the material and labour of the following :-
(a) Excavation and earth work for drilling hole for electrode in any type of soil.
(b) PCC pit in cement concrete 1:2:4 type B-1.
(c) Precast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than 1.87 Kg/Sqm.
(d) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified.
(e) 15 mm nominal bore light grade GI protection pipe 5 mtr long for protection of earthing lead from mechanical injury or tempering.
(f) Requisite quantity of common salt and charcoal.
(g) Testing of earthing.
Note : (a) On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge. (b) The contractor shall quote his rate considering taking down cost of existing unserviceable earthing.
Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.0mm thick buried directly in ground, (Earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to and including 32 x 6 mm galvanised earth strip by means of bolts, nuts, check nuts and washers of galvanised standard iron or steel all as specified or indicated in electrical plate no 3 of MES Part-I, including testing on completion including the material and labour of the following :-
(a) Excavation and earth work for drilling hole for electrode in any type of soil.
(b) PCC pit in cement concrete 1:2:4 type B-1.
(c) Precast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than 1.87 Kg/Sqm.
(d) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified.
(e) 40 mm nominal bore light grade GI protection pipe 5 mtr long for protection of earthing lead from mechanical injury or tempering.
(f) Requisite quantity of common salt and charcoal.
(g) Testing of earthing.
Note : (a) On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge. (b) The contractor shall quote his rate considering taking down cost of existing unserviceable earthing.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm, 2 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm, 4 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm, 4 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm, 3.5 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sq mm, 3.5 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sq mm, 3.5 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm, 3.5 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 150 sq mm, 3.5 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Taking out of old serviceable/unserviceable PVC under ground LT or HT cable of any size and type fixed on pole, wll or laid in floors, trenches, across road crossing, etc. including taking out cable covers of precast PCC/RCC slab or brick covers, etc., including setting a side serviceable materials in safe costody for reuse and or unserviceable materials shifting to store complete all as specified and as directed. Note: (i) Dismantling of clamps, nuts, bolts, etc., taking out of GI pipe in cable protection shall be measured and paid separately under respective item of this schedule. (ii) Cost for making good the disturbed ground surfaces of floors/walls in cement mortar 1:3 shall deemed to be included in the unit rate quoted. However cost for making good the disturbed surfaces of roads with PCC and hard core filling is out of scope of this work and shall be measured and paid separetely under respective item of this schedule.
Relaying only of serviceable LT or HT under ground cable of any size and any type in trenches, floors, across road crossing or fixed on poles, walls, or passing through pipe, cable obtained from ser item No 54.00 here-in-before complete all as specified and as directed by the Engineer-in-Charge. NOTE: Handling of under groucn cable to working site as ordered shll be carried out by the firm and rate for the same is to be deemed in overall rates quoted by the tenderer under this item.
Relaying only of serviceable bricks/PCC slab cover obtained from item No 10.00 here-in-before for cable protection cover laid width wise along length of cable complete all as specified and as directed by the Engineer-in-Charge.
Supply, install and erect in true vertical position (or to be fixed in an inclined position as strut pole) steel tubular swaged poles complete with MS base plate of 6 mm thick of size 300 mm x 300 mm, finial taper plug, pole cap, bolts, nuts and washers and screwed pole made out of FRW MS tubing conforming to IS-2713 (Part-II) 1980 type 410-SP-31 ( 9 meters long ) pole including drilling of holes of required size and Nos for fixing of cross arms, painting with one coat of red oxide primer and two coats of aluminium paint for exposed surfaces and two coats of black bituminous paint for portion embeded in concrete, incl taking down carefully old deterioiated RCC/steel pole etc complete all as specified and directed.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in any type of soil for laying of LT UG cables, foundation of poles, etc. complete. Note:- The Rate quoted deemed to including cutting and removal of PSP Sheets wherever occured during excavation and the same shall be staged at desired location as directed at site which will be handed over to the appropriate authority as directed by Engineer-in-Charge
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in hard rock for laying of LT UG cables, foundation of poles, etc. complete. Note:- The Rate quoted deemed to including cutting and removal of PSP Sheets wherever occured during excavation and the same shall be staged at desired location as directed at site which will be handed over to the appropriate authority as directed by Engineer-in-Charge
Returning, filling in, including spreading levelling, watering and well ramming in layers not exceeding 25 cm thick in hard dense soil
Removing excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point
Dry coarse sand as cushioning to under ground cable provided with layer of 8 cms deep before laying the cable and 15 cms deep after laying and stretching the cable, punned to 18 cm thick complete all as specified and as directed by Engr-in-Charge. NOTE Only punned thickness shall be measured for payment purpose.
Sub class 'B' old size bricks well burnt as covering to under ground cables , laid dry, flat over the cables on sand cushioning with width equal to length of the brick as mechanical protection to cable, complete all as specified and directed.
Plain cement concrete 1:4:8 type D2 using 40mm graded stone aggregate for foundation and mass concrete of poles complete all as specified and as directed.
PCC 1:3:6 type C1 using 20 mm graded stone aggregate for coping of poles/plinth blocks of HT poles etc incl fair finishing the exposed surfaces even and smooth without using extra cement including necessary form work complete all as specified & directed.
Supply and Fixing GI tubing medium grade 40mm dia along the wall/in trenches/in duct/in culvert/road crossing and including provisioning of suitable mild steel flat iron clamps and bolts, nuts and double washers etc for holding of GI pipe alongwith poles including taking out old broken Gi pipes, complete all as specified and as directed by Engr-in-Charge.
Supply and Fixing GI tubing medium grade 50mm dia along the wall/in trenches/in duct/in culvert/road crossing and including provisioning of suitable mild steel flat iron clamps and bolts, nuts and double washers etc for holding of GI pipe alongwith poles including taking out old broken Gi pipes, complete all as specified and as directed by Engr-in-Charge.
Supply and Fixing GI tubing medium grade 80mm dia along the wall/in trenches/in duct/in culvert/road crossing and including provisioning of suitable mild steel flat iron clamps and bolts, nuts and double washers etc for holding of GI pipe alongwith poles including taking out old broken Gi pipes, complete all as specified and as directed by Engr-in-Charge.
Supply and Fixing GI tubing medium grade 100mm dia along the wall/in trenches/in duct/in culvert/road crossing and including provisioning of suitable mild steel flat iron clamps and bolts, nuts and double washers etc for holding of GI pipe alongwith poles including taking out old broken Gi pipes, complete all as specified and as directed by Engr-in-Charge.
Supply and fixing in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 16 Sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position, extending the cable from cable loop including neccesory earth work and reconnecting the same.
Supply and fixing in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 25Sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position, extending the cable from cable loop including neccesory earth work and reconnecting the same.
Supply and fixing in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 35 Sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position, extending the cable from cable loop including neccesory earth work and reconnecting the same.
Supply and fixing in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 50 Sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position, extending the cable from cable loop including neccesory earth work and reconnecting the same.
Supply and fixing in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 70 Sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position, extending the cable from cable loop including neccesory earth work and reconnecting the same.
Supply and fixing in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 95 Sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position, extending the cable from cable loop including neccesory earth work and reconnecting the same.
Supply and fixing in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 185 Sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position, extending the cable from cable loop including neccesory earth work and reconnecting the same.
Supply and fixing in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 240 Sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position, extending the cable from cable loop including neccesory earth work and reconnecting the same.
Supply and fixing in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 400 Sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position, extending the cable from cable loop including neccesory earth work and reconnecting the same.
SCHEDULE 'A' PART-II (Schedule of credit) Credit amount of Rs (Refer schedule of credit) for retrieved material mentioned in Sch 'A' Part-II of Tender documents in PDF form will be deducted offline during acceptance of tender of lowest bidder.
Note: (1) The repair has to carried out as and when required basis and accordingly site will be available in piecemeal wise and as directed by Enginer-in-Charge in the Air Force station at Jammu and Kaluchak area
Harsh Electricals
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .