GM P
YAMUNA EXPRESSWAY INDUSTRIAL DEVELOPMENT AUTHORITY
Construction of 11/0.415 Kv Substation in Sector-20 Pocket-F YEIDA (WC-EandM-02)
2026_YEIDA_1160708_17
YEA/GM(PROJECT)/2026/523 DT-12/06/2026
Open Tender
Electrical Works
180 days
YAMUNA EXPRESSWAY INDUSTRIAL DEVELOPMENT AUTHORITY
REFER TENDER DOC
5 documents required · 5 mandatory
₹6,770
₹14.8 L
13 Jul 2026
19 Jun 2026
14 Jul 2026
19 Jun 2026
13 Jul 2026
19 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Bill of Quantity-A (For 5 Nos Electrical Substation) | |||||
| 1.01 | Supply, Installations, Testing & Commissioning of 11kV HT PANELS Indoor type 4 panel board, 2 I/C and 2 O/G (1 T/F + 1 spare) 630 Amps, 11 KV, 3 phase, 25 KA for 1 sec. Vacuum circuit breaker including two bus PT with all necessary protection, metering and other accessories complete in all respect.as per the directions of the Engineer-in-charge Complete in all respects as per direction of the Engineer-in-charge. YEIDA SOR-67 | 5 | Nos. | 0.74 | ₹3.71 |
| 2 | Supply, delivery, assembly, installation, testing and commissioning of Outdoor type distribution transformer. 11/0.433 KV, 3 Phase, Double wound winding. Voltage ratio 11000/433-250 Volts, vector group Dyn 11. Air cooled with manually operated +5% and -10% off load Tap changer and complete with standard fitting & accessories as given in the specification and also confirming to IS: 1180 (Level-2) with first filling of the oil complete as required. (This includes oil testing for dielectric strength, flask over test and filtration of transformer oil to be conducted in the event of unsatisfactory results of oil testing. (Crompton, NGEF, Alstom, BHEL, Voltamp, Diamond, Reychem, Kanohar make) complete in all respect.as per the directions of the Engineer-in-charge. YEIDA SOR-74 (a) 630 KVA. Copper wound. | 5 | Nos. | 0.74 | ₹3.71 |
| 3 | Supply & Fixing of Main LT & APFC Consisting One Incoming 1000A,4P ACB EDO Type and 6 Nos Outgoing (5 No 400A TPN MCCB and 1 Nos 63A TPN MCCB ) with digital metering & Indicating lamps and Capacitor bank 250KVAR for APFC Panel Board & along with other accessories as required. complete in all respect.as per the directions of the Engineer-in-charge. YEIDA SOR-68 | 20 | Nos. | 0.16 | ₹3.23 |
| 4Supply, Assembling, Installation, Commissioning of Sealed maintenance free (SMF) 110V D.C., 150 AH batteries. The batteries shall rest on treated wooden planks fabricated from MS angle and free standing floor mounted rack with acid resistant finish and complete with series connecting electrical leads and charging of batteries. The batteries shall be accompanied with tester. This shall have incoming leads as well as outgoing leads and of suitable battery charger for 8 hrs. charge of 150AH battery charger enclosed in sheet metal with fan on top and it should automatically charge the batteries With booster and trickle charge. | |||||
| 4.01 | Charger shall be complete with incoming & outgoing leads and D.C. Distribution board will have one set of 63 amps MCB as incomer and ten number of suitable rated MCB (as per coil rating of VCB) on outgoing side enclosed in metal sheet enclosure of 2mm thick and suitably painted. The unit will be complete with bus bars, accessories, links, terminal strip, clamps etc. along with cables up to incoming & outgoing to VCB panels. Complete in all respect.as per the directions of the Engineer-in-charge. Complete in all respect.as per the directions of the Engineer-in-charge. YEIDA SOR-69 | 5 | No. | 0.29 | ₹1.45 |
| 5Supply, delivery, laying testing & commissioning of 11KV (E), XLPE cable having compacted circular staranded aluminium conductor, conductor screening of extruded semi conducting compound, cross linked polythylane (XLPE), insulation screening of the extruded semi conducting compound followed by copper tape, cores laid up, taped PVC inner sheath, single layer of steel strip armouring, overall PVC outer sheath conforming to IS: 7098 (Part-amendments) for following mentioned sizes. It should be operational at 11 KV, 50 Hz. AC system in ground at a depth of 1200 mm below ground level over a cushion of 75 mm thick sand alround and protected with bricks on sides and top on surface the cable run shall be fixed on M.S. clamps etc of suitable size or as directed by the E/I. Complete in all respect. | |||||
| 5.01 | The price are inclusive of all earth work such as digging, back filling, supply & spreading of good earth all around the cable, supply & providing cable identification markers. The installation should be complete in all respects and as per requirement of the job. (CCI , Fort Gloster , Asian, Universal , Nicco , ICL , Diamond, Havells, KEI make | - | - | - | - |
| 5.02 | 11kV, 3C X 120 sq. mm. (Cable form 11/0.415kV Sub-stations to 630kVA, 11/0.415kV Transformers) PWD-2018 PS No-506 | 150 | Mtrs. | - | - |
| 6Supply, Installation, Testing & Commissioning of 11KV, indoor type cable termination kit of 3 core cable with cable termination at the panel & transformer complete in all respect as required for proper completion of work as per direction of Engineer-in-charge.(Make- Raychem/ C.C.I./ Frontec) | |||||
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.81 MB
17.pdf
Tender Documents • 1.64 MB
BOQ_2178028.xls
BOQ • 0.41 MB
422.pdf
PDF • 0.08 MB
539.pdf
PDF • 0.45 MB
Download all tender documents and submit your bid