Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.7 LAccepted-AOC | L1 | Accepted-AOC Lowest | |
| 2 | L2₹39.1 L+₹19,507.50 (0.50%)Rejected-AOC 58 CHANDRALOK BUILDING MAYO HOSPITAL ROAD NAGPUR 440 018 | NAGPUR | MAHARASHTRA | 440018 | L2 | Rejected-AOC Not Lowest | |
| 3 | L3₹39.7 L+₹73,968.50 (1.90%)Rejected-AOC 58 CHANDRALOK BLDG MAYO HOSPITAL ROAD NAGPUR 440018 | NAGPUR | NAGPUR | MAHARASHTRA | 440018 | L3 | Rejected-AOC Not Lowest |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
28 Dec 2024, 6:00 pmClosed
Garrison Engineer
Military Engineer Services, Garrison Engineer, Kamptee 441001
REPAIR/REPLACEMENT AND UPGRADATION OF LT UG CABLE, LT PANEL, STREET LIGHT FITTINGS STREET LIGHT TIMER, MCCBS EARTHINGS AND CONNECTED ITEMS IN CERTAIN UNIT AT MIL STN KAMPTEE UNDER GE KAMPTEE.
2024_MES_686319_1
8712/E8
Open Tender
Civil Works
Item Rate
180 days
Kamptee
All as per NIT
8 documents required · 8 mandatory
₹0
₹80,000
Yes
27 Jan 2025
29 Nov 2024
30 Dec 2024
29 Nov 2024
28 Dec 2024
13 Dec 2024
Amount
Supply and laying in trenches or fixing in walls / poles or drawing through pipe XLPE insulated, screened,PVC bedded, galvanised steel strip, electric power cables (heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 240 Sqmm, 3.5 core including testing after laid and jointed, including taking down of the existing cable, cable is upgraded hance existing cable to be taken on ledger charge, for reuse, all as specified and as directed. Make :- Polycab/Havells/KEI Note:- Excavation and earth work, cable protection shall be measured and paid separetely.
All as per item No. 1 but cable size 185 Sqmm, 3.5 core all as specified and as directed.
All as per item No. 1 but cable size 150 Sqmm, 3.5 core all as specified and as directed.
Excavation in trenches in soft/loose of soil not exceeding 1.5 meter wide and not exceeding 1.5M in depth for laying of Cables, poles, stay and getting out of excavated material complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the cables have been laid and tested complete all as specified and directed.
Removal of surplus soil to a distance not exc. 50m and deposited where directed at a level not exc. 1.5 m above the starting point all as specified and as directed .
Supply and fix in repair Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 120 mm outer diameter and 103.5 mm inner Diameter with IS 16285 (part 2):2001 laid in trenches, wall, floor, pole including bends, sockets and other connected accessories complete all as specified and directed. Make:- Dura. Line/Tijaria/REX/Ketron
Supply and fix in repair Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 90 mm outer diameter and 75 mm inner Diameter with IS 16285 (part 2):2001 laid in trenches, wall, floor, pole including bends, sockets and other connected accessories complete all as specified and directed. Make:- Dura. Line/Tijaria/REX/Ketron
Material and labour for testing the cables with high voltage DC testing machine and locating the fault in the cables by fault locating machine to pin point exact position of fault, disconnecting faulty 1100 Volt LT cables of different sizes from both ends, removal of Fault, Re-connections and testing of cables after removal of fault complete all as specified and directed. Notes : (i) All T&P and other accessories required for checking and finding of fault in cable shall be provided by the Contractor (ii) Charges/rent of the fault locating mobile machine, operator, engineer, electricians etc shall be deemed to included rate quoted by Contractor. (iii) Checking and finding fault upto 05 places of same route of the cable will be considered as one Job.
Supply and fix in repair Heat shrinkable straight through cable jointing kit for 1100 Volts grade cable joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 240 Sqmm. Note :- Any Excavation and earth work, Returning and filling, Removing involved shall be measured and paid separately. Make :- Densons / M-Seal / Raychems
All as per item No. 21 but cable size 70 Sqmm to 95 Sqmm all complete as specified and directed.
All as per item No. 21 but cable size 16 Sqmm to 50 Sqmm all complete as specified and directed.
S&F in renewal MCCB 63 Amps, 4 Pole, 415V, 50 Hz, Adjustable type, with breaking capacity 16 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / C & S / ABB
S&F in renewal MCCB 100 Amps, 4 Pole, 415V, 50 Hz, Adjustable type, with breaking capacity 25 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / C & S / ABB
S&F in renewal MCCB 125 Amps, 4 Pole, 415V, 50 Hz, Adjustable type, with breaking capacity 25 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / C & S / ABB
S&F in renewal MCCB 160 Amps, 4 Pole, 415V, 50 Hz, microprocessor release based type, with breaking capacity 36 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / C & S / ABB
S&F in renewal MCCB 200 Amps, 4 Pole, 415V, 50 Hz, microprocessor release based type, with breaking capacity 36 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / C & S / ABB
S&F in renewal MCCB 250 Amps, 4 Pole, 415V, 50 Hz, microprocessor release based type, with breaking capacity 36 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / C & S / ABB
S&F in renewal MCCB 320 Amps, 4 Pole, 415V, 50 Hz, microprocessor release based type, with breaking capacity 36 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / C & S / ABB
S&F in renewal MCCB 400 Amps, 4 Pole, 415V, 50 Hz, microprocessor release based type, with breaking capacity 36 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / C & S / ABB
S&F in renewal MCCB 63 Amps, 3 Pole, 415V, 50 Hz, Adjustable type, with breaking capacity 16 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / C & S / ABB
S&F in renewal MCCB 100 Amps, 3 Pole, 415V, 50 Hz, Adjustable type, with breaking capacity 25 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / C & S / ABB
S&F in renewal MCCB 125 Amps, 3 Pole, 415V, 50 Hz, Adjustable type, with breaking capacity 25 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / C & S / ABB
S&F in renewal MCCB 160 Amps, 3 Pole, 415V, 50 Hz, microprocessor release based type, with breaking capacity 36 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / C & S / ABB
S&F in renewal MCCB 200 Amps, 3 Pole, 415V, 50 Hz, microprocessor release based type, with breaking capacity 36 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / C & S / ABB
S&F in renewal MCCB 250 Amps, 3 Pole, 415V, 50 Hz, microprocessor release based type, with breaking capacity 36 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / C & S / ABB
S&F in renewal MCCB 320 Amps, 3 Pole, 415V, 50 Hz, microprocessor release based type, with breaking capacity 36 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / C & S / ABB
S&F in renewal MCCB 400 Amps, 3 Pole, 415V, 50 Hz, microprocessor release based type, with breaking capacity 36 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / C & S / ABB
Supply and fix in repair LED street light luminaires of capacity 60 watts with pressure die cast aluminium housing heat resistance toughened glass, IP 66 protection and efficacy minimum 120 Lumen per watt, complete with driver, including three core copper flexible wire of size 0.75 Sqmm for connection from street light fitting to OH line or junction box, fixing accessories and complete all as specified and directed. Make :- Philips / CG / Havells
Supply and fix in repair LED street light luminaires of capacity 120 watts with pressure die cast aluminium housing heat resistance toughened glass, IP 66 protection and efficacy minimum 120 Lumen per watt, complete with driver, including three core copper flexible wire of size 0.75 Sqmm for connection from street light fitting to OH line or junction box, fixing accessories and complete all as specified and directed. Make :- Philips / CG / Havells
Supply and fixing of smart integrated 36 Watt Smart Bright, All in one Solar Street Light including galvanized steel pole with suitable bracket for hanging, with Infra Red Remote, with built in mono crystalline panel, Lithium ferro phospate (Lite PO 4) Battery , MPPT charge controller and PIR sensor with colour teperature 6000-6500 K, including nuts, bolts, washers, excavation /earth work, PCC 1:4:8 type D-2 using 40mm aggregate for pole foundations of suitable size recommended by the manufacturer and using PCC 1:2:4 B-1 for coping with suitable of size including necessary formwork etc, complete all as specified and directed. Make : Philips/Havells/CG
Supply and fixing in repair of smart integrated 36 Watt Smart Bright, All in one Solar Street Light including suitable bracket for hanging on existing pole / wall, with Infra Red Remote, with built in mono crystalline panel, Lithium ferro phospate (Lite PO 4) Battery , MPPT charge controller and PIR sensor with colour teperature 6000-6500 K, including nuts, bolts and washers etc, complete all as specified and directed. Make : Philips/Havells/CG
Supply and fix in repairs thermoplastic cable entry junction boxes of size 250 x 220 x 135 mm and IP-65 protection level with metric knock out fixed on poles with MS clamps, nuts, bolts and washers including MCB SPN, 5-32 amps, 'C' series, breaking capacity 10 KA, 'C' curve 240 volts, 50Hz including necessary incoming and outgoing electric connection with suitable size of copper lugs etc., separate (detachable) gland plate, bakelite connector 4 way 20 amp, dust and vermin proof, front door opening with hinges and locking arrangement, complete all as specified and as directed. Make:- Sintex/Hensel or equivalent
Supply and fix in repair bracket for street light fittings made out of 32 mm dia GI pipe of light grade 1.5 m long each bent to shape & size required & fixed to pole with and including flat iron clamps 02 Nos made out of 30 x 5 mm flat iron including GI Nuts, bolts and washers and painting of clamps and street light brackets with two coat of aluminium paint over a coat of red oxide primer and fittings bracket to street light fitting including taking down old unserviceable bracket of any shape and size all as specified and as directed.
Supply, erecting & fixing in replacement of steel tubular swaged pole complete with base plate, pole cap, nut bolt washer etc type 410 SP-31 (9.00 meters long) swaged poles conforming to IS 2713 (Part-I to III) 1980 all as specified including two coats of black bitumen paint through out internally and externally upto planting depth and applying two coats of aluminum paint over one coat of red oxide primer (externally) and Numbering of poles as directed including excavation /earth work, PCC 1:4:8 type D-2 using 40mm aggregate for pole foundations of size 600x600x1500mm height upto ground level and using PCC 1:2:4 B-1 for coping with size 450x450x300mm including necessary formwork complete with including taking down old unserviceable pole all as specified and as directed.
Materials and labour as in replacement for earthing complete with galvanized earth plate electrode 600 x 600 x6mm thick burried directly in ground vertically to a depth not less than 2.25 M below normal ground level ) with top edge of the plate not less than 1.50 M below normal ground level , connected to and including GI wire 4.0 mm as earth lead soldered and riveted to earth plate by means of nuts, bolts, check nuts & washers, of galvanized iron or steel with connected to test point and testing on completion including 40mm GI light grade pipe for earth lead protection from earth point to earth plate, including provn adequate quantity of charcoal dust mixed with 35 % common salt to a packed thickness of not less than 32 cm in alternate layers of charcoal and salt on all sides of earth plate with 20mm bore medium grade GI Pipe for watering,GI check nut, funnel and wire mesh with and including all necessary excavation & earth work in soft/loose soil, returning filling in, removal of surplus soil to a distance 50 metre, PCC 1:3:6 type C-1 as in earth pit, 40 mm thick RCC cover using cement concrete 1:2:4 type B-1 reinforced with & including 8 mm dia mild steel TMT bar @ 100 mm c/c Both way with suitable handle for lifting arrangement & including form work complete all as specified and shown in electrical plate No 3 of MES SSR Part I 2009 and as directed. NOTES:- (a) On testing, after completion of Job, if desired earth resistance is not obtained, the earthing shall be redone at without any extra cost by contractor.
Materials and labour as in replacement for earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground vertically to a depth not less than 2.25m below ground level with top edge of earth plate not less than 1.5m below ground level connected to galvanized iron earth strip 32 x 6 mm by means of bolts, nuts, check nuts, washers of galvanized iron and connected to main switch/control board upto 7.5m away from the earth electrode including excavation earth work, PCC chamber, RCC cover slab char coal, watering pipe, wire mesh lugs, earth lead protection pipe 40 mm bore, light grade 7.5m long as applicable and as per plate No. 3 of SSR 2009 and all as specified. (a) Excavation and earth work in any type of soil. (b) Drilling of holes in electrode (c) PCC pit in cement concrete (1:2:4) type B-1 (d) 40 mm thick Pre-cast RCC cover with suitable handle. (e) Funnel with watering pipe of GI 20 mm nominal bore ,medium grade & copper lug etc. (f) 40 mm nominal bore medium grade GI protection pipe 7.50 m long for protection of earthing lead. (g) Requisite quantity of charcoal and common salt. (h) Connection to earthing test point and testing on completion.
M&L for plate earthing in replacement of old earthing complete with copper earth plate electrode 60 cm x 60 cm x 3.15 mm thick buried directly in ground vertically (in earth pit not less than 2.25 m below normal ground level) with the top edge of the earth plate at a depth not less than 1.5 m below normal ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides and incl copper earth strip 20 x 3 mm bolted (with copper/ brass nuts, bolts & check nuts) and riveted to earth plate at one end and connected to metallic bodies of equipment’s/ earthing test point etc at the other end, earth strip encased in and including 40 mm GI light grade pipe with all fittings from top of electrode to body of equipment fixed with and including 25x4mm iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from bottom of earth pit to top of electrode complete with wire mesh funnel and earth pit in PCC 1:3:6 type C-1 using 20 mm graded crushed stone aggregate and CI cover and frame complete all specified and shown in electrical plate No 3 of SSR Part-1 including testing earth resistance and submitting test report to AGE E/M by the contractor complete all as specified and directed. Note:- (i) Rates for excavation and earthwork in any kind of soil/ strata, testing on completion, copper strip 20x3 mm and 40 mm dia light grade GI protection pipe upto 7.5 metres from earth plate is deemed to be included in the rate quoted.
M&L for Loose filling with aggregates of gauge 20 mm crushed stone back colour suitable for spreading in electrical sub stn after preparation site by removing all type of debris, removing unwanted soil, and spreading lime powdwer beneath the aggregate all as directed.
Supply and fixing in replacement LED flood light 100 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete with taking down old unserviceable flood light complete all as specified and directed by Engineer -in -charge. Make :- Phillips / CG/ Havells
Supply and fixing in replacment Automatic Load Transfer Switch Changeover 100 Amps, 4 Pole with CM 331 Controller, 415 Volts, with 16 A DP MCB for protection with all control wiring , incoming and outgoing connection with cable lugs, washers, nutbolts, Sheet Enclosure Box (2mm thick sheet ) which is suitable of outdoor and accessories complete with taking down old unserviceable changeover switch all as specified and as directed. Make :- HPL Item code ATS100 4 POS or equivalent
Supply, fixing and testing in replacement of Automatic Street light Timer Switch using combination of NATURE SWITCH for automatic switching of street lights based on LUX level of natural light consisting with Sensor (Natural Switch) along with suitable power contractor, MCB and support terminals should be enclosed in pole/ wall mountable SMC enclosure made out of Rust proof, Electric shock proof, termite proof and FR grade SMC junction Box conforming to IP 54 protection of capacity 12 KW 3 phase, current range 40 Amps, 4 wire (3 separate power contactor) including all accessories and fixing arrangement all as specified and directed. Model No. Swadeep - 02EC-8kW3P.
Supply and installation, testing & commissioning self-supporting totally enclosed factory fabricated LT bus Each bar panel box made out of 3.15mm thick MS sheet with projected globe roof for rain water protection, dust and vermin proof hinged double shutter doors with neoprene rubber gasket epoxy powder coated including danger plate, earth strip, ventilation louvers, bottom detachable gland plate complete with suitable size zinc chromium plated nuts, bolts, and washers etc outdoor type cubicle panel board suitable for 3 Feeder phase 4 wire 415 volt 50 HZ and 40 mm x 40 mm x 6 mm angle iron frame, weather proof ventilated with locking arrangement incl of PCC pedestal, accommodate and consisting of the following items :- (i) Aluminium bus-bar 600 Amps, supported with suitable size Porcelain stand lock with suitable size brass nut, bolts and washers with heat shrinkable colour coded PVC sleeving for 3 phase & neutral . - 01 Set (ii) MCCB with microprocessor release, 4 pole, 400Amps, 36 KA, 415 Volts, 50 Hz Adjustable - 01 No. Make:- C&S/ABB /Havells.
Supply and installation, testing & commissioning self-supporting totally enclosed factory fabricated LT bus Each bar panel box made out of 3.15mm thick MS sheet with projected globe roof for rain water protection, dust and vermin proof hinged double shutter doors with neoprene rubber gasket epoxy powder coated including danger plate, earth strip, ventilation louvers, bottom detachable gland plate complete with suitable size zinc chromium plated nuts, bolts, and washers etc outdoor type cubicle panel board suitable for 3 Feeder phase 4 wire 415 volt 50 HZ and 40 mm x 40 mm x 6 mm angle iron frame, weather proof ventilated with locking arrangement incl of PCC pedestal, accommodate and consisting of the following items :- (i) Aluminium bus-bar 400 Amps, supported with suitable size Porcelain stand lock with suitable size brass nut, bolts and washers with heat shrinkable colour coded PVC sleeving for 3 phase & neutral . - 01 Set (ii) MCCB with microprocessor release, 4 pole, 200Amps, 36 KA, 415 Volts, 50 Hz Adjustable - 01 No. Make:- C&S/ABB /Havells.
M&L for drilling suitable dia horizontal bore holes for insertion/ laying of upto 110mm bore HDPE pipe/GI pipe of any description below/under existing road surfaces/apron /floors etc with using mechanical and / or manual devices as required at site including making good the disturbed surfaces to match with the existing strata after laying pipes complete all as specified and directed. (NOTE : (i) Pipes shall be laid minimum 60 cm below/under existing road surfaces/ apron /floors etc). (ii) Equipment, tools and plant material (horizontal boring rig machine) required for boring shall be arranged by contractor without any extra cost to the Govt.
Supply and fixing in replacement of GI tubing, 100 mm bore, light grade as in sleeving/protection of cable etc fixed on pole / wall etc. with and including suitable size of MS clamp and nut, bolt, washer etc, complete all as specified and directed.
Supply and fixing in replacement of Contactor of type MU-2P series (rating 16 A / 25A / 40A) suitable for existing Automatic Street light Timer Switch complete with taking down old unserviceable Contactor all as specified and as directed. Make - L&T/ Havells or equivalent in approved make.
Supply and fixing in replacement of Contactor of Freedom series, 3 pole (rating 18 A / 25A / 40A) suitable for existing Automatic Street light Timer Switch complete with taking down old unserviceable Contactor all as specified and as directed. Make - L&T/ Havells or equivalent in approved make.
Cleaning of sub station area by uprooting all types vegitation, shrubs, weeds, saplings and creepers of unwanted trees complete with the help of spade, axes, crowbars, and thereafter chemical spraying will be done and other mechanical means after taking necessary electrical shutdown from concerned incharge of various sub stns of Military Stn Kamptee.
M & L for attending emergent complaint on call basis, checking of DG Set (capactiy 20 KVA to 200 KVA ) & AMF Panel (any type and size) for detecting any kind of fault in DG Set & AMF Panel and attending the fault immediately at any time round the clock and carry out certain repair as per site requirement and checking of DG Set and AMF Panel and replacing of worn out parts of DG Set & AMF Panel by expert Engineer, complete all as specified and directed. Note : (a) Charges for detecting the fault in DG Set/AMF Panel/Electric System are included in the quoted items rate. (b) Amount of minor repairs, nut-botls-washers, cleaning cloth, grease etc are included in the quoted items rate. (c) Repalcement of worn out major parts of DG Set/AMF Panel shall be measured and paid separately under items of schedule 'A'.
M&L for carrying out "B" check for 20 KVA to 200 KV DG set [Make : Ashok Leyland / KOEL / Mahindra / Kirloskar] as per manufacturer's recommendation including replacement of necessary spares and filters such as Fuel filter-02 Nos , SLO Bypass filters-02 Nos and Lub oil filters-04 Nos complete including rectification of minor defects, cleaning of air filters/ crankcase breather/Baffel type breather & coolant tank with air blower, replacement of Engine oil & coolant and tuning of engine all as specified and directed. [Notes: (i) Rate quoted shall include for all filters, topping up Engine oil, Coolant & distilled water in batteries & minor accessories like nuts, bolts, 'O' rings etc.]
Material & labour and T&P for disconnecting cable connection, shifting, installing, testing and commissioning of Diesel Generator / Transformer of any capacity from one location to other location within the defence land at Mil Stn Kamptee / Nagpur complete all as specified and directed. Note : Cost of materials required for connecting, commissioning and testing of transformer shall be deemed to be included in quoted rate.
M&L for Diesel Generator Set platform of size 4.0 m x 2.25 m x 0.70 m height comprising of PCC 1:2:4 grade (nominal mix) using 40mm gradred crushed stone aggregate in foundation, providing 150mm thick hardcore of broken stone or boulders of gauge n exc. 63 mm and 150mm thick RCC slab M-25 grade (Nominal Mix) on top reinforced with 12mm dia TMT bars and finishing top surface with 15mm thick plastering in cement mortar 1:4 finished even and smooth using extra cement complete all as specified and directed. Note:- (excavation and earth work and PCC shall be Included in quoted rate).
M&L for PCC 1:4:8 type D2 (40 mm graded aggregate) for foundation work / plinth / hardstanding etc, complete all as specified and directed.
M&L for PCC 1:2:4 type B1 (20 mm graded aggregate) for coping of pole foundation, formwork etc. complete all as specified and directed.
Material and labour for cable route indicator made out of PCC (1:2:4) type B1 of size 60cm x 15cm x 5cm thick grouted in PCC (1:2:4) type B1 pillar fo size 30 x 30 x 45 cm in ground with and including necessary foam work and making on board 1100 Volt LT Cable with arrow indicating cable path (marking shall be engraved and colour painted), complete all as specified and directed.
NOTE:- SCHEDULE OF CREDIT (Amount shall be deducted offline from the total quoted amount to workout the net contract sum to be considered for acceptance.) [(-) Rs. 21,675.00]
M/S. ELECTROPOWER TECHNOLOGIES (BID ID -3194448)
Paragon Electrotechnics (BID ID -3194694)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .