| 4 | Not Admitted-Fee/PreQual/Technical 145 1 0 NEAR OLD LIC SHIV NAGAR VILLAGE TOWN MODIPURAM CITY MEERUT MEERUT UTTAR PRADESH 250110 INDIA | MEERUT | UTTAR PRADESH | 250110 | Not Admitted-Fee/PreQual/Technical Others-You have not submitted EMD by NEFT / RTGS and Bank guarantee is not prescribed format as mentioned in bid |
Tender Value
₹27.9 L
EMD Value
₹28,000
Closing Date
17 May 2023, 12:00 pmClosed
Superintending Engineer
Electricity Transmission Circle Agra Kakraitha Road, Near Amar Ujala Press, Sikandara , Agra
Construction of 02 Nos. 132 KV Metro Bay at 220 KV Sub-Station Sikandra under ETD - II Agra
2023_UPTCL_798826_1
ET_07_ETC_A_23_24
Open Tender
Electrical Works
Lump-sum
120 days
Agra
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,770
EE_A_ETC_AGRA
₹28,000
26 May 2023
25 Apr 2023
18 May 2023
25 Apr 2023
17 May 2023
25 Apr 2023
Supply
Supply of U bolted type Single Tension Fitting Assembly with Turn Buckle ,suitable for Single ACSR Panther Conductor and 132 KV Bus bar insulator including complete with Hardware fitting ,D sackle,Socket Eye,Ball Hook,Yoke Plate ,D-Clip,Tension Clamp etc. as per Technical Specification and sample
Supply of U bolted type Single suspension Fitting Assembly with Turn Buckle ,suitable for ACSR Single Panther Conductorand 132 KV Bus bar insulator including complete with Hardware fitting ,D sackle,Socket Eye,Ball Hook,Yoke Plate ,D-Clip,Tension Clamp etc. as per Technical Specification and sample
Supply of U bolted type Single Tension Fitting Assembly with Turn Buckle ,suitable for twin AAC Tranantulla Conductorand 132 KV Bus bar insulator including complete with Hardware fitting ,D sackle,Socket Eye,Ball Hook,Yoke Plate ,D-Clip,Tension Clamp etc. as per Technical Specification and sample
Supply of PG Clamp duly made of LM-6Aluminium Alloy suitable for ACSR Tarantulla to Tarantulla conductor complete with 4 No. 16X90mm GI Bolts ,Nuts,Spring &plain Washer as per technical specification and sample
Supply of PG Clamp duly made of LM-6Aluminium Alloy suitable for AAC tarantulla to ACSR Panther conductor complete with 4 No. 16X90mm GI Bolts ,Nuts,Spring &plain Washer as per technical specification and sample
Supply of PG Clamp duly made of LM-6Aluminium Alloy suitable for ACSR panther to ACSR panther conductor complete with 4 No. 16X90mm GI Bolts ,Nuts,Spring &plain Washer as per technical specification and sample
Supply of cooper flexible bond of 15X450 mm size with cooper lug fitted at both end having hole of 15mm dia in one lug and 12mm dia in other lug as per specification and sample
Supply of (LM-6) All-Alloy run through Bus post clamp suitable for twin panther conductor with nut, bolt & washer as per sample.
Supply of Performated tray 150MM wide made of All-Alloy suitable to various cable size complete with all assocaited accessories as per sample
Supply of cable glands for 2core, 4 core,6 core ,12 core cable with double compression type as per sample ( 1set = 50 gland of each type i.e total 200)
Supply of rigid spacers suitable for 132KV Bus bar Twin AAC Trantulla Conductor with 250mm spacing and duly made of LM-6 Aluminium Alloy complete with 12mm dia HDG bolts,Nuts,Spring, and plain washer as per technical specification and sample(total length of twin tarantulla bus =180 mtr ,each spacer at 2.5 mtr i.e 72 total)
Supply of 22 Kg fire extinguisher carbon dioxide type as per IS specification number 2878/1986 and as per technical specification
Supply of 11 Kg fire extinguisher carbon dioxide type as per IS specification number 2878/1986 and as per technical specification
Supply of 4.5 Kg fire extinguisher carbon dioxide type as per IS specification number 2878/1986 and as per technical specification
Supply of 50 Kg portable AFF mechnical foam type fire extinguisher complete with initial charge hose pipe and all other accessories and fitting as per IS1024 Trolly /wheel mounted
Supply of 120KN procelin disk insulator (54 tension string* 10 disk/string=540)
Supply of 70Kn porcelin disk insulator( 18 suspension string* 10 disk /string=180)
Earthmat extention and strenghtening work
Laying of earthmat in the exitended switchyard of the substation alomg with connecting the newly laid earthmat with existing earthmat as per details below:-
Fabrication of 3 mtr long electrode with 40mm dia Ms Round bar having 150mm long conical shape by due cutting straighting etc. and then piercing it vertically inside the ground with top 700mm below the ground level including shifting of MS round bar from the storage place at substation to switcyard
Laying of 40mm Dia MS round bar, 700mm below the ground level by due cutting straighting welding,painting excavation of trenches,backfilling of trench after laying of earthmat include shifting of MS round bar from storage place to switchyard
Making of 150mm long lap joint of above laid 40mm dia round bar to conect with existing earth mat of substation by due cutting straighting welding etc.
Making of 150 mm long lap jpint of above laid 40mm dia round bar by due cutting straighting welding etc.
Making of cross joint of above laid 40mm dia MS round bar 700mm below the ground level by due welding at all four corners including provifing and welding od suitable size 4 No of MS angle pieces on opposite corner of cross joint
Making of MS joint of above laid 40mm dia MS round bar with top of already vertically peirced MS electrode 700mm below ground level by due welding
Boring with 150 mm dia casing pipe to a probable depth of 21.0 meter long from ground level with skilled and unskilled labour including all T&P, boring apparatus and supervision charges etc. required for proper completion of work.Inserting 40x6 mm G.I. flat in 50 mm dia B-class (jindal) ISI mark 6.0 meter long 3 pipe placed horizontally on ground and bolting the G.I. flat with 150 mm long 75x6 mm copper plate conical piece on and then bolting the G.I. flat with G.I. pipe in such a way that copper flat remains in contact with the pipe. Lowering of 6.0 meter long G.I. pipe with conical copper Plate connected and at bottom along with G.I. flat inside the pipe in boring of 150 mm G.I. pipe pieces by G.I. sockets along with 40x6 mm G.I. flat running inside the pipe by making 150 cm lap joints 75 mm above ground level. Taking out 40x6 mm G.I. flat from the upper end of pipe by making a cut of 45 mm wide up to a depth of 50 mm in upper portion of G.I pipe and providing 1 no. cap type G.I. socket on upper threaded portion of pipe for water pouring in the pipe at regular intervals filling the space. All material to be provided by the contractorFabrication of M.S. electrodes out of 32 mm dia M.S. round 3.0 meter long having 150 mm long conical shape.Excavation of pit of size 2.00 M x 2.00 M x 1.50 M. driven of M.S. electrodes of 40 mm dia 3.0 Mtr. long in the earth on three corner of the pit equal distance of 2.0 Mtr. long keeping the top of electrode 50 cm above the pit ground level, welding of 40 mm M.S. round pieces of 3 Mtr. long on all three sides of electrodes and 15 cm below of top of electrode by 8 Nos. U-type clamp of 50x6 mm M.S. flat connecting a piece of 3 Mtr. long 40x6 mm G.I flat on opposite side of square welding of 40x6mm G.I flat on opposite M.S. electrode driven in ground and connecting the 40x6 mm G.I. flat. (Only M.S. Round & M.S. Flat shall be supplied by the department free of cost.)(G.I. Pipe, G.I. Flat, Copper Plate, Coal, Salt, Nut & Bolt shall be arrange by the contractor )
132 KV Main bus and Bay Erection
Erection and Fabrication (if needed) of Lattice type main gantry and auxillary structure their respective beams as per drawing /BOM is to be carraied out by contractor .All the duly stacked members of structure are to be shifted from store to work site ,tightining of nut ,bolts washer,fastening of beams applying standard practise .Beams are to be fastened on the proper alignment with exting coloum including cost of all labour ,T&P etc
Stringing of 132 KV 3 phase main bus and transfer bus bar including hoisting of disc insulator, suspension and tension fitting etc. along with shifting of the conductor/material place at that substation to the erection site
Stringing of 132 KV 3 phase main bus bar of of double AAC taruntulla conductor(1 JOB for each phase of bus bar per section)
Stringing of 132 Kv 3 phase tranfer bus bar of single ACSR panther/Zebra conductor (1 job for each phase bus bar per section)
Erection of equipment in proper alignment with complete adjustment in switchyard on the erected structure as per manufacture drawing or as per direction of supervising engineer after levelling including shifting the equipment from store to working site etc, alonf with their junction box, control cubical and accessories including the cost of labour T&P cranes for proper completion of work
145 KV SF6 CB including erection of structure and CB poles
132 Kv distance protection Panel
132 Kv Double feeder Control Panel
132 KV CT with junction box
132 KV PT with junction box
132 KV Line isolator with PI ,earth switch and adjustment
132 KV Bus isolator with PI ,earth switch and adjustment
132 KV Tendom isolator with PI ,earth switch and adjustment
132 KV Post insulator on ALP structure
120 KV Lighting Aresstor with surge counter
Dismentalling of Line/Bus/Tendom isolator with complete accessories of 100 MVA Transfomer as per instruction of engineer
Dismentelling of Fire hut/store and again reerection of Fire hut/store after repairing to other loacation as per instruction of enhineer
Opening of trench cover ,Laying and dressing of following size control cable on the cable racks in the trenches from crontrol and relay panel to various equipments for AC/DC connection of CT,PT,CB, isolator,junction box incude shifing of cables drums from store to erection site &shifting back the balanced material to store again placing back the opened trench cover including cost of labour,,T&P,etc. to complete the works
2C*2.5 sq mm
4C *2.5 sq mm
6C*2.5 sq mm
Termination of various sizes above laid control cable as per schedule and connection diagram ,extending DC supply from DCDB and AC supply from ACDB ,C&R panel,Equipment,CT,PT, including Drilling of holes wherever required ,fixing of performated cable tray ,fixing different sizes of cable gland ,ferrul,&crimping type ,lugs,including cost of required skilled material ,Technician,T&P for proper completion of work.
Earthing of main and auxillary structure equipment,trench and panels with the help of specified size MS flat along with cutting ,bendind and straigtining of MS flat to give it proper shape Two coat if Enamel based paint of green colour above red oxide primer layer at joint ,riser strips in all sides of surface as per drawing of earthing and standard practise incuding cost of consumable material,T&P ,lobour Etc.
Earthing with 75*12mm MS Flat
Earthing with 50*6mm MS Flat
Earthing with 25*6mm MS Flat
Jumpering of equipment of 132 KV metro bay with the help of ACSR Panther conductor to connect main bus bar anf tranfer bus bar with equipment and eqipment to equipment with help of suitable clamp /connector including ,cutting ,bending,shaping,etc,of the conductor as per site requirment
Making of shielding Mesh for 132 KV LA by fabrication of 3 meter long electrode with 40 mm dia MS round bar having 150mm long conical shape and then its piercing vertically in the ground with top 700mm below ground level jointing the electrode with 75 *12mm size MS flat by welding for making mesh ,connecting the shielding mesh with main earth mat at 2 places anf finnaly painting the shielding mesh /earthing strip with anti- corrosive red oxide primer and 2 coats of green paiht with digging of earth /trench and its back filling
Work of loading, safe carriage and unlaoding of any equipment, structure or any other material from any substation to JE store of 220KV S/S,Sikandra,Agra. Every to and from carriage from 220KV S/S,Sikandra,Agra will be considered as one job
Emulsifier Supply and Extention work
Supply along with installation , testing & commissioning of MS pipe 'B' class as per IS specification (IS code 1239,IS code 3589) for fire hydrant system complete with elbow,tee ,socet, reducer etc. with anti- corrosive paint teatment with detail given below (JINDAL,APPOLO,TATA).
Pressure guage as per IS Specification 3624 Accuracy 5%
Supply along with installation , testing & commissioning of gate valve (Sludge Valve/Butterfly Valve) (Kartar/Sir/ Zoloto make) as per IS Specification (is Code:14846)
Provide and fixing one coat of 4mm pypwrap/coatax antirust pipe protection including primer and lap of 25mm on external buried pipe including surface preparation complete in all respects.
Supply & installation of flange as per IS-1538 of different size as per drawing work include proper Butt welding with pipe & proper packing and coupling with Nut bolt ( 1 set = 2 no flange).
Supply & installation of MS pipe supports made of 'C' section angle of size 25*25*50mm suitable for different type of pipes with plinth below ground level as suitable with cement coarse sand and concrete for supporting pipe with Hydrant outliet/pipeline above the ground.Casting of pylon founadation in 1:2:4 concrete mixture sizw .5*.5*1 mtr with 16*450 4 Nos and 400*400*8mm plate including all material as cement ,sand,20mm stone
Supply & installation testing commissing of fire hose boxes suitable for 15 mtr long,63 mm dia reinforced rubber lined fire hose pipe (as per IS-636) with gun metal branch pipe nozzel ( As per IS -903) and gunmetal landing valve of 63 mm dia (As per IS code 5290). (1Set =15 meter long RRL hose pipe with gunmetal nozzel+15 meter long gun metal male and female coupling pipe for quick assem bling with existing branch pipe+63 mmgunmetal hydrant landing valve + box) .
Providing ,fixing and installation of Sign board of 3ft*2ftduly made of 2mm thick GI plate painted with red oxide promer with 2 coatinf and then yellow bright and shiny yellow paint and panted with black letter as direction of site engineer.board shall be provided with back support frame of size 35mm*35mm*5mm with provision of 2 leg for grouting duly painyed with black enamel paint complete with all repect to be grouted with casting of C.C founadation
Miscellaneous work
Supply and fixing of outdoor high beam flood light with power 100 Watt (LED) as light Sourse and versitile pressure Die-cast aluminium body with poly carbonate fitting having potted type power driver suitable for 220 AC input supply of IS marked havels/philips/Syska with warrenty of 2 year including laying of cable & termination of connection LED in switchyard with the help of clamps.
Supply and fixing of junction box of size 280X22X150mm made of 16 SWG sheet duly painted on cloumn by fixing GI flat and its earthing with 12 SWG GI wire and fixing 1 no of 6 amp MCB for connection to the LED with 3 phase backalite terminal block and cooper neutral link complete in all respect with all material,labour and T&P
laying and termination of 2C/4C/6C 2.5 sq mm size of cable 500mm below the ground including excavation of trench of appropriate size ,laying cable termination proper dressing and all assocated work to complete the job as per specification.
Supply and fixing of outdoor 3 phase Lightining AC Subdistribution box of size 450x450x250mm duly painted with one coat of red oxie primer and two coat of synthetic enamel paint .4 No almunium insulated bus bar for AC distributional and 1 no. of 100AMP TPN SFU with SS of haevells /L&T make/C&S.It should have 4 no. of bakalite fuse with fuse base of 100 Amp and hole should be provided for 4 no. cables of 50/95 sq mm with cable glands(fire proof) of dowell make then termination on both side cables .cubical box made of 16 SWG MS sheet sheet in double shutter with indoor locking arrangements complete with wiring of proper size and phase indicatora nd earthing terminal
Supply and fixing of 2 tonn split air conditioning unit with stabalizer in the control room make HITACHI/ Ogeneral/ Mitishubushi complete with all associated accessories having 2 year comprehensive and 5 year compressor warrenty due to not availibilty of air conditining in new extended control room
Providing and erecting of new pale fencing made of MS Sheet of size 18 SWG 2400mm long and 100mm width each pale.The work include erecting of new pale fencing vertically after properly weding and bolting with MS angle support on each grouting leg.Cleaning of complete pale fencing and making the surface suitable for painting. Then applying one coat of red oxide primer of good quality and then two coat of synthetic enamel paint in green colour ASIAN/BURGER/NEROLEC.
KARAN SINGH
P&H Engineering
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .