Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.7 LAccepted-Finance CHANDURIA SIMURALI DIST NADIA PIN 741248 | NADIA | WEST BENGAL | 741248 | ₹17.7 L | L1 | Accepted-Finance Lowest Bid |
| 2 | L2₹18.0 LRejected-Finance NABAJIBAN 1 NABAJIBAN COLONY BISHARPARA KOLKATA 700158 WEST BENGAL | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700158 | ₹18.0 L | L2 | Rejected-Finance Higher Bid |
| 3 | L3₹18.1 LRejected-Finance 10B DR LAHIT BANERJEE SARANI GROUND FLOOR KOLKATA 700 073 | KOLKATA | KOLKATA | WEST BENGAL | 700073 | ₹18.1 L | L3 | Rejected-Finance Higher Bid |
| Sl No | Description | Qty | Unit | ANIKET COOLING AND REFRIGERATION CO L2 | ROY REFRIGERATION L1 | CARRION AIR COOLING L3 |
|---|---|---|---|---|---|---|
| 1.00 | PART-A (S.I.T.C of AC Machine):
Sub Head 1 : SITC of Ductable Air Conditioner Unit:
Supply of Microprocessor based air cooled ceiling suspended 11 TR capacity Ductable type Split Air Conditioner of rated cooling capacity of 132000 BTU/hr with 1 Nos. ODU Scroll compressor of 3 phase 415V input, (R-32/R-410A/R-407C) Refrigerant,1 nos. IDU of 4400 CFM Air -flow / IDU & wireless remote. (Make-Mitsubishi Electric/ Daikin/ OGeneral/ Carrier/ LG/ Panasonic/Johnson Controls (Hitachi) / Toshiba/ Sharp/ Mitsubishi Heavy/Voltas) [indoor unit (IDU) serves as the fan coil unit (FCU)] | 2 | Nos. | 3,22,000 ₹6.4 L | 3,20,000 ₹6.4 L | 3,22,000 ₹6.4 L |
| 2.00 | Erection & Commissioning Charges for 11 TR Ductable type Split Air Conditioner Indoor and outdoor unit. | 2 | Nos. | 15,000 ₹30,000 | 12,000 ₹24,000 | 15,000 ₹30,000 |
| 2.01Sub Head 2 : Refrigerant, Piping etc | ||||||
| 3.00 | Suupply and charging Refrigerant - R-32/R-410A/R-407C. | 10 | Kg | 2,200 ₹22,000 | 2,200 ₹22,000 | 2,200 ₹22,000 |
| 4.00Copper Refrigeration pipe line for liquid and suction line with fittings, elbows, bends, supports & brackets (Make-Ryoku/Totaline/Jobu) | ||||||
| 4.01 | Suction Line (1 1/8" OD with 0.7mm thick) | 30 | RM | 1,700 ₹51,000 | 1,700 ₹51,000 | 1,700 ₹51,000 |
| 4.02 | Liquid Line (5/8" OD with 0.6 mm thick) | 30 | RM | 900 ₹27,000 | 900 ₹27,000 | 900 ₹27,000 |
| 5.00Supply & Fixing Pipe Insulation in liquid & suction line with 9mm nitrile rubber tube (Accoflex) | ||||||
| 5.01 | Suction Line (1 1/8" OD with 0.7mm thick) | 30 | RM | 150 ₹4,500 | 150 ₹4,500 | 150 ₹4,500 |
| 5.02 | Liquid Line (5/8" OD with 0.6 mm thick) | 30 | RM | 50 ₹1,500 | 50 ₹1,500 | 50 ₹1,500 |
Tender Value
₹18.2 L
EMD Value
₹36,339
Closing Date
27 Feb 2026, 12:00 pmClosed
Executive Engineer Cooch Behar Electrical Division
Executive Engineer Cooch Behar Electrical Division Sunity Road, Circuit house Campus
Implementation of Standard Operating Procedure SOP in main store at District Reserve store DRS of CMOH Office Building, Alipurduar.- Electrical Installation Works.
2026_WBPWD_1002872_1
WBPWD/EE/CED/eNIT-32/2025-2026
Open Tender
ELECTRICAL WORKS ORG
45 days
Alipurduar
Please refer Tender documents.
5 documents required · 5 mandatory
₹36,339
Cooch Behar Electrical Division, Sunity Road, Circ
9 Apr 2026
10 Feb 2026
2 Mar 2026
10 Feb 2026
27 Feb 2026
17 Feb 2026
16 Feb 2026
PART-A (S.I.T.C of AC Machine): Sub Head 1 : SITC of Ductable Air Conditioner Unit: Supply of Microprocessor based air cooled ceiling suspended 11 TR capacity Ductable type Split Air Conditioner of rated cooling capacity of 132000 BTU/hr with 1 Nos. ODU Scroll compressor of 3 phase 415V input, (R-32/R-410A/R-407C) Refrigerant,1 nos. IDU of 4400 CFM Air -flow / IDU & wireless remote. (Make-Mitsubishi Electric/ Daikin/ OGeneral/ Carrier/ LG/ Panasonic/Johnson Controls (Hitachi) / Toshiba/ Sharp/ Mitsubishi Heavy/Voltas) [indoor unit (IDU) serves as the fan coil unit (FCU)]
Erection & Commissioning Charges for 11 TR Ductable type Split Air Conditioner Indoor and outdoor unit.
Sub Head 2 : Refrigerant, Piping etc
Suupply and charging Refrigerant - R-32/R-410A/R-407C.
Copper Refrigeration pipe line for liquid and suction line with fittings, elbows, bends, supports & brackets (Make-Ryoku/Totaline/Jobu)
Suction Line (1 1/8" OD with 0.7mm thick)
Liquid Line (5/8" OD with 0.6 mm thick)
Supply & Fixing Pipe Insulation in liquid & suction line with 9mm nitrile rubber tube (Accoflex)
Suction Line (1 1/8" OD with 0.7mm thick)
Liquid Line (5/8" OD with 0.6 mm thick)
Supply and fixing flexible canvass connection for concealed split air-conditioners.
Control copper Cabling from Condensing Unit to control panel (Make: polycab/finolex/KEI)
4 core 4 sq.mm communication cable
Sub-Head 3 - Duct Work
Supply, installtion, testing and commissioning of Class - VIII grade (120 GSM) supply & return air duct along with necessary supports, flanges etc. as required and as per IS 655 and IS-277 standards of following gauges.
Supplying & fixing of 19 mm thick duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class “O”) insulation on new duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete
Supplying & fixing of acoustic insulation inside ducting with 10mm thick open cell nitrile rubber (class O) of density 140Kg/cu.m-160 Kg/Cum insulation with bolts nuts GI washers etc as required.
Supply and fixing of Al powder coated continuous Grill (Make- Premier)
Supplying, fixing, testing & commissioning of powder coated extruded aluminium section supply air diffuser with M.S volume control dampers as required. (Make-Premire/Dynacraft/Air Master / Caryire)
Supply, installation, testing and commissioning of opposed type Duct dampers GI mannual type.
Supply and installation of fusible link Fire Damper .(Make- System Air/premire/Dynacraft).
Supplying, fabrication & fixing of trap door made for maintenance of IDU of Air conditioning system by frame work of aluminium hollow section of size 50mm x25mm (2.0mm thickness) combined with aluminium corners of size 38mm x 25mm, suspended by aluminium hollow tube section of size 38mm x 25mm ,25mm x 25mm powder coated wall angle with aluminium composit panel of thickness 3.0mm comprising of protective film, polyester coating, primer, aluminium coil, adhesive film, polyethylene core again with one layer adhesive film, aluminium bottom coating and finally service coating as per manufacturer's specification finished with aluminium screw and silicon sealent complete in all respect as per direction of EIC.
Supply, Installation, testing and commissioning of fresh air provision as per direction of the EIC incl. filter, damper, bird screen etc complete as required
Supplying, fabrication & fixing M.S u-channel of 6 mm thick of size (75 mm x 40 mm x 40 mm) for making platform for installation of outdoor unit of 8.5/3 TR ductable split AC incl. drilling 2 nos holes in each channel including cutting holes into the wall & grouting the same with cement concrete (1:1 ½ :3) etc. fabricated with horizontal angle of 25 mm x 25 mm x 6 mm including supporting angle 50 mm x50mm x 6 mm in each platform in outer edge for transmitting the load centrally through 2Nos. (50 mm x 50 mm x 6 mm) Angle inserted into the exiting wall. The entire structure should be baricated & safe for ODU maintenance. Area of the platform is 3Mtr. x 1.2Mtr.
S & F iron cage ( 4O"x 36"x24") structure for the split AС machine ODUs on wall for holding and provide protection with locking arrangement & shade arrangement above the grills with corrugated tin shade, necessary anti-rust painting as per direction of EIC
Supply & wiring with 3 core 2.5 Sq.mm XLPE Insulated, PVC tape innersheathed unarmoured copper cable. Make Polycab / RR /KEI/ Havells/ Gloster as approved by E.I.C] (For Indoor Unit Connection)
PART-B (Electrical Installation work)
Sub Head 1 : Isolator/MCB/Timer DB/Enclosure
Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection. [Make: Legrand/ ABB/ SIEMENS/ Schneider/ L&T]
Supplying and fixing MCB SS enclosure with IP-20/30 protection, powder coated provision for two/four pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment
S & F 415V 40A Timer controller for Three phase twin control AC machine in SS double door in suitable SS enclosure with S&F following electrical accessories & front door locking arrangement with all connection by finishing the ends of 4x4 & 1x2.5 copper wire dowells solderless socket by crimping method as to GS earthing attachment on wall incl necessary connections as per direction of EIC :-
10kA, C-Curve, 415V, 40A,FPMCB(LT/Schnider/ABB Elegance) as incomer --- 1 No. & 25A 3P MCB(LT / Schnider/ABB Elegance) as outgoing ----2 Nos
24 Hr programmable Digital/Analog Timer (LT make cat no 67DDT0) ----1 No
415V, 40A, 3 pole power contractor (LT make cat no MNX 32/230V/415V) with 1 NO +1 NC additional contact block ---- 2 sets
ON & OFF push button switch ----4 Nos
Overload (Range 9-14A) & SPP protection --------- 1 Set.
20A Auto-Off-Bipass SPDT toggle switch (Approved /reputed make) ---- 2 Nos & 6A MCB for control circuit ----- 3 Nos.
10A SPST Moduler type switch (Make :- Legrand/ Myrius) - 1 No.
70V-250V, LED Indicating Lamp (Make (Siemens) -------- 8 Nos
Outgoing connector make ELMAX (Approved/reputed make) - 1 No
S&F of 250V, 25A timer controlled single starter for controlling compound lights/ Single Air Conditioning Machines in SS double door 2+10 way DB enclosure (L&T / ABB / Legrand make) with S&F following electrical accessories & front door locking arrangement with all connections by finishing the ends of 2 x 4 & 1 x 2.5 mm2 copper wire with dowells solderless socket by crimping method as to GS, earthing attachment on wall incl. necessary connections as per direction of EIC : -
25A DP MCB (L&T / ABB / Legrand make) – 1 no.
24Hr x 7 days programmable Digital timer (L&T make Cat no 67DDTO) – 1 no.
3-pole power contactor (L&T make Cat no MNX22 / 250V) – 1 no.
2-Modular AC motor starter (Legrand / Myrius Cat no 673031) – 1 no.
1-Module 10A Modular switch (Make Legrand / Myrius) – 1 no.
3-module plate with cover (Make Legrand / Myrius) – 1 no.
25A Auto-Off-Bipass SPDT toggle switch (approved reputed make) – 1 no.
LED indication lamp (approved reputed make) – 1 no.
Outgoing bakelite connector 32A (Reputed make as approved by EIC) – 2 nos.
Sub Head 2 : Cable & Wire
Supply of 2/4 Core XLPE Insulated & Sheathed Armoured stranded Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [Make Polycab / RR /KEI/ Havells/ Gloster as approved by E.I.C] [From Timer DB to Loop Box ]
4 Core 16 Sqmm
Laying of cable upto 3/4 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below :
4 core 16 Sq. mm
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials :
4 core 16 Sq. mm
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20 mm size PVC rigid conduit 'FR' (Precision make) incl. necy.fittings as required [ From Loop Box to OD unit / 2 x 6A / 16A PP ]
2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make] on wall, ceiling with saddles and other accessories as required and mending good damages to building works
25mm size
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required
4x80/0.4 (10 sqmm) + 2x84/0.3 (6 sqmm) as ECC
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.
SUB-HEAD 3--Distribution Wiring
Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board with top cover plate and 2 no. suitable size “Ph & N” copper bar & earthing attachment fixed on wall incl. mending good damages to original finish.
Average run 10 mtr
Distribution wiring in 1.1 KV grade 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1.1 KV grade 1 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire as ECC, to 6A 3 pin Modular type plug socket & switch (Brand approved by EIC) on 4 Module GI switch board with 3/4 Module top cover plate on wall incl. necy. connection making earthing attachment, painting and mending good damages to building works.
On Board
SUB-HEAD 4-- PLUGS & SOCKETS
Supplying & Fixing GI Modular Switch Board of the following sizes complete with three no. suitable size Copper bar with holes (for Ph, N & E) fixed on bakelite/Hard Rubber insulator over the MS welded chairs incl. top cover flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works
6 Module
Supply & Fixing 240 V 6 A Modular type switch (Brand approved by EIC) on existing GI Modular type switch board having top cover plate and making necessary connections as required
Supply & Fixing 240 V, 6A, 5 pin Modular type plug socket (Brand approved by EIC), without switch & plug top, on existing GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
SUB-HEAD 5---SUPPLY OF LIGHT FITTINGS
[Supply & Delivery of following LED Industrial Batten light (System lumen efficacy 2110 Im/Watt) made of CRCA Sheet Body (Thickness > 0.50 mm) and construction as per relevant IS, along with LED lamp (Opal finish polycarbonate housing with Aluminium end-cap), Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range Oo to 400 C, internal surge protection of 2.5 KV with Short & Open circuit protection .
ITHD < 10% , P. F.20.95, P20, CRI >80, Flicker free, (Ricker should be below 5%), life time (LED, Driver & electrical circuitary), of minimum 40000 Burning Hours, with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.).
Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FR/FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 3 year OEM warranty. LM79 & LM8O Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise abovel 50° C)
Double Batten Fittings (2 x 18/20 Watt)
SUB-HEAD 6-- FIXING OF LIGHT FITTINGS
Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length.
SUB-HEAD 7 -- SUPPLY OF FANS
Supply & Delivery of 230V, 1-phase AC ceiling fans incl. all accssories, the capacitor of fan must be P-2 type brust proof & must have safety wire directly linked from fan hook to stator of fan. [Make: Crompton / Usha/ Havells/ Orient]
Sweep Size- 1200 mm (48"), Wattage ≤ 55 Watt, R.PM ≤ 350, Air Delivery ≥ 220 C.M.M
Supplying, installation, Testing & Commissioning of 230V, 1-phase AC exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust fan of following diameter, complete as required. [Make: EPC /Crompton /Usha /Havells/Orient]
300 mm (12"), 4 Blade, RPM ≤ 1420 , Wattage ≤ 82 Watt, Sound level ≤ 56 dB, Air Displacement (In CFM) ≥ 1120
SUB-HEAD 8-- FIXING OF FANS
Supplying & Fixing iron beam fan clamp of two piece type, as per approved specification, fabricated from 40 mm x 9 mm MS sheet flat suitable for beam having flange upto 150 mm wide – (As per Drawing no. 476 of PWD Specification Book – May 1991)
Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) (Brand approved by EIC) on existing Modular GI switch board with top cover plate incl. making necy. connections etc.
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire.
Extra for supplying additional wire for down rod & painting the rod exceeding 30 cm by 2x1.5 sqmm flexible copper wire.
Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of following diameter.
Supply & Fixing GI sheet (20SWG) metal Cowl with MS flat iron frame & GI wire mesh on wall with necy. bolts & nuts (6 mm dia x 62 mm long)
For 30 cm Exhaust fan (12")
PART-C (SITC OF UPS )
SITC of 415V, 3 Phase, 20 KVA 3Φ in - 1Φ out online UPS (Non- Modular) system with 30 minutes backup including batteries, interconnecting cables, battery rack etc.
Supplying & Fixing Industrial Plug & Socket board with 415 V, 30A, TPN & Earth Metal Industrial Plug socket & 30A Industrial top incl. S&F 32 A TPN/FP MCB breaking capcity 10kA (C- Curve) in SS enclosure fixed on wall and necessary conection.
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection [Make: Legrand / ABB / SIEMENS / Schneider /L&T]
415V, FP 32A (For UPS IN/OUT)
Supplying and fixing MCB SS enclosure with IP-20/30 protection, powder coated provision for two/four pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment [Make: Legrand / ABB / SIEMENS / Schneider /L&T]
Note: 1) All the above rates should be quoted inclusive of all taxes, duties and all ancilery charges with cost of maintenance, servicing, supply & replacement of spares for 1 (One) year from the date of commissioning. 2) Total is rounded off to the nearest rupees.
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
technical_2458165.pdf
techsummary_2458165.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.53 MB
Tendernotice_2.pdf
PDF • 1.03 MB
BOQ_2458165.xls
BOQ • 0.32 MB