Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹49.9 LAccepted-Finance | ₹49.9 L | L1 | Accepted-Finance Being lowest bidder |
| 2 | L2₹51.3 LRejected-Finance | ₹51.3 L | L2 | Rejected-Finance Not become Lowest bidder |
| 3 | L3₹54.7 LRejected-Finance MATHOSHREE PLOT NO 55 SR NO 787 A BEHIND ASHWANI HOSPITAL GOVIND NAGAR NASIK 422 009 | NASIK | NASHIK | MAHARASHTRA | 422009 | ₹54.7 L | L3 | Rejected-Finance Not become Lowest bidder |
| 4 | L4₹55.4 LRejected-Finance D12 GROTH CENTRE COLONY BIJAULI JHANSI U P | JHANSI | UTTAR PRADESH | 284001 | ₹55.4 L | L4 | Rejected-Finance Not become Lowest bidder |
| 5 | L5₹55.8 LRejected-Finance A 63 ELDECO COUNTY PHASE II RAJGARH JHANSI U P 284135 | JHANSI | JHANSI | UTTAR PRADESH | 284135 | ₹55.8 L | L5 | Rejected-Finance Not become Lowest bidder |
| Sl No | Description | Qty | Unit | M/s Raghav Traders L8 | VIJAY BUILDERS L7 | M/S Kumar Contractors L1 | ROHIT ENTERPRISES L5 | M/s Sohanil Construction L2 | ADARSH ENTERPRISES L6 | FTH TRADERS L4 | DURGAI ELECTRICALS L3 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Design, Fabricate, Supply, Installation, Testing & Commissioning in replacement of outdoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus bar and cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3.15mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall be suitable for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity including taking down old unserviceable Feeder Pillar Box of any description complete all as specified and directed :- | 2 | Each Job | 15,100 ₹30,200 | 14,400 ₹28,800 | 1,40,000 ₹2.8 L | 14,500 ₹29,000 | 95,555 ₹1.9 L | 15,000 ₹30,000 | 14,000 ₹28,000 | 15,440 ₹30,880 |
| 1.01Note : (i) Factory made name plates with feeder names/ Bldg Nos shall be fixed on relevant incomer/outgoing MCCB doors. (ii) The contractor shall submit set of all drawings of the LT Pillar Boxes and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing.However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations. | |||||||||||
| 1.02(i) Bus bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeves insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCB's and outgoing MCCB's up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.) and continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel. (ii) Incomer : (a) MCCB 250 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 01 No (b) Digital Voltmeter with selector switch - 01 Set (c) Digital Ammeter with selector switch & suitable ratio of CT's - 01 Set of 3 (d) LED Pilot light indication lamps R,Y,B phases - 01 Set of 3 (iii) Outgoing :- (a) MCCB 100 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 05 Nos | |||||||||||
| 2.00 | Design, Fabricate, Supply, Installation, Testing & Commissioning in replacement of outdoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus bar and cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3.15mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall be suitable for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity including taking down old unserviceable Feeder Pillar Box of any description complete all as specified and directed :- | 2 | Each Job | 27,700 ₹55,400 | 21,000 ₹42,000 | 1,95,000 ₹3.9 L | 20,000 ₹40,000 | 2,85,555 ₹5.7 L | 21,000 ₹42,000 | 21,500 ₹43,000 | 21,000 ₹42,000 |
| 2.01Note : (i) Factory made name plates with feeder names/ Bldg Nos shall be fixed on relevant incomer/outgoing MCCB doors. (ii) The contractor shall submit set of all drawings of the LT Pillar Boxes and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing.However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations. | |||||||||||
| 2.02(i) Bus bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeves insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCB's and outgoing MCCB's up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.) and continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel. (ii) Incomer : (a) MCCB 200 Amps, 4 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 01 No (b) Digital Voltmeter with selector switch - 01 Set (c) Digital Ammeter with selector switch & suitable ratio of CT's - 01 Set of 3 (d) LED Pilot light indication lamps R,Y,B phases - 01 Set of 3 (iii) Outgoing :- (a) MCCB 63 Amps, 4 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release -10 Nos | |||||||||||
| 3.00 | Design, Fabricate, Supply, Installation, Testing & Commissioning in replacement of outdoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus bar and cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3.15mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall be suitable for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity including taking down old unserviceable Feeder Pillar Box of any description complete all as specified and directed :- | 2 | Each Job | 1,70,000 ₹3.4 L | 1,40,000 ₹2.8 L | 1,80,000 ₹3.6 L | 1,65,000 ₹3.3 L | 1,95,555 ₹3.9 L | 1,70,000 ₹3.4 L | 1,50,000 ₹3 L | 1,45,000 ₹2.9 L |
| 3.01Note : (i) Factory made name plates with feeder names/ Bldg Nos shall be fixed on relevant incomer/outgoing MCCB doors. (ii) The contractor shall submit set of all drawings of the LT Pillar Boxes and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing.However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations. | |||||||||||
| 3.02(i) Bus bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeves insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCB's and outgoing MCCB's up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.) and continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel. (ii) Incomer : (a) MCCB 160 Amps, 4 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 01 No (b) Digital multimeter - 01 Set (c) LED Pilot light indication lamps R,Y,B phases - 01 Set of 3 (iii) Outgoing :- (a) MCCB 63 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 8 Nos | |||||||||||
| 4.00 | Supply and fixing in replacement of outdoor type dust proof & vermin proof busbar chamber TPN type with aluminium busbar current rating 100 Amp 4 out going ways, solution for safe power distribution step type cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3.15mm thick for outer shell with front openable with locking arrangement . Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-42 degree of protection complete all as specified and directed :- | 4 | Each | 15,700 ₹62,800 | 16,500 ₹66,000 | 20,000 ₹80,000 | 15,500 ₹62,000 | 45,555 ₹1.8 L | 16,000 ₹64,000 | 15,600 ₹62,400 | 19,000 ₹76,000 |
Tender Value
₹50 L
EMD Value
₹1 L
Closing Date
16 Apr 2026, 6:00 pmClosed
Maj Rajesh Rathore
Garrison Engineer Jhansi
REPAIR, MAINTENANCE AND RENEWALS TO VARIOUS LT OH LINES, LT UG CABLES ALONG WITH LT PANELS AND CONNECTED WORKS AT B ZONE UNDER AGE E/M AT GE JHANSI
2026_MES_757785_1
GE/JHA/TOK/110 OF 2025-26
Open Tender
Electrical and Maintenance Works
180 days
GE Jhansi
As per NIT and Tender Documents
9 documents required · 9 mandatory
₹500
GE Jhansi
₹1 L
Yes
9 Jun 2026
26 Mar 2026
18 Apr 2026
26 Mar 2026
16 Apr 2026
9 Apr 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
Design, Fabricate, Supply, Installation, Testing & Commissioning in replacement of outdoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus bar and cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3.15mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall be suitable for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity including taking down old unserviceable Feeder Pillar Box of any description complete all as specified and directed :- | - | Each Job | - | - | |
(i) Bus bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeves insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCB's and outgoing MCCB's up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.) and continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel.
(ii) Incomer :
(a) MCCB 250 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 01 No
(b) Digital Voltmeter with selector switch - 01 Set
(c) Digital Ammeter with selector switch & suitable ratio of CT's - 01 Set of 3
(d) LED Pilot light indication lamps R,Y,B phases - 01 Set of 3
(iii) Outgoing :-
(a) MCCB 100 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 05 Nos | - | - | - | - | |
Design, Fabricate, Supply, Installation, Testing & Commissioning in replacement of outdoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus bar and cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3.15mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall be suitable for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity including taking down old unserviceable Feeder Pillar Box of any description complete all as specified and directed :- | - | Each Job | - | - | |
(i) Bus bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeves insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCB's and outgoing MCCB's up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.) and continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel.
(ii) Incomer :
(a) MCCB 200 Amps, 4 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 01 No
(b) Digital Voltmeter with selector switch - 01 Set
(c) Digital Ammeter with selector switch & suitable ratio of CT's - 01 Set of 3
(d) LED Pilot light indication lamps R,Y,B phases - 01 Set of 3
(iii) Outgoing :-
(a) MCCB 63 Amps, 4 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release -10 Nos | - | - | - | - | |
Design, Fabricate, Supply, Installation, Testing & Commissioning in replacement of outdoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus bar and cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3.15mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall be suitable for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity including taking down old unserviceable Feeder Pillar Box of any description complete all as specified and directed :- | - | Each Job | - | - | |
(i) Bus bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeves insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCB's and outgoing MCCB's up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.) and continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel.
(ii) Incomer :
(a) MCCB 160 Amps, 4 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 01 No
(b) Digital multimeter - 01 Set
(c) LED Pilot light indication lamps R,Y,B phases - 01 Set of 3
(iii) Outgoing :-
(a) MCCB 63 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 8 Nos | - | - | - | - | |
Supply and fixing in replacement of outdoor type dust proof & vermin proof busbar chamber TPN type with aluminium busbar current rating 100 Amp 4 out going ways, solution for safe power distribution step type cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3.15mm thick for outer shell with front openable with locking arrangement . Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-42 degree of protection complete all as specified and directed :- | - | Each | - | - | |
Supply and fixing in replacement of outdoor type dust proof & vermin proof busbar chamber TPN type with aluminium busbar current rating 200 Amp 4 out going ways, solution for safe power distribution step type cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3.15mm thick for outer shell with front openable with locking arrangement . Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-42 degree of protection complete all as specified and directed :- | - | Each | - | - | |
Supply and fixing in replacement of outdoor type dust proof & vermin proof busbar chamber TPN type with aluminium busbar current rating 250Amp 4 out going ways, solution for safe power distribution step type cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3.15mm thick for outer shell with front openable with locking arrangement . Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-42 degree of protection complete all as specified and directed :- | - | Each | - | - | |
Supply and fixing in replacement of outdoor type dust proof & vermin proof busbar chamber TPN type with aluminium busbar current rating 300 Amp 4 out going ways, solution for safe power distribution step type cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3.15mm thick for outer shell with front openable with locking arrangement . Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-42 degree of protection complete all as specified and directed :- | - | Each | - | - |
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.16 MB
BOQ_848809.xls
BOQ • 0.58 MB
TenderDocuments110.pdf
Tender Documents • 1.28 MB
Download all tender documents and submit your bid