Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹19.9 L
EMD Value
₹39,800
Closing Date
3 Nov 2025, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE Amrisar
HQ CWE Amritsar
SPL REPAIR FOR REPLACEMENT OF DG SET 125 KVA AGAINST BER AT MH IN OLD AMRITSAR CANTT
2025_MES_734874_1
83049/E8
Open Tender
Civil Works - Others
Item Rate
120 days
GE Amritsar
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE Amritsar
₹39,800
Yes
11 Nov 2025
13 Oct 2025
10 Nov 2025
13 Oct 2025
3 Nov 2025
27 Oct 2025
Supply, install, commissioning and testing Diesel generating set 125 KVA/100 KW capacityy, 3 phase, 415 volts, 50 hz, 174 Amps, 1500 RPM, 4 Wire, 4 cylinder as per BS 5514/IS-10002 high speed diesel Engine with starting system 24 volts DC electrical exhaust temperature 488 ˚C as per 125 KVA/100 KW latest CPCB-IV norms complete with standard control of at NTP conditions with acoustic weather prooof enclosure of canopy set as per CPCB (Central pollution control Board) norms and noise level shall not exceed 75 decible at distance of 1 m and comprising of turbo charge water cooled engine inclusive of following standard accessories.
(a) Engine : Multi/cylinder compression ignition, heavy duty, compact diesel engine liquid cooled with standard accessories, all as per BS-5514/SO-3046, 1500 RPM, control gauges, RPM/Hours meters etc; shaft H.P suitable for generating application and capable of giving an output for coupled alternator under NTP conditions, complete with following :- (i) Flyewheel housing with flywheel to suit closed coupled single bearing alternator. (ii) Air-cleaner dry type with vacuum indicator. (iii) Fuel pump and fuel piping 15mm M.S pipe with bends, flanges etc. (iv) Fuel filter with water separtor and filter element. (v) Lub-oil filter with filter element (vi) D.C starter 24 volts. (vii) Storage Batteries of suitable voltage and ampere-hours as recommended by the manufacturerd. (viii) Residential silencer as per existing CPCB IV norms (ix) Supporting/fixing arrangement for muffler with ceiling through antivibration pads. (x) Enginer overspeed stop/trip switch. (xi) Rediator with fan. (xii) Dynamo for battery charging. (xiii) Gerrosion inhibitor coolant. (xiv) Engine control panel electronic digital display type consisting of battery volatage indicator, lub oil temp and pressure gauges coolant water temp gauge, RPM indicator cum hour meter etc. (xv) Safety controls for alarm due to high water temp (HWT) and low lub oil pressure (LLOP). (xvi) Any other devices/accessories recommended/supplied by the manufacturers as standard equipment.
(b) ALTERNATOR: Self regulated with brushless self excitation 125 KVA/100 KW 415 V, 3 phase, 4 wire, 50 HZ, 0.8.P.F., 1500 RPM, with voltage variation plus or minus 2.5% of rated voltage from no-load to full-load foot mounted, screen protected drip proof type with class 'F insulation, closed coupled single bearing alternator, with necessary controls as recommended by the manufacturers, conforming to BS-5000/IS-4772, capable of supplying unbalanced load. (I) Any other devices/accessories recommended/supplied by the manufacturers as standard equipment. (c) Fuel tank as recommended by manufacturer with inlet and outlet connection and fuel level indicator & cap of tank should not be less than 275 liters. (d) base frame fabricated from MS channel of suitable size and machined to ensure perfect alignment. (e) One No manintenance free battery of 12 volts each of 180 AH lead acid type (f) Built in battery charger free as per OEM recommendation complete with fittings. (g) SKID: The engine and alternator will be coupled, aligned and mounted on a specially designed common base frame fabricated from M.S chaneels of suitable cross sectional area and length with bottom drilled holes suitable for and including supplying and fixing anti vibration Paus of required size numbers as recommended by the manufacturers for mounting of 125 KVA/100 KW DG set.
(I) Any other devices/accessories recommended/supplied by the manufacturers as standard equipment. (c) Fuel tank as recommended by manufacturer with inlet and outlet connection and fuel level indicator & cap of tank should not be less than 275 liters. (d) base frame fabricated from MS channel of suitable size and machined to ensure perfect alignment. (e) One No manintenance free battery of 12 volts each of 180 AH lead acid type (f) Built in battery charger free as per OEM recommendation complete with fittings. (g) SKID: The engine and alternator will be coupled, aligned and mounted on a specially designed common base frame fabricated from M.S chaneels of suitable cross sectional area and length with bottom drilled holes suitable for and including supplying and fixing anti vibration Paus of required size numbers as recommended by the manufacturers for mounting of 125 KVA/100 KW DG set. (h) AME Panel : AMF panel shall be suitable size factory made indoor cubical type front openable fabricated from CRCA steel sheet 1.6 mm thick complete as per manufacturer specification of fiesel Engine suitable for DG set of capacity 125 KVA grouted in floor by providing PCC 1:2:4 type B-2 foundation of suitable size as per manufacturers recommendations complete in all respects and consisting of the followings :
Notes : (i) Contractor will satisfactoryilly conduct load test of DG set for 12 hours including run on 10% overhead for 1 hours. (ii) testing equipment will be arranged by the contractor. (iii) Fuel/oil required for load test shall be procured from same , (v) DG set shall be DG set shall be the representative of Accepting officer before commissioning and cost thereof deemed to be included in quoted rates. (vi) The foundation of DG set shall be provided as per manufacturer's drawing/instructions and quoted shall deemed to be included for this provison and noting extra shall be admixible on this account.
Supply and laying testing cable XLPE insulated armoured electric power cables heavy duty 1100 volts grade with aluminium conductor of size 95 Sqm x 3.5 crore laid in trenches/ on wall/ poles / floor complete all as specified and directed.
Supply and laying HDPE pipe 65mm bore for laying of LT cables etc complete with all accessores complete, all as specified and directed.
Supply and fixing of off-load change over switch side handle 415 volts 4 pole 200 Amp including incoming & outgoging connection complete, all as specified and directed.
Material and labour for Earthing complete with galvanised earth plate 600 x 600 x 6mm thick burried directly in ground ( Earth pit not less than 2.25 m below ground level) with top edge of earth plate not less than 1.5 m below normal ground level, connected to galvanised earth strip 32 x 6 mm size by means of nuts, bolts, check nuts & washers of galvanised iron of steel all as electrical plate No .3 of MES schdule 2009, part-I (Specification) and connected to main switch board / main DB's earthing test point including all necessary excavation and earth work in any type of soil, adequate quantity of charcoal dust & common salt all around the earth plate minimum 150 mm in all directions with & including watering pipe 20 mm dia GI Medium grade, GI funnel made out of 0.63 mm thcik GI sheet, wire gauge, 50 mm thick RCC cover in PCC 1:2:4, type B-1 (using 20 mm graded crushed stone aggregate), duly reinforced with 6 mm dia mild steel round bars @ 150mm both ways center to center with suitable lifting handle to ceover, earth pit of PCC 1:3:6 type C-1 (using 20 graded crushed stone aggregate), GI protection pipe light grade 40 mm bore up to 7.5m length from earth electrode & engraving of earth marking on nearby building with CM:4 plate size 200 x 150 x 15 mm & painting of earth result etc. including testing on complete all as specified and directed. Note :- On testing after completion of JOB, if desired earth resistance is not more than 1 ohm obtained the earthing shall be redone by the contractor without any extra cost to Govt.
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.34 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.27 MB
Tender83049.pdf
Tender Documents • 0.83 MB
BOQ_822878.xls
BOQ • 0.24 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .