Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.9 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹12.7 L+₹55,100 (4.55%)Rejected-Finance | L2 | Rejected-Finance Being other than L1 | |
| 3 | L3₹13.4 L+₹1.3 L (10.8%)Rejected-Finance 34 1 12 2F SAINIK VIHAR DEORI ROAD AGRA UP 282007 | AGRA | UTTAR PRADESH | 282007 | L3 | Rejected-Finance Being other than L1 | |
| 4 | L4₹17.6 L+₹5.5 L (45.2%)Rejected-Finance | L4 | Rejected-Finance Being other than L1 |
Tender Value
₹19.8 L
EMD Value
₹39,540
Closing Date
6 Aug 2022, 6:00 pmClosed
GE EAST AGRA
GE East Agra, Military Engineer Services, Gwalior House, 62 Taj Road Agra Cantt 282001
REPAIR/ REPLACEMENT OF INTERNAL WIRING, SWITCHES SOCKETS AND DBS INCLUDING ELECTRICAL FITTING / FIXTURES IN PARA HANGERS UNDER GE (E) AGRA
2022_MES_536159_1
9503/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AGRA
Please refer tender documents
9 documents required · 9 mandatory
₹500
Yes
GE EAST AGRA
₹39,540
Yes
26 Aug 2022
6 Jul 2022
17 Aug 2022
6 Jul 2022
6 Aug 2022
21 Jul 2022
Amount
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc. complete and all as specified and removing from site.
M&L point wiring with 1.5 sqmm multi stranded copper conductor 1100 volts. grade FRLS PVC insulated unsheathed cable with proper colour coding drawn in including stove enammelled steel conduit not less than 20 mm dia with all accessories and FR PVC insulated 1.5 Sqmm multi standard sheathed copper wire for continues earth, sunk in cast iron/Pressed steel terminal boxes 60 mm deep & 1.6 mm thick duly painted with aluminum inside and anticorrosive paint out side/PVC polycarbonate PVC rectangular block 50 mm deep, including 3 mm thick plastic laminated sheet for mounting switches, sockets, fan regulators etc connecting earth and making good to the disturbed surface of wall/floor and matching with existing specifications. Connections of cable with MCB's or bus bar shall be done through proper size copper/brass thimbles. Make Polycab/Finolex/RR Kablel/Grandlay. Note :Conduit shall be fixed on surface of roof with necessary saddles where concealing of conduit is not feasible at no extra cost for the following :-
One light /fan point controlled by one switch
One 5 pin socket outlet 5 Amps on independent board
One 5 pin socket outlet 5 Amps on same board
All as per item No 2 above but with 2.5 sqmm multi stranded copper conductor 1100 volts grade FRLS PVC insulated sheathed cable with FR PVC 2.5 Sqmm multi standard insulated unsheathed copper wire for continues earth on independent board
Supply and fix switch piano flush button single pole one way 5 amps 240 volts with polycarbonate body all as specified and directed. Make : Plaza/Cona/Havells
Supply and fix Switch piano flush button single pole one way 15 amps 230 Volts with polycarbonate body all as specified and directed. Make : Plaza/Cona/Havells
Supply and fix socket 5 amps 5 pin flush type, 240 volts. with polycarbonate body. Make : Plaza/Cona/Havells
Supply and fix socket out let, 6 pin 5 and 15 amps multi purpose 2 in 1 flush type, 230 volts with polycarbonate body all as specified and directed. Make : Plaza/Cona/Havells
Supply and fix stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc. as reqd, complete all as specified and directed. Make : Plaza/Cona/Havells
Supply and fix ceiling rose, PVC/poly carbonate, isolated body suface bakelite 65mm dia three terminals all as specified and directed. Make : Plaza/Cona/Havells.
Supply and fix Lamp holder/angle holder insulated body with black/white plate for batten fittings all as specified and directed. Make : Plaza/Cona/Havells.
Supply and fix of LED Bulb 7 W, warm white all as specified and directed. Make : Cat Pt No LHLDEUHEML8R009 of Havells or equivalent in Bajaj/Philips/Wipro
Supply and fix in repair energy saving 13.5 Watt LED IP 65 bulk head luminaries, complete with all accessories, internally pre wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size 230V,50 HZ all as specified and directed. Make : Cat Pt No LHEXCGP7IN5W013 of Havells or equivalent in Bajaj/Philips/Wipro
Supply and fix in repair LED lights fitting 1x 20W(batten and rod separate), 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as as specified and directed. Make : Havells/Bajaj/Philips/Wipro
Supply and fix in repair Highbay light fitting 130W, Extra Efficient (150 Lm/W) next Gen Highbay with Elliptical design, modular lens Optics for optimized Lighting distribution to improve 20% operational efficiency, with EMC/ EMI Complient Potted Driver & easy maintenance, Flicker free Illumination for Industrial Space., surge protector, BIS electronic driver, etc and all accessories pre-wired including connecting up with PVC insulated copper conductor cable 2.5 sqmm , 3 core as required for connections etc. complete all as specified and directed. Make: Cat part No BY325P LED 130S CW PSU GR FG WB XTFCL V1 of Philips or equivalent of make Bajaj/Havells.
Supply and fix in repair LED flood light 100 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and directed. Make : Havells/Bajaj/Philips/Wipro
S&F sub Main Wiring with two single core FRLS PVC insulated unsheathed multistranded flexible copper conductor cable of size 2x1.5 sqmm and one single core PVC insulated multistranded unsheathed flexible copper conductor 1x1.5 sqmm size (green colour) cable as earthing lead connecting to main earthing dolly drawn in Steel Conduit not less than 20 mm dia including dismantling of old unsv submain wiring complete all as specified and directed by Engineer-in-charge including taking down of existing un serviceable sub main wiring complete.Make Polycab/Finolex/RR Kablel/Grandlay
S&F sub Main Wiring with two single core FRLS PVC insulated unsheathed multistranded flexible copper conductor cable of size 3x6 sqmm and one single core PVC insulated multistranded unsheathed flexible copper conductor 1x4 sqmm size (green colour) cable as earthing lead connecting to main earthing dolly drawn in Steel Conduit not less than 20 mm dia including dismantling of old unsv submain wiring complete all as specified and directed by Engineer-in-charge including taking down of existing un serviceable sub main wiring complete.Make Polycab/Finolex/RR Kablel/Grandlay
S&F sub Main Wiring with two single core FRLS PVC insulated unsheathed multistranded flexible copper conductor cable of size 3x16 sqmm and one single core PVC insulated multistranded unsheathed flexible copper conductor 1x10 sqmm size (green colour) cable as earthing lead connecting to main earthing dolly drawn in Steel Conduit not less than 32 mm dia including dismantling of old unsv submain wiring complete all as specified and directed by Engineer-in-charge including taking down of existing un serviceable sub main wiring complete.Make Polycab/Finolex/RR Kablel/Grandlay
Supply & fix in repair sheet metal enclosure Vertical TPN DB 8 way as per IEC 61439-3, Suitable for Flush Mounting and Surface Mounting, With 250 A Copper Busbar for each phase with 2 Neutral bar, 2 Earthbar and Cable ties for Cable management, fully insulated busbar & shrouded Neutral bars, Improved Pan assembly for ease of installation, Prefitted masking sheet, Reversible Door for IP 43 & IP 54 DB's, With provision for DPX³ 250 MCCB as incomer and SP/TP MCB's as outgoing, Complete all as specified and directed. Make : Legrand/Schneider (Acti-9)/L&T/Hager .
Supply & fix in repair sheet metal enclosure MCB distribution board. triple pole & neutral 415 volts 6 way with IP-43 protection double door suitable for including MCB as incommer complete with appropriate size bus bar and neutral link, fixed flush in wall including chases wall for fixing DB and making good distributed wall surfaces to match with existing specification all as specified and directed. Make : Legrand/Schneider (Acti-9)/L&T/Hager .
Supply, fix in repair of MCCB 4 Pole, 415 V, Adjustable type, 250 Amps with breaking capacity 36 KA, complete all as specified and directed. Make : Legrand/Schneider (Acti-9)/L&T/Hager .
Supply & fix in repair sheet metal enclosure MCB distribution board. Single pole & neutral 240 volts 4 way with IP-43 protection double door complete with appropriate size bus bar and neutral link all as specified and directed. Make : Legrand/Schneider/L&T/Hager
Supply & fix in repair sheet metal enclosure MCB distribution board. Single pole & neutral 240 volts 8 way with IP-43 protection double door complete with appropriate size bus bar and neutral link all as specified and directed. Make : Legrand/Schneider/L&T/Hager
Supply and fixing in repair MCB TP 25 to 63 Amp rating 240V, 10KA 'C' curve and current carrying capacity in the MCB DB complete with connection testing and commissioning complete all as specified and directed. Make : Legrand/Schneider (Acti-9)/L&T/Hager .
Supply and fixing in repair MCB TPN 40 to 63 Amp rating 240V, 10KA 'C' curve and current carrying capacity in the MCB DB complete with connection testing and commissioning complete all as specified and directed. Make : Legrand/Schneider (Acti-9)/L&T/Hager .
Supply and fixing in repair MCB SPN 40 to 63 Amp rating 240V, 10KA 'C' curve and current carrying capacity in the MCB DB complete with connection testing and commissioning complete all as specified and directed. Make : Legrand/Schneider (Acti-9)/L&T/Hager .
Supply and fixing in repair MCB SP 1 to 32 Amp rating 240V, 10KA 'C' curve and current carrying capacity in the MCB DB complete with connection testing and commissioning complete all as specified and directed. Make : Legrand/Schneider (Acti-9)/L&T/Hager.
Supply and fix MCB isolator four pole 415 volts any rating 100 amps, with rupturing capacity 10 KA ` C' series, including providing thimble for out going cables complete all as specified and directed. Make : Cat Pt No 4086 80 of Legrand/Schneider (Acti-9)/L&T/Hager .
Taking down ceiling fan/exhaust fan, sealing cable end, dismantling blades and removing fan and blades to store, complete all as specified and directed
Refixing ceiling fan/ exhaust fan received from item No - 29 here in before and connecting up including provision of cable from ceiling rose or connector to fan.
M&L for earthing complete with galvanised steel earth plate electrode size 600x600x6.0mm thick buried directly in ground vertically in a pit of depth not less than 2.25 mtr below ground levels with top edge of the earth plate not less than 1.5 mtr below normal ground level surrounded from all sides by mixture of charcoal and common salt (100 kg each) and electrode connected to and including galvanised earth strip 25X4 mm means of bolts, nuts, check nuts and washers of galvanised steel and GI pipe light grade 20mm dia bore for watering funnel with wire mesh. CI cover with frame, PCC chamber pit with PCC 1:3:6 type C-2 excavation and earth work all as shown in electrical plate No 3 connected to earthing test point all as specified or indicated including testing on completion. NOTES : 1. The unit rate includes for protection pipe and GI wire dia from top of earth plate up to7.50 meter above ground level. 2. Filling of earth pit shall be done from vegetable soil,soil should be from any type of stone,aggregate,boulders or impurities except vegetable soil. 3. Rates of excavation, removal & returning filling of soil shall be deemed to be included .
M&L Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4 mm dia galvanised iron or steel wire complete all as specified and directed.
Supply and fix 3 phase and neutral copper Bus bar chamber of 100 amps, complete fixing on walls/angle all as specified and directed
Supply and lay XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 25 Sqmm 3.5 Core, Complete all as specified and directed. Make : KEI/Polycab/Havells.
Excavating in trenches n exc 1.5m wide and n exc 1.5m deep and getting out in hard/dense soil complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers n exc 25cm complete all as specified and directed.
Removing excavated material n exc 50m and depositing where directed at a level n exc 1.5m above the starting point complete all as specified and directed.
Material and labour for sand cushioning with dry river sand in trenches for cushioning of underground cable line including spreading, leveling, well ramming completed all as specified and directed.
Supply and laying well burnt sub class ‘B’ bricks. ( designated 75) locally available best quality laid dry in trenches for protection of underground cable all as specified and directed.
Supply and lay Tubes,'light grade' galvansized 40mm dia for cable protection with all fitting and fixed complete to walls and ceiling or laid in floors/road crossing all as specified.
Balaji Associates
M/S OM Enterprises
jmd engineers
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .