IISER Pune Dr Homi Bhabha Road Pashan Pune 411008
Supply installation testing and commissioning of UV lights in AHU ducts at Main Building IISER Campus Pune
2022_IISRP_676007_1
32/ IISER/PUNE/2021-22
Open Tender
Electrical Works
Works
90 days
IISER Pune
As per tender documents
3 documents required · 3 mandatory
₹590
Director IISER Pune
₹51,100
Yes
19 Apr 2022
1 Mar 2022
18 Mar 2022
1 Mar 2022
17 Mar 2022
1 Mar 2022
Amount
Please note that Quoted rates are inclusive of all taxes,labor,transportation etc. Nothing Extra shall be paid separtely.
Supply installation testing and commissioning of UVGI lamps in the ducts of the AHU’s with complete set. Each set includes, cutting of GI ducts and making a trap door to insert the UV lamps in the ducts, UV lamps, indicator, run hour meter, MCB of size 6 Amps, choke of required size, ballast of required size, MS control panel, internal wiring (UV Lamps to control panel of required size upto 4 meters) and lamp mounting frame of required size Etc. The size of lamps for each AHU are as below. UV Lamp Make Philips/Syska/Totaline/aeropure Run Hout Meter Make : minilac/Gic/Omran
3285 CFM AHU, duct size-400*1000 mm Wattage required - 280 watts, 4 nos of UVGI lamps
1510 cfm - duct size- 300*700 Wattage required - 235 watts, 3 nos of UVGI lamps
5000 cfm and duct size - 1000*400 Wattage required - 300 watts, 4 nos of UVGI lamps
4440 cfm and duct size - 500*400 Wattage required - 290 watts, 4 nos of UVGI lamps
2600 cfm and duct size - 500*300 Wattage required - 280 watts, 4 nos of uVGI lamps
6375 cfm and duct size - 550*550 Wattage required - 300 watts, 4 nos ofUVGI lamps
13225 cfm and duct size - 600*1150 Wattage required - 420 watts, 6 nos of UVGI lamps
14000 cfm and duct size - 1400*500 Wattage required - 425 watts, 6 nos of UVGI lamps
3170 cfm and duct size - 400*500 Wattage required - 280 watts, 4 nos of UVGI lamps
3605 cfm and duct size - 5500*500 Wattage required - 290 watts, 4 nos of lUVGI amps
3200 cfm and duct size - 450*450 Wattage required - 280 watts, 4 nos of lUVGI amps
6850 cfm and duct size - 8000*450 Wattage required - 320 watts, 4 nos of UVGI lamps
5000 cfm and duct size - 1000*400 Wattage required - 300 watts, 4 nos of lUVGI amps
17850 cfm and duct size - 1200*900 Wattage required - 470 watts, 6 nos of UVGI lamps
19750 cfm and duct size - 1360*360, 1500*500 Wattage required - 500 watts, 7 nos of UVGI lamps
5000 cfm and duct size - 950*350 Wattage required - 300 watts, 4 nos of UVGI lamps
6200 cfm and duct size - 1000*400 Wattage required - 430 watts, 6 nos of UVGI lamps
5000 cfm and duct size - 950*500 Wattage required - 300 watts, 4 nos of UVGI lamps
19200 cfm and duct size - 900*750 *2 nos. Wattage required - 485 watts, 6 nos of UVGI lamps
21050 cfm and duct size - 700*700 * 2 nos. Wattage required - 510 watts, 7 nos of UVGI lamps
5000 cfm and duct size - 950*350 Wattage required - 300 watts, 4 nos of UVGI lamps
5000 cfm and duct size - 1150*350 Wattage required - 300 watts, 4 nos of UVGI lamps
4000 cfm and duct size - 750*300 Wattage required - 290 watts, 4 nos of UVGI lamps
3000 cfm and duct size - 950*300 Wattage required - 280 watts, 4 nos of UVGI lamps
12700 cfm and duct size - 1150*650 Wattage required - 420 watts, 6 nos of UVGI lamps
10000 cfm and duct size - 1100*500 Wattage required - 370 watts, 5 nos of UVGI lamps
10000 cfm and duct size - 1100*500 Wattage required - 370 watts, 5 nos of lUVGI amps
4000 cfm and duct size - 950*350 Wattage required - 290 watts, 4 nos of UVGI lamps
19250 cfm and duct size - 2000*550, 500*350 Wattage required - 485 watts, 6 nos of UVGI lamps
12000 cfm and duct size - 850*450 - 2 Nos. Wattage required - 400 watts, 5 nos of UVGI lamps
9200 cfm and duct size - 1400*450 Wattage required - 355 watts, 5 nos of UVGI lamps
23000 cfm and duct size - 1300*550, 1200*450 Wattage required - 530 watts, 7 nos of UVGI lamps
2100 cfm and duct size - 300*300 Wattage required - 255 watts, 3 nos of UVGI lamps
18000 cfm and duct size - 1450*400, 1150*400 Wattage required - 470 watts, 6 nos of UVGI lamps
11000 cfm and duct size - 400*400, 400*600 Wattage required - 370 watts, 5 nos of UVGI lamps
17500 cfm and duct size - 1200*550, 550*700 Wattage required - 460 watts, 6 nos of UVGI lamps
20000 cfm and duct size - 1400*550, 1000*550 Wattage required - 500 watts, 7 nos of UVGI lamps
19250 cfm and duct size - 1700*500, 650*350, 650*350 Wattage required - 485 watts, 6 nos of UVGI lamps
17500 cfm and duct size - 1400*550, 800*450 Wattage required - 460 watts, 6 nos of UVGI lamps
12750 cfm and duct size - 1600*550 Wattage required - 420 watts, 6 nos of UVGI lamps
3600 cfm and duct size - 900*300 Wattage required - 280 watts, 4 nos of UVGI lamps
4400 cfm and duct size - 850*350 Wattage required - 290 watts, 4 nos ofUVGI lamps
3200 cfm and duct size - 850*300 Wattage required - 280 watts, 4 nos of UVGI lamps
6500 cfm and duct size - 1200*400 Wattage required - 320 watts, 4 nos of UVGI lamps
10000 cfm and duct size - 1550*500 Wattage required - 370 watts, 5 nos of UVGI lamps
12000 cfm and duct size - 2000*550 Wattage required - 400 watts, 5 nos of UVGI lamps
11750 cfm and duct size - 1500*750 Wattage required - 370 watts, 5 nos of UVGI lamps
9975 cfm and duct size - 1200*550 Wattage required - 370 watts, 5 nos of UVGI lamps
4530 cfm and duct size - 800*350 Wattage required - 300 watts, 4 nos of UVGI lamps
12000 cfm and duct size - 1500*550 Wattage required - 400 watts, 5 nos of UVGI lamps
12750 cfm and duct size - 2000*550 Wattage required - 420 watts, 6 nos ofUVGI lamps
9675 cfm and duct size - 1100*450 Wattage required - 370 watts, 5 nos of UVGI lamps
2100 cfm and duct size - 500*300 Wattage required - 265 watts, 4 nos of UVGI lamps
Supply of AHU coil cleaning chemical i.e. Vaniklin WB as per the standard conditions. To remove the dust particles stipulated on the AHU coils.
Supply of AHU filter cleaning chemical i.e. Lysol (Cresol 50% + Soap 50%) as per the standard conditions. To kill the germs and bacteria stipulated on the AHU filters.
stage.html
html • 0.02 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .