Loading…
Loading…
Tender Value
₹73.3 L
EMD Value
₹1.5 L
Closing Date
25 Jun 2026, 11:00 pm
Karnataka Power Transmission Corporation Limited
Stringing of 2nd circuit line
306202
KPTCL/2026-27/TL/WORK_INDENT3639/CALL-2
Open
Transmission Line
KPTCL CEE Transmission Zone Office Mysuru
4 documents required · 0 mandatory · 4 optional
Past Experience Documents (if any) such as LOI or LOA, DWA, Work Done Certificate, Performance Certificates from KPTCL and Non-KPTCL in last 05 years
valid Super grade Electrical Contractor License issued by the Government of Karnataka as on the date of opening of techno-commercial bid (refer 2.3 of ITT)
Construction equipment owned by the tenderer and equipment proposed to be deployed on this contract, if awarded
Reports on the financial standing of the tenderer, such as profit and loss statements and auditors reports for the last five years as per 3.10(iv) of ITT.
Qualification and experience of the key technical and management personnel in permanent employment with the tenderer and those that are proposed to be deployed on this contract, if awarded as per 3.10(xv) of ITT.
3.6: Tenderers who meet the above specified minimum qualifying criteria, will only be qualified, if their available tender capacity is more than the total tender value. The available tender capacity will be calculated as under:Assessed Available Tender Capacity: (AxNx2.5-B)Where A-Maximum value of works executed (KPTCL & Non-KPTCL) in any one year during the last five years (updated to FY 2024-2025) taking into account the completed as well as works in progress.
3.7: Even though the Tenderers meet the above criteria, they are subject to be disqualified if they have:- Made misleading or false representations in the forms, statements and attachments submitted in proof of the qualification requirements and/or- Record of poor performance such as abandoning the works, not properly completing the contract, inordinate delays in completion, litigation history, or financial failures etc. and/or- Participated in the previous Tender for the same work and had quoted unreasonably high Tender prices and could not furnish rational justification.
Minimum Average Annual Turnover (MAAT) of the bidder for best two years out of last preceding five financial years ending on March or December as the case may be, shall not be less than Amount put to Tender (APT) as per 3.2(a) of std tender documents(ITT).
The bidder should furnish as per 3.10(iv) of ITT along with UDIN details
As per 3.2 b) Qualifying Requirements (Technical) as per Details of Work Experience (format uploaded in Bid documents page)
Bidder shall ensure that soft copies of No Deviation CERTIFICATE, Letter of Undertaking, as revised in Annexure , Any other undertaking / agreement (if applicable) are uploaded besides submitting the Originals to the office of the Chief Engineer, Electy., Operation, KPTCL, Mysore, after the last submission date and on or before the date & time of opening of techno commercial bids.
Bidder shall ensure that soft copies of i. Letter of undertaking for Non performance ii. Letter of undertaking for Risk and Cost iii. Letter of undertaking for Litigation iv. Letter of undertaking to source the supply of equipment material from only KPTCL approved Vendors (if applicable) are uploaded in portal
i) Letter of undertakings as per clause No.1.5 of Annexure-XVII and (ii) Letter of undertaking as per clause No.1.6 of Annexure-XVII (if applicable) shall be uploaded besides submitting the Originals to the office of the Chief Engineer, Electy., Operation, KPTCL, Mysuru, after the last submission date and on or before the date and time of opening of techno commercial bids.
The Originals of Undertakings & Formats in ORIGINAL shall be submitted to the office of the Chief Engineer, Electy., Operation, KPTCL, Mysuru, after the last submission date and on or before the date and time of opening of techno commercial bids as per 3.10(xviii) of ITT.
Bidder shall upload selfdeclaration stating that no such actions against the bidder haven been taken by KPTCL in the last 6 months as on date of bid submission invoking Risk & cost, failing which the offer is liable to be rejected (refer clause 3.10(ii) of ITT.
3.2 b)For 66/110 kV Terminal bay: Qualifying Requirements(Technical): i) The Bidder should have satisfactorily constructed, completed and commissioned atleast (01) No. of 66kV voltage class or above voltage class Sub-Station /Terminal bay work on Total or Partial Turnkey Basis in the last 10 years preceding the date of bid submission and shall be in satisfactory service for a minimum period of One(1) year prior to the date of submission of the Bid OR The Bidder should have satisfactorily constructed, completeed & commissioned not less than Five(05) of 33kV or above voltage class Sub station/ Terminal bays works on Total turn key/ partial turn key Basis in the last 10 years preceding the date of bid submission and shall be in satisfactory service for a minimum period of One (01) year prior to the date of submission of the Bid. Strenghtening/RE-conductoring of Transmission lines: Bidder should have satisfactorily constructed, completed and commissioned 66kV or above voltage class transmission line commulatively to an extent of atleast 25% of the route lenght(Kms) of transmission line tendered on total/partial turn key basis in the last 10 years preceeding in the date of Bid submission and same shall be in the satisfactory service for a minimum period of 1 year prior to the date of submission of bid.
ESI certificate
EPF certificate
Shall Submit the ATTESTED xerox copies of Audited Profit & Loss statements of past 05 years along with Seal & Sign of the bidder to the office of the Chief Engineer, Electy., Operation, KPTCL, Mysuru, after the last submission date and on or before the date and time of opening of techno commercial bids.
Liquid Assets and /or availability of credit facilities of no less than 30% of the Amount put to Tender (Credit lines/ Letter of credit/ certificates from banks for meeting the fund requirement etc. shall be uploaded in portal and hardcopy with bidder seal & signature shall be submitted to Tendering Authority)
Any other required documents as per the terms and conditions of the tender.
₹1,840
₹1.5 L
12 Jun 2026
12 Jun 2026
29 Jun 2026
18 Jun 2026
18 Jun 2026
G.Malligere LILO- Construction of 2nd circuit on existing DC towers from existing Jakkanahalli-Nagamangala tap point to 66/11kV G.Malligere substation for a distance of about 1.36kms with coyote ACSR Conductor in Pandavapura Taluk, Mandya district along with Construction of 01 No. of 66kV Terminal Bay at existing G. Malligere 66/11 kV Sub-Station for making LILO arrangement to Jakkanahalli-Nagamangala Tap point in Pandavapura Taluk Mandya District on Total Turn Key (TTK) basis/CALL-03
Fabrication and Supply of galvanised 66KV DC Narrow Based (KPTCL Design) Transmission Line Towers : Note :- Rate to be quoted on per MT basis A) TOWER TYPE 'DD'
a) BOX Cross arm- 01Nos.
Supply of Bolts, Nuts and washers etc., (galvanised) required for 66KV DC Narrow Based (KPTCL)Transmission Line Towers , Note :- Rate to be quoted on per MT basis
A) TOWER TYPE 'A'
a) Box cross Arm...
Conductor & Earth wire:
Coyote Plain Terrian
Tower Accessories
(i)Phase Plate (set of 3 No.)
INSULATOR STRINGS WITH CLAMPS, ARCING HORNS AND HARDWARE for ACSR Coyote Conductor
(i) Single Tension string of 5 units of 90 KN each along with hard ware for Coyote ACSR and arcing horn
ii) Double Tension string of 2X5 units of 90KN each along with hard ware for Coyote ACSR and arcing horn
iii) Double Suspension string of 2X4 units of 90KN each along with hard ware for Coyote ACSR and arcing horn
iv) Single Suspension string of 1X4 units of 90KN each along with hard ware for Coyote ACSR and arcing horn
Hardwares and ACSR Coyote Accessories
i) Hardwares and ACSR Coyote AccessoriesM S C Joints suitable for Coyote ACSR
ii) Repair sleeves suitable for coyote ACSR
iii) P G Clamps suitable for COYOTE ACSR
iv) Vibration dampers for coyote
v) Pre formed armour rods suitable for Coyote ACSR
Survey:Check survey using their own equipment for 66 kV Plain terrain.
Conducting drone survey of Transmission lines for collection of data along with Aerial inspection of EHV line Corridor using LIDAR method for Measurements of vertical, horizontal and ground clearances...
Fabrication and Supply of galvanised 66KV DC Narrow Based (KPTCL Design) Transmission Line Towers : Note :- Rate to be quoted on per MT basis A) TOWER TYPE 'DD'
a) BOX Cross arm- 01Nos.
Supply of Bolts, Nuts and washers etc., (galvanised) required for 66KV DC Narrow Based (KPTCL)Transmission Line Towers , Note :- Rate to be quoted on per MT basis
A) TOWER TYPE 'A'
a) Box cross Arm...
Conductor & Earth wire:
Coyote Plain Terrian
Tower Accessories
(i)Phase Plate (set of 3 No.)
Clearing of Bushes, branches of tree & crops for erection of tower & stringing of line for full corridor width
CIRCUIT BREAKER : 72 kV, 2500 A, 40 kA SF-6 Gas circuit breaker with semi-pneumatic / pneumatic operated / spring type operating mechanism including mounting arrangements bi-metallic terminal connect...
ISOLATORS : 66kV, 1250A, 40kA class double break Manually operated isolator with solid core insulators along with terminal connectors suitable for Drake ACSR
(i) Upright mounting type with Earth switc...
ii) Upright mounting type without Earth switch. LPH 4.60 Mtr.
CURRENT TRANSFORMER : Current Transformer Single phase, oil filled outdoor type with bimetallic terminal connectors suitable for drake ACSR.
(i) 66 kV class, 40KA, CT of ratio 400 - 200/ 1-1-1A for L...
SURGE ARRESTOR (Lightning Arrestors) : (Procelain housing) metal oxide, Gapless type with R bimetallic connectors suitable for drake ACSR.
(i) 60 kV, 10 KA, class - II, Normal duty Metal oxide type
Control and Relay Panel complete
(i) 66kV Transmission line Panel - simplex type
STATION STRUCTURES : 66kv side station structure fabricated out of galvanized mild steel including bolts and nuts
(i) Station towers(vertical 6T1)(0.956MT)-01Nos
ii) Station beams (6B1) (0.449MT)-01Nos
GI MOUNTING STRUCTURES :
(i) Isolator Live point height 4600 mm . (0.532MT per tower)-3NOS
ii) Current transformer. (0.158 MT per tower)-06Nos
iii) Lightening Arrestors. 66 kV. (0.116 MT per tower)-03NOS
iv) Post insulators for 66 kV Bus. (0.140MT per tower)-04NOS
BUS BAR FORMATION :
(i) Post insulator Solid core Insulator 66 kV
(i) C type wedge connector suitable for Drake - Drake
ii) Post insulator clamp suitable for Single Drake ACSR. 127/76 mm 66 kV
PVC Insulated copper control cable with lugs/ferrules
i) 19 Core 2.5 Sq.mm. Copper Control Cables
ii) 4 Core 6.0 Sq.mm. Copper Control Cables
iii) 4 Core 2.5 Sq.mm. Copper Control Cables
iv) 2 Core 6 Sq.mm. Copper Control Cables
Equipments required for establing SCADA Communication as per KPTCL Specification
(i) Multi functional Transducer (MFT)
ii) Opto coupler
iii) Current Cables-Copper Core with c/s 4.0 sq.mm Multistrand 4 Core
Voltage Cables-Copper Core with c/s 2.5 sq.mm Multistrand 4 Core
Signal Cables-armoured Copper Core with c/s 0.5 sq.mm Multi strand 10 Core
Control Cables- Copper Core with c/s 1.5 sq.mm Multi strand 10 Core
Supply Cables-Copper Core with c/s 4.0 sq.mm Multi strand 3 Core for AC input to UPS & UPS to RTU,conforming to KPTCL specifications.
Supply Cables-Copper Core with c/s 32.0 sq.mm Multi strand for Battery conforming to KPTCL specifications.
CIRCUIT BREAKER : 72 kV, 2500 A, 40 kA SF-6 Gas circuit breaker with semi-pneumatic / pneumatic operated / spring type operating mechanism including mounting arrangements bi-metallic terminal connect...
ISOLATORS : 66kV, 1250A, 40kA class double break Manually operated isolator with solid core insulators along with terminal connectors suitable for Drake ACSR
(i) Upright mounting type with Earth switc...
ii) Upright mounting type without Earth switch. LPH 4.60 Mtr.
CURRENT TRANSFORMER : Current Transformer Single phase, oil filled outdoor type with bimetallic terminal connectors suitable for drake ACSR.
(i) 66 kV class, 40KA, CT of ratio 400 - 200/ 1-1-1A for L...
SURGE ARRESTOR (Lightning Arrestors) : (Procelain housing) metal oxide, Gapless type with R bimetallic connectors suitable for drake ACSR.
(i) 60 kV, 10 KA, class - II, Normal duty Metal oxide type
Control and Relay Panel complete
(i) 66kV Transmission line Panel - simplex type
STATION STRUCTURES : 66kv side station structure fabricated out of galvanized mild steel including bolts and nuts
(i) Station towers(vertical 6T1)(0.956MT)-01Nos
ii) Station beams (6B1) (0.449MT)-01Nos
GI MOUNTING STRUCTURES :
(i) Isolator Live point height 4600 mm . (0.532MT per tower)-3NOS
ii) Current transformer. (0.158 MT per tower)-06Nos
iii) Lightening Arrestors. 66 kV. (0.116 MT per tower)-03NOS
iv) Post insulators for 66 kV Bus. (0.140MT per tower)-04NOS
BUS BAR FORMATION :
ii) Formation of Main/Cross bus with Single Drake
(i) Post insulator Solid core Insulator 66 kV
PVC Insulated copper control cable with lugs/ferrules
i) 19 Core 2.5 Sq.mm. Copper Control Cables
ii) 4 Core 6.0 Sq.mm. Copper Control Cables
iii) 4 Core 2.5 Sq.mm. Copper Control Cables
iv) 2 Core 6 Sq.mm. Copper Control Cables
Equipments required for establing SCADA Communication as per KPTCL Specification
(i) Multi functional Transducer (MFT)
ii) Opto coupler
iii) Current Cables-Copper Core with c/s 4.0 sq.mm Multistrand 4 Core
Voltage Cables-Copper Core with c/s 2.5 sq.mm Multistrand 4 Core
Signal Cables-armoured Copper Core with c/s 0.5 sq.mm Multi strand 10 Core
Control Cables- Copper Core with c/s 1.5 sq.mm Multi strand 10 Core
Supply Cables-Copper Core with c/s 4.0 sq.mm Multi strand 3 Core for AC input to UPS & UPS to RTU,conforming to KPTCL specifications.
Supply Cables-Copper Core with c/s 32.0 sq.mm Multi strand for Battery conforming to KPTCL specifications.
Earthmat formation:
(i) Grounding of equipments with 50 x 6 mm G I flat and connecting equipments to the earth mat/ground pit including all connected works with all materials supplied by the contra...
ii. Providing C.I. Pipe of 100mm ID 13mm thick 2.75 mtr. long with 2 part GI Flat 50x6mm clamp welded allround the pipe etc., including cost of excavation (all materials supplied by contractor)
iii. Supplying and fixing 450mm dia x 450mm height 1.5" to 2" Hume pipe collars for earth pits.
CIRCUIT BREAKER : 72 kV, 2500 A, 40 kA SF-6 Gas circuit breaker with semi-pneumatic / pneumatic operated / spring type operating mechanism including mounting arrangements bi-metallic terminal connect...
ISOLATORS : 66kV, 1250A, 40kA class double break Manually operated isolator with solid core insulators along with terminal connectors suitable for Drake ACSR
(i) Upright mounting type with Earth switc...
ii) Upright mounting type without Earth switch. LPH 4.60 Mtr.
CURRENT TRANSFORMER : Current Transformer Single phase, oil filled outdoor type with bimetallic terminal connectors suitable for drake ACSR.
(i) 66 kV class, 40KA, CT of ratio 400 - 200/ 1-1-1A for L...
Control and Relay Panel complete
(i) 66kV Transmission line Panel - simplex type
Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution li...
Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes...
Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with supe...
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by r...
Steel Fabrication: Supplying, fitting and placing TMT FE 550 / 550D Steel Reinforcement including cost of all materials, machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/w...
Removing the existing jelly and respreading after the completion of work as per direction of Engineer in charge.(10mX25m)
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT- Mys Tz- LILO G Malligere.docx
Tender Document • 0.04 MB
Tender Docs Mys Tz- LILO G Malligere.docx
Instructions to Tenderers • 0.50 MB
Download all tender documents and submit your bid