Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.0 LAccepted-AOC | L1 | Accepted-AOC Quoting Lowest rate | |
| 2 | L2₹6.4 L+₹44,000 (7.35%)Rejected-Finance 4 4 FAIRLIE PLACE ROOM NO 630A HMP HOUSE KOLKATA 700001 700001 CALCUTTA CENTRAL DIVISION WEST BENGAL 700001 | KOLKATA | WEST BENGAL | 700001 | L2 | Rejected-Finance Quoting Higher Rate | |
| 3 | L3₹6.5 L+₹51,001 (8.51%)Rejected-Finance | L3 | Rejected-Finance Quoting Higher Rate | |
| 4 | L4₹6.8 L+₹86,001 (14.4%)Rejected-Finance 141 1 ARYAPALLY NORTH BARANILPUR PURBA BARDHAMAN | BARANILPUR | PURBA BARDHAMAN | WEST BENGAL | L4 | Rejected-Finance Quoting Higher Rate | |
| 5 | L5₹6.9 L+₹91,001 (15.2%)Rejected-Finance | L5 | Rejected-Finance Quoting Higher Rate |
Tender Value
Refer Docs
EMD Value
₹15,000
Closing Date
19 Mar 2018, 3:00 pmClosed
Superintending Engineer,Western El.Circle,PWD
Office of the Superintending Engineer, Western Electrical Circle , PWD, Purta Bhavan, 1st floor, Burdwan-713103
Electrical work for Coprehensive Store at Burdwan Medical College and Hospital , Burdwan (East)..-----SITC of 50 KVA Diesel Generator Set.
2018_WBPWD_161740_1
WBPWD/SEWEC/BED /NIQ-84/2017-18 (3rd Call)
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Burdwan
Please refer Tender documents.
4 documents required · 4 mandatory
₹15,000
Yes
10 Jul 2020
8 Mar 2018
21 Mar 2018
8 Mar 2018
19 Mar 2018
8 Mar 2018
Amount
Supply ,delivery and Commissioning of 50 KVA/40 KW, 415 V, 50 Hz, 3ph silent Diesel Generator Set, (Make- Kirloskar /Ashok Layland/ Jakson) comprising of Engine, alternator, AMF Panel , Base frame, Fuel tank, Battery and CPCB approved Acoustic silent enclosure including all inter conection between Generator and AMF Panel etc. having following specification.
Engine a) Make- Jakson/Kirloskar/Ashok Layland b) MOEF Certified power : Minimum 84 BHP, 4 Cylinder / EQ c) Aspiration -Turbocharged – (TC) d) No of stroke -4 e) RPM -1500 f) Battery -1 x 12V, 100AH Dry or Suitable as per mfg design , each with connnecting leads and terminals . ( make : Exide) g) Type of cooling -Radiator cooled with engine water pump and coolant along with first fill of coolant. h) Air intake system -Air intake manifold with air filter system & vacuum indicator.
i) Exhaust system -Provided with turbo charger and residential exhaust silencer with manifold flexible bellow and companion flanges. j) Coupling and fly wheel -Coupling, fly wheel and flywheel housing. k) Lubricating system -Provided with oil pan, engine mounted lube oil pump and full flow lube oil filter, lube oil bypass filter along with first fill of lube oil. l) Fuel system -Comprising of fuel pump with Electronic / Mechanical Governor, fuel injector, 12 V solenoid coil and replaceable fuel filter. m) Starting system -12 V D.C electric starter and 12 V Battery charging alternator. n) Safety control -Comprising of protection against – low lube oil pressure trip, High water temperature trip High/Low DC voltage trip, weak battery trip and over speed trip
o) Power Start Control -Provided with Micro processor based generator set monitoring and control system with the followings i) Start / stop key switch -ii) Lube oil pressure indication -iii) Water temperature indication -iv) RPM indication -v) Engine running indication -vi) Low lube oil trip indication -vii) High water temperature trip indication -viii) Over speed indication -ix) Battery charging indication, weak battery indication -x) High / Low DC voltage xi) LED lamp indication for genset running remote start , shut down , warning, manual, auto & stop. xii) Data log includes engine run time & controller on time . Xiii) Engine data display arrangement - Starting Battery voltage , Engine running hour , engine temperature & Engine oil pressure.
2.Alternator -Make Stamford / Leroy Somer/Kirloskar Rating -50 KVA at .8 P.f (lag) – 3 phase – 4 wire system. Voltage regulator -±1.0% (max.) in static condition. Type of alternator -Brushless, self excited and self regulated through AVR. Protection -IP- 23 protection with class H insulation having protection for under voltage, over voltage, over current, under/over frequency, loss of Sensing, field overload.Overload -Permissible over load of 10% for one hour in 12 hours of operation.
Control/ Logic Panel : In built with the generator consisting of 100A TP MCCB, 25KA with O/L, S/C protection, DG Auto start / stop, Alt. Mtg. protection and engine protection, Power cable (Flexible “Cu”) 2 x 35 sq. mm/ P (6 x 2.3 mtr.), Power cable (Flexible “Cu”) 1 x 35 sq. mm/N (1 x 2.3 mtr.), Crimping type copper lugs (Ring type) 35 sq. mm., Cable gland, 50 mm.
4.. Base frame -Common iron channel fabricated base frame containing the engine and alternator mounted through AVM Pads. 5.. Fuel Tank -Capacity 150 Lts. Made of 14 SWG sheet metal built inside base fame complete with drain valve, air vent, inlet and out let connection, fuel gauge. 6.. Acoustic enclosure -High quality Sound proof, weather proof environmental friendly acoustic encloser fabricated from 14/16 SWG sheet Steel & powder coated specially design to meet up CPCB - II standards to maintain the noise level 75 dB (A) at distance of 1 meter from acquistic encloser under free field condition with hinged gasketted doors with suitable locking arrangement.
NOTE: 1) Efficiency not less than 90 % 2) Warrenty : Engine and Alternator for 2 years or 5000 hours whichever is earlier from the date of commissioning .Other Item for 1 year from the date of commissioning .
Sohum Industrial Sales Corporation
BURDWAN REFRIGARATION SERVICE
M/S. DAS ELECTRIC CO.
M/S SAHARA ENGINEERING
S. N. ENTERPRISE
Shakti Industries
Mayank International Pvt Ltd
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .