Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | I₹15.4 LAccepted-AOC NO 43 MARUTHI TOWER 4TH CROSS SAMPIGE ROAD MALLESHWARAM BANGALORE URBAN BANGALORE KARNATAKA 560003 | BENGALURU URBAN | KARNATAKA | 560003 | I | Accepted-AOC PO Placed on 12-01-2023 Awarded value is inclusive of tax. | |
| 2 | Rejected-Technical | - | Rejected-Technical Technical Bid Rejected |
Tender Value
Refer Docs
Closing Date
10 Oct 2022, 10:00 amClosed
THE DIRECTOR
CSIR-NAL, HAL AIRPORT ROAD, KODIHALLI, BENGALURU-560017
Replacement of existing 66KV CTs, 66KV PTs and 0.2S class Energy meters at 2X10MVA,66/11KV SUB-STATION, CSIR-NAL, N.W.T.C, Belur campus
2022_CSIR_129027_1
NAL/PUR/ELB/155/22-Z
Open Tender
Miscellaneous Goods
Supply
160 days
ELB, CSIR-NAL, NWTC, BELUR, BENGALURU
AS PER TENDER DOCUMENT
11 documents required · 11 mandatory
₹0
Exempted
17 Jan 2023
15 Sept 2022
11 Oct 2022
15 Sept 2022
10 Oct 2022
15 Sept 2022
Amount
66KV Voltage Transformer Supply of outdoor, Oil cooled, Single phase, Single pole, Dead tank, OIP insulated voltage transformer as per IS:3156/1992 with following specification along with suitable connecting clamps as per KPTCL latest specifications. Ratio: (66KV /√3) / (110V/√3) - (110V/√3) BIL : 72.5/140 /325kVp Sec.1 : 10VA Class : 0.2 Sec.2 : 10VA Class : 0.2 VF : 1.2 for Cont. & 1.5 for 30secs Creepage Distance : 25 mm/KV Frequency : 50Hz Make : Pragathi / Lamco / Mehru / Vidyut (Any KPTCL approved make as per KPTCL approved Vendor/Bidder list OM no: CEE / T&P /SEE-2 /KCO-147 /43596 /2022-23 /3736-50 dt:09.06.2022.)
66KV Voltage Transformer Installation, Testing and Commissioning of item no:01 above using crane as per standard.
66KV Current Transformer Supply of outdoor, Oil cooled, Single phase, wound primary type, Live tank, two core current transformer as per IS:2705/1992 with following specification along with suitable connecting clamps as per KPTCL latest specifications. Ratio: 75 / 1-1A Core1: 5VA, Class: 0.2S, ISF: <=5 Core2: 5VA, Class: 0.2S, ISF: <=5 STC (Short-Time Current): 31.5kA for 1sec. Creepage Distance : 25 mm/KV Frequency : 50Hz Make : Pragathi / Lamco / Mehru / Vidyut (Any KPTCL approved make as per KPTCL approved Vendor/Bidder list OM no: CEE / T&P /SEE-2 /KCO-147 /43596 /2022-23 /3736-50 dt:09.06.2022.)
66KV Current Transformer Installation, Testing and Commisssioning of item no:03 above using crane as per standard.
Charges towards dismantling of existing 3Nos of 66KV CTs and 3Nos of 66KV PTs using crane.
Energy Meters Supply ,Installation, Testing and Commisssioning of 2Nos of TVM Meters(Main & Check)-AC,3phase, 4wire,CT & PT operated electronic Trivector meter accuracy 0.2s Class with ABT & TOD features and DLMS complaint which suitable for EHT Metering installation as per latest BESCOM/KPTCL specification. Make : L&T.
Removing of existing cables from CTs , PTs & meters.
Site modification of existing CT & PT structures suitable to install new CTs & PTs as per requirement arises at site for item no:1&3 using necessary hardware complete as per standard.
Supply and laying of 4C X 6 sq.mm multi-strand copper conductor with PVC insulated un-armoured cable of voltage gradient 1.1Kv including end terminations. Make: Polycab / Finolex / Havells
Supply and laying of 4C X 4 sq.mm multi-strand copper conductor with PVC insulated un-armoured cable of voltage gradient 1.1Kv including end terminations. Make: Polycab / Finolex / Havells
Supply and laying of 50mm, B-class GI pipe on surface / in ground including excavation including concrete if any and back filling to match the surrounding as required.
Professional charges towards submission of drawings to KPTCL / BESCOM and obtaining approval, co -ordination with TAQC, KPTCL for factory inspection of equipment and obtaining DI from KPTCL / BESCOM and co-ordination with TL & SS , KPTCL for obtaining LC required for the replacement of equipments including co-ordination with BESCOM, MT division for decommissioning of existing metering panel, 66KV CTs & PTs and commissioning of new CTs, PTs & TVMs.
Sub-Total:Ex-Works Price
Less: Discount (if any)
Sub-Total:
Add: Packing & Forwarding charges (if any)
Add: Transportation Charges (if any)
Add: Insurance charges (from warehouse-to-warehouse) (if any)
Total (A):
Installation & Commissioning charges (if any)
Training charges (if any)
Total (B):
Bank Charges, if any
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .