HQ CWE AF JODHPUR
HQ CWE AF JODHPUR 342011 RAJASTHAN
Repair and Maint of HT Infra and allied works at Air Force Stn Mount Abu and Gurushikhar
2023_MES_574673_1
85966/E8
Open Tender
Civil Works
Item Rate
270 days
AGE I AF MOUNT ABU
As per NIT
7 documents required · 7 mandatory
₹500
AGE I AF MOUNT ABU
₹16,000
Yes
29 Mar 2023
12 Jan 2023
11 Feb 2023
12 Jan 2023
9 Feb 2023
27 Jan 2023
Amount
Disconnecting 11KV/440 Volts transformer complete all as specified and directed by Engineer-in-charge.
S & F in Reapir Disconnecting the transformer by taking out transformer oil for comprehensive maintenance of all parts including and terminals , replacement of rubber gasket sheet ,silica gel, cleaning and removing moisture from it taking all the assembly of transformer and removing / repairing the unserviceable parts, reassembling it after repair testing and commissioning the transformer of capacity 250- 400 KVA stepdown type complete all specified and directed .Repair to power distribution to stop the oil leakage by draining out transformer oil complete in moisture proof drum, dismantling the top cover along with conservator tank, Mashalling box, breather etc and replacing the oil seals and reassembling transformer, refilling oil after filtration by high vacuum oil filtration plant & testing complete all as specified and directed by Engineer-in-Charge.
Checking of ACB 1100 Volt cap 630-800 Amps and servicing/maintenance through authorised dealer for rectification of fault, connecting and testing on load complete all as specified and directed by Engineer-in-Charge.
Checking of VCB 11 KV cap 1200 Amps Make- ABB and Finding for Fault through authorised dealer for rectification of fault, connecting and testing on load all complete all as specified and directed by Engineer-in-Charge. Note: Replacement of unserviceable spares shall be measured & paid separately under other items of the schedule
Servicing, Testing and Calibration of 11KV HT-VCB
S & F in repair IDMT Relay Model No CGI
S & F In repair Master Trip Relay- 1 Element
S & F In repair Common Alarm Relay-01
S & F in repair 11KV CTs Dual Core, Dual Ratio, Class 0.5 & 5P10-01 nos
S & F in repair 11KV PT, 110V, Class 1.0 , 1 Phase -01 nos
S & F in repair TNC Switch
S & F in reapir LED Indicators st of three
S Hooter-01
Window Anunciator-01
Powerpack with Battery Backup-01
Thermostat
M & L ISI Marked transformer oil in sealed drum and topping up of transformer oil in transformers after filtration with 50 to 60 KV/min of die-electric strength of oil by high vacuum oil filtration plant complete all as specified and directed by Engineer-in-Charge.
Supply, laying, jointing and testing XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts, grade following cross sectional area laid in trenches / ducts / fixed on pole / wall / laid under road / path / culvert / drains / encased in pipe including taking down the existing cable complete all as specified and directed by Engineer-in-Charge. (a) 120 Sqmm 3 core
S & F In repair Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm
S & F in Repair Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm
S&F HT brass spindles with porcelain bush of power distribution transformer of capacity 200 KVA to 400 KVA including taking out unserviceable spindle complete all as specified and directed by Engineer-in-Charge.
Supply and filling dehydrating breather with first fill dehydrating agent (silica jel) supply and fix Dehydrating agent (silica jel) of power distribution transformer of capacity 200 KVA to 400 KVA including taking out unserviceable Silica Jel complete all as specified and directed by Engineer-in-Charge.
Disconnecting the GOD of any capacity and make from main power supply afte taking proper shut down and carrying out repairing of unserviceable GOD by taking down, dismantling & removing dust, carbon deposits or any other substance and replacing worn out parts like fixed contactor-01 Nos set, moving contactor-01 No. set, reasssembling complete GOD, re installing in position after applying petroleum jelly on moving and fixed contactor complete all as specified and directed by Engineer-in-Charge.
M & L Drop out fuse with fuse links and wire fuse complete of capacity HT 11KV 200 Amps 10(KA) station class complete with fixing clamps, bolts, nuts and washers fixed in repairs complete all as specified and directed by Engineer-in-Charge.
S&F in repair Lightening arrester of capacity HT 11KV 200 Amps 65(KA) station class complete with fixing clamps, bolts, nuts and washers fixed in repairs complete all as specified and directed by Engineer-in-Charge.
Excavation in trenches not exceeding 1.5 mtr deep and not exceeding 1.5m wide and getting out in hard / dense soil for laying of cables complete all as specified and directed by Engineer-in-Charge.
Returning and filling in including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick in hard / dense soil and making mounts of surplus soil complete all as specified and directed by Engineer-in-Charge.
Removing excavated surplus soil to a distance not exceeding 50 Mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-Charge.
Supply and laying bricks of size 230mmx115mmx75mmxcified and directed by Engineer-in-Charge.
M&L for sand cushioning using dry river sand for cable cushioning complete all as specified and directed by Engineer-in-Charge. Note:- for the purpose of payment punned thickness will be measured.
S&F RYB 3 phase LED indicator lamps (set of 3) complete all as specified and directed by Engineer-in-Charge.
Supply & F in reapiraluiminium lugs of 100 Sqmm to 400 Sqmm size complete all as specified and directed by Engineer-in-Charge.
M&L for preparation of old painted external exposed surfaces of HT panel board of any size and painting one coat of synthetic enamel paint of approved colour and make complete all as specified and directed by Engineer-in-Charge.
Comprehensive maintenance servicing and testing of APFC panel of capacity 90 KVAr -120 KVAr including cheching of Phase cap capacitors in all capacitor banks ,all MCCB's ,duty contactors, ST relay and all connected wiring including refitting of all as specified and directed by Engineer-in- charge. Note :- (a) Spares required for replacement shall be measured and paid separately.
Taking out unserviceable capacitors from the site of any/size complete all as specified and directed by Engineer-in-Charge.
S&F phase cap capacitor of capacity 5 KVAr in APFC panel complete all as specified and directed by Engineer-in-Charge.
S&F phase cap capacitor of capacity 10 KVAr in APFC panel complete all as specified and directed by Engineer-in-Charge.
S&F phase cap capacitor of capacity 12.5 KVAr in APFC panel complete all as specified and directed by Engineer-in-Charge.
S&F phase cap capacitor of capacity 15 KVAr in APFC panel complete all as specified and directed by Engineer-in-Charge.
S&F power factor controller ST relay ,230 Volt suitable for 120 KVAr APFC panel in APFC panel complete all as specified and directed by Engineer-in-Charge.
Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT , 25x20cm size
Checking of VCB 11 KV cap 400 Amps Make- ABB and servicing/maintenance through authorised dealer for rectification of fault, connecting and testing on load all complete all as specified and directed by Engineer-in-Charge. Note: Replacement of unserviceable spares shall be measured & paid separately under other items of the schedule
Servicing, Testing and Calibration of 11KV HT-VCB
S & F in repair IDMT Relay Model No CGI
S & F In repair Master Trip Relay- 1 Element
S & F In repair Common Alarm Relay-01
S & F in repair TNC Switch
S & F in reapir LED Indicators st of three
S & F Repair Window Anunciator-01
S & F repair Powerpack with Battery Backup-01
S & F Repair Thermostat
S & F Repair Dismantling insulators any type, any size
S & F Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150mm height, 150mm dia for 550 volts grade
rajesh builders
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .