Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹79.5 LAccepted-AOC 10TH FLOOR UNIT 2 TECHNIPLEX 2 VEER SAVARKAR FLYOVER S V ROAD GOREGOAN WEST MUMBAI 400 062 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400062 | ₹79.5 L Quoted ₹79.7 L | L1 | Accepted-AOC Award of contract |
| 2 | Rejected-Technical | - | - | Rejected-Technical Technically disqualified |
| 3 | Rejected-Technical | - | - | Rejected-Technical Technically disqualified |
| 4 | Rejected-Technical | - | - | Rejected-Technical Technically disqualified |
| Sl No | Description | Qty | Unit | VAV Airconditioning L1 |
|---|---|---|---|---|
| 1.00 | HVAC Works | 1 | Nos | 67,11,502 ₹67.1 L |
| 2.00 | Fire Fighting Works | 1 | Nos | 12,56,337 ₹12.6 L |
Tender Value
₹96.8 L
EMD Value
₹1.9 L
Closing Date
4 Aug 2025, 6:55 pmClosed
OIC, Engineering TMC on behalf of Director, TMC
Engineering Department, 6th floor, Service Block, TMH, Parel
Proposed renovation of Auditorium, 2nd floor, GJB, TMH, Parel - HVAC Mechanical Works
2025_TMC_868103_2
TMC/Mech/HVAC/Auditorium/23
Open Tender
Machineries/ Mechanical Engg Items
120 days
TMH, Parel
As per tender document
5 documents required · 5 mandatory
₹0
₹1.9 L
28 Mar 2026
18 Jul 2025
6 Aug 2025
18 Jul 2025
4 Aug 2025
21 Jul 2025
Amount
HVAC Works
Fire Fighting Works
Description of Work / Item(s)
Amount
S.I.T.C. of 4 way type Chilled water Cassette Units complete as per technical specifications and including multiple speed fan control, intelligent drain-pump mechanism to be included, built in drain pump interlock, Factory made pre-fit valve assembly box with inlet outlet valve with and witjout strainer, including 2 way PICV/ PIBCV and supplied with LCD corded /cordless remote control. The Fan assembly shall include fan impeller with BLDC direct drive fan motor. The motor shall be sealed and lubricated for life, the whole assembly being statically and dynamically balanced. The motor shall be of the totally enclosed, permanent split capacitor type with thermal safety cut out. The evaporator coil shall be manufactured from seamless copper tubes with internal grooving, and mechanically bonded to aluminium fins. Units shall have power plug with 1.5 mtrs cable. 1 mtr inlet and 1 mtr outlet suitable dia copper piping tube thickness 1.2 mm insulated with with 19 mm thick nitrile insulation for connection with header. Capacity -1.5 TR / 600 CFM. Make - Sinco, Midea, Bhutoria, Trane.
Chilled water piping out of M.S. heavy class ERW C -class pipe (pressure rating PN 16) confirming to relevant IS 1239 Code upto 150 mm dia pipes, from 150 mm and above upto 2S0 mm dia 6 mm thick pipes and above 250 mm dia 6-8 mm thick pipes, with necessary fittings, teak wood gutties for indoor and hard puff blocks for outdoor pipes, elbows, tees, reducers. Suitable GI supports as specified.Insulated with 25 mm Nitrile insulation and commercial grade aluminium cladding. Pipe make - Tata / Jindal / SAIL Insulation make - Armacell, K-Flex
40 mm dia pipe
25 mm dia pipe
SITC of insulated Ball Valves as per relevent standards and specification. Make- Kitz/Audco/Advance/Castle
40 mm dia
32 mm dia
25 mm dia.
Supply and Installation of 5 mm wall thickness PVC drain piping for Air handling unit with all fittings and supports, saddle, pressure clamps etc with 9 mm thick tubular type nitrile insulation wrapped with glass cloth dipped in adhesive recommended by manufacturer and as per specification.
50 mm dia
Supply, installation, balancing and commissioning of factory fabricated GSS sheet ducting with Companion flange joints girth angle and MS angle of 50 mm x 3 mm. Metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, G.I. hangers, G.I. Angle supports etc. as per approved drawings and as per specifications of following sheet thickness complete as required. Make- Jindal / Sail / Tata
22Gauge GI ducting
20 Gauge GI ducting
18 Gauge GI ducting
Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc as per specifications. Make- Dynacraft, Cosmos, System Air, Trox
Supply and Fixing of Extruded AL powder coated Linear Grill with 4 side flanges and AL Box Damper. Make- Dynacraft, Cosmos, System Air, Trox
Supply and Fixing of Extruded AL powder coated Linear Grill with 4 side flanges without damper Make- Dynacraft, Cosmos, System Air, Trox
Supply fixing testing commissioning of supply air diffusers of powder coated AL with AL volume control dampers with anti smudge ring & removable core. Make- Dynacraft, Cosmos, System Air, Trox
Supply fixing testing commissioning of Return air diffusers of powder coated AL without AL volume control dampers, with anti smudge ring & removable core. Make- Dynacraft, Cosmos, System Air, Trox
Supply and Fixing of Silent Air Swril Diffuser with radilly arranged control blades with factory fabricated plenum box damper. for Supply air. Make- Dynacraft, Cosmos, System Air, Trox
Supply fixing testing commissioning of Perforated supply air diffusers of powder coated AL with AL volume control dampers with anti smudge ring & removable core and factory fabricated plenum. Make- Dynacraft, Cosmos, System Air, Trox
SITC of linear 2 slot diffuser as per specification.
S/F of canvas Piece According to Duct size.
SITC of motorised combined smoke and fire damper (UL listed, leackage S1 class) complete with control panel and all control wiring with necessary accessories to ensure proper functioning of damper as per standards. Make- Caryaire/Trox/Ravistar/Comos/System Air.
SITC of Smoke and Fire Damper. Make- Caryaire/Trox/Ravistar/Cosmos/System Air.
SITC of Actuators for above dampers. Make- Belimo/Siemens
SITC of thermal Insulation with Closed Cell Elastomeric Nitrile Rubber with Density 40 to 55KG & Thermal conductivity shall not exceed 0.035 W/(m. K) at mean temperature of 0C as per EN 12667.Covering material shall be of multiple layered laminate of polymeric material reinforced with scrim with a special UV protection with Black colour. Mat FINISH, 380 ± 20 GSM as per ASTM D 646. &ASTM E 252 and have good UV resistance as per ISO 4892-2 Method A tested for 1000 Hrs, the tensile strength of >5 MPa in MD & CD as per ASTM D 638 – All INSULATION SHALL BE WETTED WITH MANUFACTURER. Exposed Joints to be seal with recommended sealant. Make - Armaflex/Vidoflex/Fireflex/ALP
Supply & Installation of Acoustic lining on GI Supply air ducts. The Acoustic material shall be 15 mm thick open cell elastomeric foam class '1'. The density shall be 140 to 180 kg.m3 with thermal conductivity of 0.047 W/ m2k Deg @20deg .Material shall have anti-bacterial properties The insulation shall be as per technical specification and drawings etc, All joints to be sealed with anti condensation tapes. All loose ends to be trated with nosing frames as per details provided in Typical connection details drawing. Make : Armaflex, Vidoflex, fireflex, ALP
Supply, installation, of Room Acoustic lining insulation non fibrous, asbestors free of 15mm thick open cell nitrile rubber accoustic insulation with sound absorption property with desnity of 140-180 kg/m3 shall install with 2.5 mm thick mass loaded vinyl sheet of 2000 kg/m3 to achive sound reduction as specified in specification (AHU ROOMS). Mass vinyl sheet should be tested for weighted sound reduction index as per ISO 10140-2 and both open cell and mass loaded vinyl sheet should be class 1 fire rated as per BS 476 part 7. Adhesive used for sealing the insulation shall be non-flammable and with loe VOC content (maximum 850gm/I as per IGBC guide lines) strictly as per manufacture's recommendations. Manufactures representative should guide the installtion work at start of application wotk free of cost and should confirm quality of the insulation work done as per manufacturers standard in middle of insulation application work. Make : Armaflex, Vidoflex, Fireflex, ALP
Supply, Installation of Under-deck Roof insulation with COA-25MM/EDU-BK12 Nitrile Rubber Insulation Insulation shall be Closed Cell Elastomeric Nitrile Rubber with Density 40 to 55KG & Thermal conductivity shall not exceed 0.035 W/(m. K) at mean temperature of 0C as per EN 12667.Covering material shall be of multiple layered laminate of polymeric material reinforced with scrim with a special UV protection with Black colour. Mat FINISH, 380 ± 20 GSM as per ASTM D 646. &ASTM E 252 and have good UV resistance as per ISO 4892-2 Method A tested for 1000 Hrs, the tensile strength of >5 MPa in MD & CD as per ASTM D 638 – All INSULATION SHALL BE WETTED WITH MANUFACTURER. Exposed Joints to be seal with recommended sealant. In addition Insulation to be screwed to the ceilig with SS screw PVC rawal plugs, PVC washers etc. Make : Armaflex, Vidoflex, Fireflex, ALP
Structural steel work : With M.S.channel, M.S.angle, M.S. plate at all levels including supplying, cutting, fabricating, welding or bolting, errecting and fixing in position including painting with a primary coat of approved amke Zinc Chromate primer, including cost of materials labour directed by engineer in charge with two coats of enamel paint. Neccessary arrangement of scaffolding to be made by vendor. Vender shall take all safety precaution while execution of work. Make - Tata / Jindal
SITC of 1100 V a.c. grade FRLS PVC armoured AL/CU cabling along with appropriate size of saddles,spacers complete with GI conduit in approved manner. Make- Polycab/RRK/Finolex
3 Core x 4 Sqmm CU Cable
3 Core x 2.5 Sqmm CU Cable
3 Core x 1.5 Sqmm CU Cable
2 Core x 1.5 Sqmm CU Cable
4 Core x 4 Sqmm CU Cable
SITC of GI earthing of 8 SWG including end connections complete in all respect.
Supply, installation, testing and commissioning of Tube / Vane Axial Flow type fresh / exhaust air fan of following capacity with powder coated MS/ GSS casing and aluminium alloy impellers with high efficiency aero-foil sections, blades, the impeller directly driven by TEFC induction motor (EFF- 1) and 'H' class insulation suitable for 1Phase or 3 Phase, 50 Hz, 415±10% Volt, ac supply, Suitable capacity of TP isolator within M.S enclosure box with suitable length of Fire Survival (LPCB approved) cable for connection with fan from isolator complete as required and as per specifications. Fans should be AMCA certified for air & sound performance & should be statically & dynamically balanced upto G 2.5 as per latest ISO & AMCA standards. Entire fan model and AMCA seal shall appear in technical submittal of fan. The sound pressure should not exceed 85 db(A) at a distance of 3 Mts. Fan and Motor for Fire exhaust fans shall be suitable for operation at minimum 250 deg C for 2 hrs. and shall be UL/CE/TUV certified. Fan should be complete with all accessories including fire rated canvas connection with metallic flange, vibration isolators, gravity louvers, bird screen as specified in the specification. Fan total efficiency should not be less than 70%. Make- Greenheck, System Air, Ebm nadi
Smoke Exhaust Air Axial Fan 7000 CFM
Smoke Control Press. Axial Fan 10000 CFM
Supply,installation, testing and commissioning of electrical starter panel for smoke exhaust and fresh air fans with appropriate motor, protection circuit breaker, overload relay, control wiring with auto and manual functions potential free contacts to be provided to interlock with local emergency fire panel, Starter panel shall be Comprising of all electrical accessories for smooth operation of fan including suitable starter for thesame. MCB, DOL/Star-delta Starters, neccessary safety controls, RYB indication, ON/OFF indications, start/stop and emergency stop push button, Step down transformer as required to operate the fan on receiving signal from smoke dector. Panel should be with control relay logics for operation of AHU damper, Exhaust fan damper, Exhaust fan and AHU based on input from fire panel. Makes- Elecrical Panel - Shivam Electricals/ Arrow Engineering / Adarsh Electricals MCB- LT / Schneider Starter- LT/ Shneider RYB Indications - Vaishnoy/ LT On/Off Indications - Vaishnoy/ LT
Starter 5.5KW 3PH
Supply and laying of 2C x 1.5 Sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring and LSZH outer sheath comlete as required. Colour - Red. Make -Polycab / Caliplast / Century
Supply,Installation, Testing & Commissioning of addressable, UL listed, Photoelectric smoke detector with Heat element(57Deg C), 0.5% to 2.35% per foot obscuration,loop powered, class A wired, low profile, temper resistant, low quiescent current, 360Deg View LED, Rotary/DIP decimal address setting switch,24V DC(15-32V), suitable for below & above false ceiling, complete with Base, wiring box, In/Out cable glands. Make- Siemens Cerberus FIT / Bosch / Honeywell Esser
Supply and application of Fire-Retardant Ductwork. Ducts shall be coated with Fire Resistance coating of minimum 600-700 micron (DFT) thickness applied over ducts to provide 2 hours Fire rating. The Fire Resistance coating shall be tested as per requirements of BS 476 : part 6 'Class O' and part 7 'Class 1' and BS 476 part 24 (Type A and B) to analyze stabiltiy, integrity,insulation performance for 2 hours, the duct sheet shall also conform to performance criteria (stability, integrity, insulation) without insulation for 2 hours. The average and maximum temperature of unexposed faces with or without insulation shall not exceed 140 deg. Cel and 180 deg. Cel respectively to ensure the insulation performance criteria . The coationg shall be free or has minimum toxic elements such as lead, mercury, arsenic and has low VOC less than 50 gm/ liter. Coated Ducts shall be treated externally with 48 Kg/m3, 50 mm thick mineral wool insulation laminated with aluminium foil. Make :- Feukem / Hilti / 3 M
Supply, Installation, Testing and Commissioning of addressable, UL listed, Control module (with 6 out puts) with relay for AHU/Damper/switch gear operation, loop powered, class A wired, low quiescent current, rotary/DIP decimal address setting switch, 24V DC(15-32V), Suitable for surface/recess installation, wiring box, in/out cable glands Make-Honeywell/Tyco/Siemens/Bosch
Buy Back Items
Buy-Back (ie minus)Amount of Removing of old ducting, insulation, supports, old piping of fire fighting system with sprinklers supports and debries generated etc in the auditorium and AHU room. Taking out of TMH premises and disposing in proper manner is in the scope of the vendor IMP NOTE Removing and fixing of ducting, insulation and fire fighting piping shall be above 18 feet height. M.S. Angle of 50 mm x 50 mm x 3 mm to be considered for SA/RA Ducting above false ceiling. One shut down activity to be considered for Chilled water piping connection. Material to be procured as per site requirement only.
Description of Work / Item(s)
Amount
Supplying, installing and testing & commissioning above ground GI .Steel Pipe of Heavy class C ERW of following sizes conforming to IS 1239 & IS 3589 along with fittings,pipe support, nuts, bolts, washers, gaskets etc as required& with 2 coats epoxy, primer suitable for GI pipes and 2 coats final red acrylic painting suitable for GI pipes thereafter complete in all respect(Pipes: Tata, Jindal, SAIL; Make Paints: Asian/Berger/ICI)
100mm dia
40mm dia
32mm dia
25mm dia
Supply, fixing, testing and commissioning of following valves, as per specifications:-Butterfly valve (manual) with C.I body SS disc nitrile sheet & O ring & PN 16 Pressure rating as specified . It should be complete in all respect & as per directions of Engineer-in-charge. Make ADVANCE, INTERVALVE ,KITZ ,SANT
150mm dia
100 mm dia.
40mm dia
SITC of Pendant/Upright Type 3 mm Quick Response, Standard Coverage, UL Listed or FM Approved Sprinklers K80 operating at 68 degC with required GI socket complete in all respect & as per directions of Engineer-in-charge. Make: Tyco/Viking/HD Fire
SITC of Flexible SS Dropper Pipe Braided for K 80 sprinkler, 1.5 meter long, UL Listed or FM approved complete with all accessories like nipple, GI square bar, necessary GI brackets, gaskets, isolation ring and reducer for securing the pipe, maximum rated pressure 200 psi, Hydro test pressure 250 psi, Burst Pressure 870 psi complete in all respect & as per directions of Engineer-in-charge. , Make: Tyco, HD Fire, Spectra
SITC of SS Round Rossette Plate for false ceiling mounting with Chrome finish, working pressure 1.2 MPA as Required. Make: Sainath, HD Fire,NEWAGE,TYCO,VIKING
Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.Make-NEWAGE,SAFEX ,NITIN FIRE
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required Make ADVANCE, INTERVALVE ,KITZ ,SANT
100mm dia
40mm dia
Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required.100mmMake: Honeywell, Siemens, Yokogawa
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid