Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.8 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | Rejected-Technical | - | Rejected-Technical As Per PQ |
Tender Value
Refer Docs
EMD Value
₹65,000
Closing Date
4 Sept 2024, 3:00 pmClosed
Managing Director
No.4, Rajiv Gandhi Salai Taramani Chennai 600 113.
E TENDER FOR PROVISION OF INTEGRATED BUILDING MANAGEMENT SYSTEM (IBMS) WITH ALL ACCESSORIES FOR MINITIDEL PARK AT PILLAIYARPATTI VILLAGE, THANJAVUR TALUK and DISTRICT.
2024_TIDEC_475190_1
TIDEL/2024-25/15
Open Tender
Electrical and Maintenance Works
Works
45 days
PILLAIYARPATTI VILLAGE, THANJAVUR TALUK
As per Tender
4 documents required · 4 mandatory
₹0
₹65,000
10 Oct 2024
22 Aug 2024
5 Sept 2024
22 Aug 2024
4 Sept 2024
30 Aug 2024
22 Aug 2024 - 29 Aug 2024
Amount
BMS SERVER, WORKSTATION, PRINTER: Intel core i7, 3 GHz processor, 16GB DDR3 RAM, 1TB SATA Hard Disk, DVD Writer, Lan Card 10/100/1000 base-T, Optical Mouse, 104 Keys Keyboard, Windows 7 / Windows 10 operating system. The workstation shall have Inbuilt graphics card and capable of connecting to dual monitor. The workstation to be supplied with latest Antivirus software.
Supply, Installation, Testing and Commissioning of 42" LED Monitor.
Supply, Installation, Testing and Commissioning of A 4 size Color Laser Alarm Printer suitable for the application, with driver software.
Supply, Installation, Testing and Commissioning of BMS SOFTWARE: Web enabled Graphical interface software based on MS Windows 10 / Latest. The system should be accessible from anywhere on LAN or WAN or Ethernet without additional licenses. The Communication protocol shall be Industry Standard BACNET Open Protocol. System should be scalable. The software shall be open system architecture type which facilitates interoperability with other system over BACNET IP with complete control and monitoring functions. Software shall be certified and complying to BACnet Advanced Operator Workstation. The software shall have facility to define alarms for certain consumption values. Software should be BACnet standard ISO 16484-5 protocol 1.13 or latest. Required gateway/open protocol software compatible to Modbus RTU/BACNet.
Supply, Installation, Testing and Commissioning of Client version BMS software for "Monitor & Control" application, complete with Advance Graphics for Realtime Graphical Depiction of the Statuses and Controls as per the Detailed IO Summary.
Supply, Installation, Testing and Commissioning of SMS & E-mail alarm notification module with unlimited user capability,SMS Paging & Email Facility for transmitting specified alarms to designated personnel.
Supply,Installation,Testing & commissioning of Serial interface Modules (as a part of IO Module train) for High Level integration with following 3rd Party Equipment's as mentioned in the data point summary. Integration of the following equipment's and generating software for monitoring the parameters. Integration cost shall include charges towards development of graphic screens for all the equipment's listed below. The system will warrant an Exclusive, Dedicated Serial Interface Card / Controller for every single individual 3rd party system ( No other 3rd Party Integration shall be clubbed with any one integration ) The Interface controller shall be Capable to Integrate Open protocol systems on BACnet / Modbus / M-Bus Protocol Made available on serial RS 485 interface. Such Interface controller shall be Installed in a deticated enclosure and the same has to be connected with the BMS system through BACNET / IP protocol with following accessories
Integration of Fire Alarm System - 500 points
Integration of Digital Load Managers for metering.- 50 Nos - 10 points each (total 500 points)
Integration of AHU VFD - 28 Nos 10 points each (total 280 points)
Integration of UPS - 2 Nos - 20 points each (total 40 no's)
Integration of VRF System - 16 ODU's - Upto 30 nos
Integration of VRF System - 32 IDU's
Integration of Diesel Generator - 2 nos
Integration of Lift - 3 nos
Integration of Solar System- 3 nos
Integration of STP
BACNET / MODBUS communication card for VRF by the OEM to integrate the VRF system with IBMS
Supply, installation, testing & commissioning of Differential Pressure Switches to monitor AHU Fan Status with necessary coolectiong tube for suitable length and NO NC for the status of range of 500 pascal
Supply, installation, testing & commissioning of Differential Pressure Switches to monitor AHU Pre Filter Status with necessary coolectiong tube for suitable length and NO NC for the status of range of 300 pascal
Supply, installation, testing & commissioning of Return air temperature sensor - Duct mount type Air Temperature (Range: 0-50⁰C ) having pt1000 / Ni1000 output for Temperature and temperature accuracy +/- 0.5 ˚C & with accessories & all complete,
Supply, installation, testing & commissioning of Ambient Temperature and RH Sensor with Radiation shield - Outside Air Temperature & RH Sensor (Range: Temp 0-50⁰C & Humidity 0-100% ) having 0-10V DC output for Temperature & RH , Temperature accuracy +/- 0.5 ˚C, RH accuracy +/- 3% for 10-90% RH , to be installed in common return duct at AHU side with accessories & all complete.
Supply, installation, testing & commissioning of Level Switch For Water Tank
Supply and Run of 2 Core 1.0 SQ. MM, GI unarmored ATC conductor multi strand, Unscreened cable. Laid on Surface / On Cable Trays. All Cables shall be ferruled and tagged, and shall use lugs for termination at both ends.
Supply and Run of 2 Core 1.0 SQ. MM, GI unarmored ATC conductor multi strand, screened cable. Laid on Surface / On Cable Trays. All Cables shall be ferruled and tagged, and shall use lugs for termination at both ends.
Supply and Run of 2 Core 1.5 SQ. MM, GI unarmored ATC conductor multi strand, screened cable. Laid on Surface / On Cable Trays. All Cables shall be ferruled and tagged, and shall use lugs for termination at both ends.
Supply and Run of 3 core x 1.5 sqmm screened unarmored cable for Power. Laid on Surface / On Cable Trays. All Cables shall be ferruled and tagged, and shall use lugs for termination at both ends.
Supply and Run of 4 Core 1.0 SQ. MM, GI unarmored ATC conductor multi strand, screened cable.. Laid on Surface / On Cable Trays. All Cables shall be ferruled and tagged, and shall use lugs for termination at both ends.
Supply and Run of CAT 6 Communicatiuon cable.. Laid on Surface / On Cable Trays. All Cables shall be ferruled and tagged, and shall use lugs for termination at both ends.
Supply & laying PVC- FRLS conduits complete with all fittings and accessories-1 " PVC Conduit on wall
Supply & laying PVC- FRLS conduits complete with all fittings and accessories-19MM PVC Conduit on wall
Supply and fixing of Factory Fabricated Perforated Cable tray of size : 50 mm x 50 mm made out of 1.6 mm thick galvanized sheet. for housing communication cables from all the systems. In all AHU Rooms, Cable trays between DDC panel to the termination should be used.
Supply and fixing of Factory Fabricated Perforated Cable tray of size : 150 mm x 50 mm made out of 1.6 mm thick galvanized sheet. for housing communication cables from all the systems. In all AHU Rooms, Cable trays between DDC panel to the termination should be used.
Supply, installation, testing & commissioning of of Network Switch : 24 port layer Network switch with 10/100/1000 Mpbs
Supply, installation, testing & commissioning of 24U Rack - 19" type Equipment racks for mounting the Servers/ Switches in the BMS Equipment Room, & for mounting field mounted Switches at every Floor. Racks shall be complete with Modular Patch Panels for Patching the Field Cables ( Cu and FO) with the Edge Switches on floor as required. Racks shall be provided with Dual Power A&B, and should have 2 PDU Strips, Redundant Fans and Door to have Tamper Switch.
Any other accessories required to complete the system configuration as per vendor specific requirements i.e. Power supplies, fiber converters, LIUs, Specific System cables etc. to complete the installation. Contractor to mention the quantity of the below items with cost apart from the below item if any other accessories are required , contractor to add the same Patch Panels,1mtrs Cat6 Patch Cords LIU’s Pigtail cables 1mtr LC to LC Single Mode Patch Cords, Labels, any Other component to complete the design intent
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .