Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹14.8 LAccepted-Finance | 1 | Accepted-Finance Lowest bidder | |
| 2 | 2₹15.6 L+₹81,310 (5.49%)Rejected-Finance | 2 | Rejected-Finance 2nd lowest bidder | |
| 3 | Not Admitted-Fee/PreQual/Technical N A | FARIDABAD | HARYANA | 121004 | - | Not Admitted-Fee/PreQual/Technical Others-Non Submission of hard copy of tender fee and non uploading of scanned documents like EMD Experience certificate pan card work completion certificates GST registration certificates etc |
Tender Value
₹16.2 L
EMD Value
₹32,320
Closing Date
12 May 2022, 4:00 pmClosed
Executive Engineer ED-III JPDCL Jammu
Office of the Executive Engineer ED-III JPDCL Jammu
Fixing of Rate contract for Augmentation of 11/0.415KV Distribution Substations from 250/400 KVA to 630KVA on turnkey Basis at various locations under the Jurisdiction of ED-III Rehari Jammu during the financial year 2022-23
2022_PDD_166579_1
ED-III/JPDCL/1 of 2022 Dated- 12-04-2022
Open Tender
Electrical Works
Turn-key
45 days
Within Jurisdiction of the XEN ED-III JPDCL Jammu
Please refer Tender documents.
3 documents required · 3 mandatory
₹1,000
Executive Engineer ED-III JPDCL Jammu
₹32,320
18 Jul 2022
13 Apr 2022
13 May 2022
13 Apr 2022
12 May 2022
13 Apr 2022
13 Apr 2022 - 12 May 2022
Amount
Augmentation of Distribution Transformer from 250/400 KVA to 630 KVA
Supply, Installation & commissioning of 11/0.433 KV, 630 KVA 3-Phase Distribution Transformer with Bi-metallic terminal Connectors, Energy Level: 2, "BIS Marked" (Copper Wound) alongwith LV Cable Box having detachable Alumnium Gland plate including Transportation
Supply & Fixing of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
Supply, Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A
Providing & Fixing of Single Phase PVC Cable 400 mm² ,1.1K V Grade, PVC Insulated Stranded Un-Armoured FRLS type alongwith Al. Thimbles for 400 mm² Cable termination with four colored PVC Tapings to distinguish the LT Phases and the Neutral. (2 Ckt)
Supply, Transportation, Erection of 9 Mtr Long ST Pole (ST-410 SP33) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. Including painting with two coats of Red Oxide and Al. Paint for smooth surface.
11kV Polymeric composite Disc Insulator 12kV with fitting, min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Supply, Transportation, Fabrication & Fixing of MS Channel Iron, Cross arms, Angle Iron Braces, Clamps etc duly fabricated, red oxide & aluminium paint coated including all necessary Nut & Bolts & Washers etc.
Providing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of Pole mounted LT Distribution Box for 630 KVA DTR with 2 No. Triple Pole MCCB of 630Amp with adjustable overload release (80-100%) for incomer & switch fuse unit for 2 Nos Out Going Ckts., Material of Busbar for Phases & Neutral-EC Grade Aluminium, PVC Insulated Sleeved Busbar of required load handling capacity with colour code for Phases and Neutral differentiation, including Aluminium thimbles of required sizes for proper termination etc.
Construction of Cement Platform (8x8x3) & 3feet below ground level ) for 630 KVA SubStation along with the mesh fencing around the Periphery. (complete Job)
Providing & Fixing of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Providing & Fixing of Wedge Connectors / PG Clamps
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Anti Climbing device with Clamps
Providing of Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole
Transportation of Dismentalled 11/0.415KV 250/400KV Distribution Transformer along with allied material from dismentalling Site to Divisional Stores.
VEENA CONSTRUCTION CO.
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .