Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Admitted-Finance | Admitted-Finance |
Tender Value
₹7.9 L
EMD Value
₹16,000
Closing Date
2 Jan 2024, 2:00 pmClosed
HOS Maintenance
IPM Section
Restoration and shifting of main outdoor feeder panel including associated works near cricket ground in IIT Guwahati Campus
2023_IITG_786524_1
IITG/IPM/NIT/R/2023-24/59
Open Tender
Electrical Works
Works
60 days
IIT Guwahati
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹16,000
Yes
8 Apr 2024
21 Dec 2023
3 Jan 2024
21 Dec 2023
2 Jan 2024
21 Dec 2023
Amount
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Above 185 sq. mm and upto 400 sq. mm
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Above 95 sq. mm and upto 185 sq. mm
Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3½ X 185 sq. mm
3½ X 300 sq. mm
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV
3½ X 185 sq. mm (57mm)
3½ X 300 sq. mm (70mm)
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.
400 A,50KA,FPMCCB
Supply, installation, testing, erection and commissioning of Outdoor Type LT Feeder Pillar Panel Board including preparation of base frame required for erection of panel:- The panel board will be floor mounted outdoor type, 3Ph 4Wire, 415V, 50Hz, AC supply system, free standing, dust and vermin proof, fabricated from 2mm CRC Sheet, finished with powder coating after chemical treatment & providing TPN 500A aluminum bus bar & wiring, consisting of the following feeders:- As Incomer 400A, 4P, 36KA, MCCB 1 nos Spreader link for 400A, 4P, MCCB 1 nos Digital Multifunction meter (V,A,PF,KW,KWH) 1nos LED Indicator lamp 1 nos CT 400/5A, Cl-1, Tape wounded 3 nos 6A, SP, MCB 3 nos As Outgoing 320A, 4P, 36KA, MCCB 1 nos Spreader link for 320A, 4P, MCCB 1 nos 200A, 4P, 36KA, MCCB 2nos Spreader link for 320A, 4P, MCCB 2 nos 100A, 4P, 25KA, MCCB 2 nos Spreader link for 100A, 4P, MCCB 2 nos Earthling bus 1 nos
Supplying of following size XLPE insulated and PVC sheathed aluminium conductor armoured power cable
3.5 core 185 sq.mm
3.5 core 300 sq.mm
Mudoi Enterprise
M/S ANUSHREE CONSTRUCTIONS & ASSOCIATES
KUMAR ELECTRICALS
GDB Engineering
JYOTI ELECTRICALS
ashirwad enginners
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .