Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹1.3 CrAccepted-AOC | ₹1.3 Cr | 1 | Accepted-AOC Being lowest |
| 2 | 2₹1.3 Cr+₹3.5 L (2.71%)Rejected-Finance | ₹1.3 Cr+₹3.5 L (2.71%) | 2 | Rejected-Finance Not being lowest |
| 3 | 3₹1.4 Cr+₹16.4 L (12.8%)Rejected-Finance | ₹1.4 Cr+₹16.4 L (12.8%) | 3 | Rejected-Finance Not being lowest |
| 4 | Rejected-Technical | - | - | Rejected-Technical Due to BOQ not uploaded |
| Sl No | Description | Qty | Unit | M/S S P CONSTRUCTION L3 | M/S Hind Constructions L2 | B.K.ASSOCIATES L1 |
|---|---|---|---|---|---|---|
| 1.00 | Design ,fabricate ,supply ,errect,construct and execute provision of simulator room as per architectural drawing and incorporting LGSF ( Light Gauge Steel Frame) Strucure technology based on drawing & design to be submitted by the contractor duly vetted by IITs/NIT & approved by the department including all fittings & fixtures complete all as specified and directed.
NOTE:- (a) Design parameters of LGSF stucture shell be as per PS and schedual 'A' Notes.
(b) Following items mentioned under srl no. 1.01 to 1.03 here in after shall also be included in lump sum rate quoted | 1 | Each Job | 1,28,80,000 ₹1,28,80,000 | 1,18,00,000 ₹1,18,00,000 | 1,10,62,582 ₹1,10,62,582 Lowest |
| 1.01M&L for Foundation and Sub Structure :- (i) Foundation with RCC grade M-25 (Design Mix) meeting the parameters of relevant IS Codes viz 1904, 2911,456 etc as applicable, reinforcement for RCC shall be as per IS-1786. (ii) Sub structure with RCC grade M-25 (Design Mix) as per IS 456. Reinforcement for RCC shall be as per IS -1786. (iii) Aggregate for RCC of foundation and substructure shall be as per Zonal specification of HQ CE Lucknow Zone. (iv) Foundation and substructure shall be conforming to recommendation of IS1893. (v) Plinth height shall be 600 mm (average) from NGL (Natural Ground Level). All necessary civil works for setting up the superstructure including layout, excavation,backfilling in building upto plinth beam,ATT in all stage ,RCC foundation ,plinth beam complete all as specified and directed Internal Wall Cladding -12.5mm (minimum) thick gypsum board over 8mm (minimum thickness) Fibre Cement Board type B. The hollow wall space between the cement boards will be provided with rock wool insulation complete all as specified and directed External Wall Cladding will consist one layers of 8 mm (minimum thickness) Fibre Cement Board type A for external use. Providing and fixing EIFS finishing system on external face of building consisting of Expanded Polystyrene (EPS) 25mm thick fixed to FCB both mechanically and with adhesive.Base Coat with modified polymer based synthetic cement compound reinforced with synthetic fibre mesh. Top Coat stuccos applied in two coats, the scratch and brown coats applied with Acrylic weather coat finishes to provide protection and beautify the finished wall system. Wall Insulation : The framed structure will be filled with 50mm (minimum) thick rock wool slabs of density 48kg/m3 plinth protection 75 mm thick PCC 1:3:6 Type C-1 in plinth protection surface finished even and smooth without using extra cement of width as direction and shall be laid slope of 1:30 in alternative bays not exceeding 3 meter in length joint of 6 mm wide and 10 mm deep shall be provided and same shall be filled with bitumen mastic(1:3) including saucer drain complete. | ||||||
| 1.02Flat Roof :- Providing and fixing GI decking sheet minimum 0.8 mm thick in trapezoidal profile having profile depth of 44mm with reinforced cement concrete of grade M-25 design mix. The total thickness of the slab shall be 100mm. Chemical waterproofing solutions shall be provided in flat roof as applicable for LGSF structure or as specified in tender complete all as specified and directed. Sufficient arrangements for water drainage using gutters, downpipes etc to be provided. False ceiling Providing and fixing false ceiling at all heights 12 mm thick GRG (Glass Fibre with reinforced Gypsum) false ceiling tiles of perforated size 595 x 595 mm of approved texture with self-drilling/tapping screws/fasteners of approved make including jointing and fixing to a flush finish of tapered and square edges of the board with recommended filler, jointing tapes and finisher as per manufacturer specification and including the cost of making openings for light fittings, grills, diffusers, cut-outs made with frame of perimeter channels suitably fixed all complete as per drawing and specification and direction of the Engineer in Charge including painting complete all as specified and directed. S& F for DOORS, WINDOWS & VENTILATORS:- The doors will be uPVC door alongwith fly proof door for mosquito proofing. Supply and fixing factory made UPVC white colour Three track three panels sliding window with fly proof S.S wire mesh (Two nos. glazed & one no. wire mesh panels). Mild steel (MS) frame with MS grill shall be provided for security purpose. The ventilators will be of powder coated aluminium glazed ventilators top hung type with fixed net for mosquito proofing. Mild steel (MS) frame with MS grill shall be provided for security purpose. | ||||||
| 1.03Internal Elecrification -Following items mentioned under srl no. i to xx here in after shall also be included in lump sum rate quoted (i) Point wiring for light and fan point with two run of 1.5 Sqmm copper conductor unsheathed wire (colour of wire red and black) and one run of earth wire 1.5 sqmm (green in colour) - Each -64 Nos (ii) Point wiring for socket point 6/16 Amp with two run of 2.5 sqmm copper conductor unsheathed wire (colour of wire red and black) and one run of earth wire 2.5 sqmm (green in colour)- Each-20 Nos (iii) Recessed mounted bottom opening LED lights (2'x2') 40/45 watt CRCA power coated housing SS frame available on request IP-54 LED ceiling lights-32 Nos (iv) 20W Trimline a PC batten LED tube light compact apperance, simple and versatile in nature makes it as long lasting, efficacy 100 lumen/watt - 04 Nos. (v) 1200 mm sweep BLDC ceiling fan BEE five star rated energy efficent - 28 Nos (vi) 06 Amps switch socket with modular metal flush box cover plater frame 03 module -10 Nos (vii) 16 Amps switch socket with modular metal flush box complete- 10 Nos (viii) 12 Module cover plate frame with modular metal flush box complete - 12 Nos (ix) 06 Amp modular switch complete-68 Nos (x) VTPN DB with 100 amps incommer MCCB 4 pole AC 50 Hz, 415 volts complete-01 No (xi) MCB DB Double door SPN 12 way 240 volts AC 50 Hz complete-02 No (xii) MCB SPN 63 Amps - 02 Nos (xiii) MCB SP 63 Amps-02 Nos (xiv) MCB SP 6 to 32 Amps-30 Nos (xv) Metal Clad DB 02 way with MCB SPN incommer 25 Amps - 08 Nos (for Air Coditioner - 08 Nos) (xvi) Sub main wiring for AC with two runs of unsheathed copper conductor wire of size 04 Sqmm with colour for phase red and neutral black and one run of earth continuity conductor 4 Sqmm colour green for 08 Nos @ 15 RM for each = 15 x 8 = 120 RM (xvii) Building Security light - 04 Nos (xviii) Modular type fan regulator 02 module - 28 Nos (xix) Earthing with 4 mm wire as per plate No.3 SSR Part-I 2009. (xx) Ceiling rose three terminal - 64 Nos Note :- All items are mentioned in BOQ and are the part of lump sump and catered in lump sump bldg work as per drawings and must be suitable make as mentioned in contract agreement. | ||||||
| 2.00 | Surface excavation in any type of soil n.exc. 30 cm deep and avg 15 cm thick etc complete all as specified and directed. | 150 | Sqm | 30 ₹4,500 Lowest | 50 ₹7,500 | 50 ₹7,500 |
| 3.00 | M & L 75 mm thick PCC 1:4:8 type D-2 as in lean concrete etc complete all as specifiedand directed | 150 | Sqm | 300 ₹45,000 Lowest | 300 ₹45,000 Lowest | 500 ₹75,000 |
| 4.00 | Providing and laying Chequered cement concrete tiles 30cm x 30cm x 25mm thick, set,jointed and pointed in neat cement slurry in floors with approved colour, design & pattern as in footparth, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over and including 50mm thick compacted bed of fine sand, compacting and proper embedding/ laying of inter locking paver blocks into the sand bedding layer through
vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand; complete. etc complete all as specified and directed | 150 | Sqm | 800 ₹1,20,000 Lowest | 800 ₹1,20,000 Lowest | 1,000 ₹1,50,000 |
| 5.00 | M & L PCC 1:2:4 type B-1 (using 20mm graded stone aggt) as in kerb stone/Coping or as in bonding etc complete all as specified and directed | 4.29 | Cum | 7,500 ₹32,175 | 5,000 ₹21,450 Lowest | 8,000 ₹34,320 |
| 6.00 | Excavation in trenches n.exc. 1.5 m wide and n.exc. 1.5 m depth and getting out soft / loose soil complete all as specified and directed for laying of under ground cable, foundation of pole and stay etc complete all as specified and directed. | 66.16 | Cum | 150 ₹9,924 Lowest | 200 ₹13,232 | 250 ₹16,540 |
| 7.00 | Returning filling in including spreading, leveling, watering and well rammining in alyers of not exc. 25 cm complete all as specified and directed. | 23 | Cum | 60 ₹1,380 | 50 ₹1,150 Lowest | 100 ₹2,300 |
Tender Value
₹1.4 Cr
EMD Value
₹2.2 L
Closing Date
4 Oct 2025, 6:00 pmClosed
HQ CWE Agra
112, Taj Road, Agra Cantt
PROVISION OF SIMULATOR ROOM FOR AGNIVEERS TRAING AT THE SIKH LI REGT CENTRE AT FATEHGARH
2025_MES_728550_1
86237/E8
Open Tender
Civil Works
Item Rate
270 days
Fatehgarh
MES contractors enlisted for Class B and above and category a(i) for unenlisted contractors meeting the enlistment criteria corresponding to value class and category of work
8 documents required · 8 mandatory
₹1,000
Yes
₹2.2 L
4 Dec 2025
30 Aug 2025
11 Oct 2025
30 Aug 2025
4 Oct 2025
20 Sept 2025
30 Aug 2025 - 6 Sept 2025
Amount
Design ,fabricate ,supply ,errect,construct and execute provision of simulator room as per architectural drawing and incorporting LGSF ( Light Gauge Steel Frame) Strucure technology based on drawing & design to be submitted by the contractor duly vetted by IITs/NIT & approved by the department including all fittings & fixtures complete all as specified and directed. NOTE:- (a) Design parameters of LGSF stucture shell be as per PS and schedual 'A' Notes. (b) Following items mentioned under srl no. 1.01 to 1.03 here in after shall also be included in lump sum rate quoted
M&L for Foundation and Sub Structure :- (i) Foundation with RCC grade M-25 (Design Mix) meeting the parameters of relevant IS Codes viz 1904, 2911,456 etc as applicable, reinforcement for RCC shall be as per IS-1786. (ii) Sub structure with RCC grade M-25 (Design Mix) as per IS 456. Reinforcement for RCC shall be as per IS -1786. (iii) Aggregate for RCC of foundation and substructure shall be as per Zonal specification of HQ CE Lucknow Zone. (iv) Foundation and substructure shall be conforming to recommendation of IS1893. (v) Plinth height shall be 600 mm (average) from NGL (Natural Ground Level). All necessary civil works for setting up the superstructure including layout, excavation,backfilling in building upto plinth beam,ATT in all stage ,RCC foundation ,plinth beam complete all as specified and directed Internal Wall Cladding -12.5mm (minimum) thick gypsum board over 8mm (minimum thickness) Fibre Cement Board type B. The hollow wall space between the cement boards will be provided with rock wool insulation complete all as specified and directed External Wall Cladding will consist one layers of 8 mm (minimum thickness) Fibre Cement Board type A for external use. Providing and fixing EIFS finishing system on external face of building consisting of Expanded Polystyrene (EPS) 25mm thick fixed to FCB both mechanically and with adhesive.Base Coat with modified polymer based synthetic cement compound reinforced with synthetic fibre mesh. Top Coat stuccos applied in two coats, the scratch and brown coats applied with Acrylic weather coat finishes to provide protection and beautify the finished wall system. Wall Insulation : The framed structure will be filled with 50mm (minimum) thick rock wool slabs of density 48kg/m3 plinth protection 75 mm thick PCC 1:3:6 Type C-1 in plinth protection surface finished even and smooth without using extra cement of width as direction and shall be laid slope of 1:30 in alternative bays not exceeding 3 meter in length joint of 6 mm wide and 10 mm deep shall be provided and same shall be filled with bitumen mastic(1:3) including saucer drain complete.
Flat Roof :- Providing and fixing GI decking sheet minimum 0.8 mm thick in trapezoidal profile having profile depth of 44mm with reinforced cement concrete of grade M-25 design mix. The total thickness of the slab shall be 100mm. Chemical waterproofing solutions shall be provided in flat roof as applicable for LGSF structure or as specified in tender complete all as specified and directed. Sufficient arrangements for water drainage using gutters, downpipes etc to be provided. False ceiling Providing and fixing false ceiling at all heights 12 mm thick GRG (Glass Fibre with reinforced Gypsum) false ceiling tiles of perforated size 595 x 595 mm of approved texture with self-drilling/tapping screws/fasteners of approved make including jointing and fixing to a flush finish of tapered and square edges of the board with recommended filler, jointing tapes and finisher as per manufacturer specification and including the cost of making openings for light fittings, grills, diffusers, cut-outs made with frame of perimeter channels suitably fixed all complete as per drawing and specification and direction of the Engineer in Charge including painting complete all as specified and directed. S& F for DOORS, WINDOWS & VENTILATORS:- The doors will be uPVC door alongwith fly proof door for mosquito proofing. Supply and fixing factory made UPVC white colour Three track three panels sliding window with fly proof S.S wire mesh (Two nos. glazed & one no. wire mesh panels). Mild steel (MS) frame with MS grill shall be provided for security purpose. The ventilators will be of powder coated aluminium glazed ventilators top hung type with fixed net for mosquito proofing. Mild steel (MS) frame with MS grill shall be provided for security purpose.
Internal Elecrification -Following items mentioned under srl no. i to xx here in after shall also be included in lump sum rate quoted (i) Point wiring for light and fan point with two run of 1.5 Sqmm copper conductor unsheathed wire (colour of wire red and black) and one run of earth wire 1.5 sqmm (green in colour) - Each -64 Nos (ii) Point wiring for socket point 6/16 Amp with two run of 2.5 sqmm copper conductor unsheathed wire (colour of wire red and black) and one run of earth wire 2.5 sqmm (green in colour)- Each-20 Nos (iii) Recessed mounted bottom opening LED lights (2'x2') 40/45 watt CRCA power coated housing SS frame available on request IP-54 LED ceiling lights-32 Nos (iv) 20W Trimline a PC batten LED tube light compact apperance, simple and versatile in nature makes it as long lasting, efficacy 100 lumen/watt - 04 Nos. (v) 1200 mm sweep BLDC ceiling fan BEE five star rated energy efficent - 28 Nos (vi) 06 Amps switch socket with modular metal flush box cover plater frame 03 module -10 Nos (vii) 16 Amps switch socket with modular metal flush box complete- 10 Nos (viii) 12 Module cover plate frame with modular metal flush box complete - 12 Nos (ix) 06 Amp modular switch complete-68 Nos (x) VTPN DB with 100 amps incommer MCCB 4 pole AC 50 Hz, 415 volts complete-01 No (xi) MCB DB Double door SPN 12 way 240 volts AC 50 Hz complete-02 No (xii) MCB SPN 63 Amps - 02 Nos (xiii) MCB SP 63 Amps-02 Nos (xiv) MCB SP 6 to 32 Amps-30 Nos (xv) Metal Clad DB 02 way with MCB SPN incommer 25 Amps - 08 Nos (for Air Coditioner - 08 Nos) (xvi) Sub main wiring for AC with two runs of unsheathed copper conductor wire of size 04 Sqmm with colour for phase red and neutral black and one run of earth continuity conductor 4 Sqmm colour green for 08 Nos @ 15 RM for each = 15 x 8 = 120 RM (xvii) Building Security light - 04 Nos (xviii) Modular type fan regulator 02 module - 28 Nos (xix) Earthing with 4 mm wire as per plate No.3 SSR Part-I 2009. (xx) Ceiling rose three terminal - 64 Nos Note :- All items are mentioned in BOQ and are the part of lump sump and catered in lump sump bldg work as per drawings and must be suitable make as mentioned in contract agreement.
Surface excavation in any type of soil n.exc. 30 cm deep and avg 15 cm thick etc complete all as specified and directed.
M & L 75 mm thick PCC 1:4:8 type D-2 as in lean concrete etc complete all as specifiedand directed
Providing and laying Chequered cement concrete tiles 30cm x 30cm x 25mm thick, set,jointed and pointed in neat cement slurry in floors with approved colour, design & pattern as in footparth, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over and including 50mm thick compacted bed of fine sand, compacting and proper embedding/ laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand; complete. etc complete all as specified and directed
M & L PCC 1:2:4 type B-1 (using 20mm graded stone aggt) as in kerb stone/Coping or as in bonding etc complete all as specified and directed
Excavation in trenches n.exc. 1.5 m wide and n.exc. 1.5 m depth and getting out soft / loose soil complete all as specified and directed for laying of under ground cable, foundation of pole and stay etc complete all as specified and directed.
Returning filling in including spreading, leveling, watering and well rammining in alyers of not exc. 25 cm complete all as specified and directed.
Removing excavated material n. exc. 50 m and depositing where directed at a level n. exc. 1.5 m above the starting point complete all as specified and directed.
M&L for sand cushioning to U/G cable in layers of 25 cm thick ( 10 cm before laying the cable and 15 cm after laying the cable) and 18 cm for punned thickness (8 cm before laying the cable and 10 cm thick after laying the cable) in trenches complete all as specified and directed. Note :- Only puned down volumne shall be measured.
Supply and lay burnt best quality locally available old size sub bass 'B' brick laid in trenches perpendicular to U/G cable for cable protection complete all as specified andirected.
M&L for 80 mm bore GI tubing light grade with all fittings laid across road in trenches or across PCC drain, along electric pole or floor / wall for cable protection with suitable size of MS clamps and nut and bolts / washer complete all as specified and directed.
Supply and laying galvanized iron pipe light grade on road drain, culvert, roof and wall of dia 50 mm for protection of cable complete all as specified and directed.
M&L for brick work with sub class 'B' bricks old size straight or curved on plan exc. 6 m mean radius built in cement mortar (1:6) complete all as specified and directed.
M&L for 15 mm thick rendering on fair faces of brick work or concrete surfaces in cement mortar (1:4) and finishing the surfaces even and smooth with using extra cement complete all as specified and directed.
S&F mild TMT steel bars 6 to 8 mm dia cut to length, bent to shape required including cranking, bending and binding with the mild steel wire (annealed) not less than 0.9 mm dia complete all as specified and directed.
M&L for precast RCC 1:2:4 type B-1 (20 mm graded stone aggregate) as in cover slab for drain and similar work complete all as specified and directed.
M&L for PCC (1:3:6) type C-2 (using 40 mm graded stone aggregate) as in surface channel of drain including providing necessary form work complete all as specified and directed.
M&L for extra for forming fair finishes drain or channel 30 cm inner girth in cement concrete using extra cement including forms, moulds, mitred / stopped ends etc complete all as specified and directed.
Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 120 sqmm 3.5 core complete all as specified and directed.
Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 50 sqmm 3.5 core complete all as specified and directed.
Supply and fix servo voltage stablizer for automatic operation, three phase naturally oil cooled indor type & designed for input variation between 340 V to 460 V with output voltage stablized at 415 with accuracy + 2.5% and speed of correction 8 volts per second and of capacity 75 KVA complete all as specified and directed.
M&L for earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried in ground vertically to a depth not less than 2.25 mtr below normal ground level connected to galvanzied steel strip 32 x 6 mm earth lead by means of bolts, nuts and washers made of galvanized iron or steel earth strip protected by 40 mm bore light grade GI pipe and connected for body earthing of feeder pillar box all as specified and directed including PCC work as per sketch No.3 of SSR part-I (2009) pit cover slab of size 300 x 300 x 50 mm with handle as shown in drawing funnel, wire mesh 20 mm dia GI pipe medium grade for watering charcoal and slat in alternate layers including necessary earth pole and excavation in hard / dense soil and removal etc including testing complete
Supply, installing, commission and testing hi wall split units indoor / outdoor Air conditioner cooling type both complete with cordless remote control unit and within built air purifier humidifier air filter and dust filter for bettter indoor air quality with minimum BEE approved minimum 5 star rating invertor type all and EER 3.2, Electric driven single phase 220 volts AC 50 Hz, R-410A refrigerant of capacity 2.0 Ton, inverter type, noise level should be less than 45 DB including copper piping of adequate size and required length as directed duly insulated with suitable insulating material e.g. glass wool, plywood, moulded thermo coal etc including antibacterial coating complete with steel bracket for condensing unit and copper cable of suitable size for making electric connections, including necessary fixing arranagement (indoor unit at suitable place and height inside the room and outdoor unit at site place outside the room) complete all as specified and directed. Note :- (a) Suitable piping shall be provided of adequate length of size 5/8' for draining icondensate water from indoor unit, Cost of same shall deemed to be included in quoted rate. (b) Cost of metallic bracket and nut bolt for fixing indoor and outdoor unit including necessary cutting grouting in walls by cutter and making good the surface in CM 1:3 and to the original finishes (white wash / colour wash / distemper) shall deemed to be included in quoted rate. (c) Contractor shall submit original purchase voucher and warranty card. Minimium warranty should be 1 year for complete product. 10 Year for compressor, 5 year for condensor and PCB card after installation and commissioning of complete unit.
Supply & installing of voltage stabilizer for automatic operation having input & output voltage, Amps, over & low voltage cutout and timer delay function etc digital display single phase naturally air cooled indoor type & designed for input variation between 130 V to 250 V with output voltage stabilized at 230 volt (+- 5%) and capacity 5 KVA with wall mounted bracket complete all as specified and directed. Note :- Contractor shall submit original purchase voucher and warranty card. Make :- V-Guard / Blue Bird/ Sinetrac
Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole 20 Amp MCB 240 volts 50 Hz complete all as specified and directed.
M/S Hind Constructions (BID ID -3437180)
M/S S P CONSTRUCTION (BID ID -3442158)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .