Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
₹17.0 L
EMD Value
₹33,964
Closing Date
4 Jun 2025, 11:00 amClosed
SO 1 wks
HQ 7 SECT AR
Repair Maint Servicing of Generator sets Transformers and other EM Items at various locations under HQ 7 Sect AR through AMC
2025_ARMHA_860992_1
Engr/2818/7 Sect/2025-26/440
Open Tender
Civil Works
Item Rate
330 days
HQ 7 SECT AR
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
Yes
Adm Comdt HQ 7 Sect AR
₹33,964
Yes
HQ 7 SECT AR
16 Jul 2025
21 May 2025
5 Jun 2025
21 May 2025
4 Jun 2025
21 May 2025
21 May 2025 - 4 Jun 2025
21 May 2025
SCHEDULE' A' PART-I (DG Set) M&L maintenance and servicing of 125 KVA DG set, water cooled (Make-Kirloskar) complete including draining out engine oil from the sump, flushing the sump and cleaning, replacement of gaskets, fuel filters, oil filters, air cleaner elements and the worn out parts like fuel flexible pipes, nuts, bolts, fuel line etc, filling the starting batteries with electrolyte, applying pertroleum jelly in battery terminals poles, checking of voltage, amps, rpm, fuel, coolant and exhaust leakages, aligment and checking of both engine and alternator part etc including refilling radiator coolant, tightening all the nuts adn bolts to the required torque incl testing in all respect as per directed by Engr-in-Charge (Rate of oil filter, fuel filter and coolant to be paid seperately
M&L maintenance and servicing of 62.5 KVA DG set, water cooled (Make-Kirloskar) complete including draining out engine oil from the sump, flushing the sump and cleaning, replacement of gaskets, fuel filters, oil filters, air cleaner elements and the worn out parts like fuel flexible pipes, nuts, bolts, fuel line etc, filling the starting batteries with electrolyte, applying pertroleum jelly in battery terminals poles, checking of voltage, amps, rpm, fuel, coolant and exhaust leakages, aligment and checking of both engine and alternator part etc including refilling radiator coolant, tightening all the nuts adn bolts to the required torque incl testing in all respect as per directed by Engr-in-Charge (Rate of oil filter, fuel filter and coolant to be paid seperately
M&L maintenance and servicing of 62.5 KVA DG set, water cooled (Make-Kirloskar) complete including draining out engine oil from the sump, flushing the sump and cleaning, replacement of gaskets, fuel filters, oil filters, air cleaner elements and the worn out parts like fuel flexible pipes, nuts, bolts, fuel line etc, filling the starting batteries with electrolyte, applying pertroleum jelly in battery terminals poles, checking of voltage, amps, rpm, fuel, coolant and exhaust leakages, aligment and checking of both engine and alternator part etc including refilling radiator coolant, tightening all the nuts adn bolts to the required torque incl testing in all respect as per directed by Engr-in-Charge (Rate of oil filter, fuel filter and coolant to be paid seperately
Draining out the old engine oil from DG set, cleaning of deposits and rectifing the leakages if any by means of welding, brazing and cleaning of oil tank and filling of new Engine oil complete all as specified and directed by Engr in Charge. Note :- The engine oil shall be measured seprately.
Opening /taking out of fuel injection pump (FIP) of DG Set of any type/make and capacity 20 KVA to 50 KVA disconnection of fuel injector line carrying complete overhauling /servicing of injecor pump, calibration of fuel pump as per manufacturer instruction , assembling of the same with DG Set properly in original position , checking the allignment , making proper fuel connection including renewal of unserviceable/defective minor parts like seal, 'O' ring, gaskit fuel pumpl, gear technometer, bushing technometer cover fuel pump gear housing fuel pump gear etc and testing for smooth operation complete all as directed , after replacement of following major parts if found defected/unserviceable :- Note Following items measured & Paid seperately.
(a) Fuel gear pump
(b) Shaft with fuel drive
All as per item No 5 here in before but 62.5 KVA to 100 KVA
(a) Fuel gear pump
(b) Shaft with fuel drive
Supply and fixing of Oil filter element for suitable size for 100 KVA to 125 KVA DG set
Supply and fixing of Oil filter element with 'O' ring for suitable size for 62.5 KVA
Supply and fixing of Oil filter element with 'O' ring for suitable size for 15 KVA to 30 KVA DG set
Supply and fixing of fuel filter element for suitable size for 62.5 KVA to 125 KVA DG set
Supply and fixing of fuel filter element for suitable size for 15 KVA to 35 KVA DG set
Supply and fixing of Air filter for suitable size for 62.5 KVA to 125 KVA DG set
Supply and fixing of Air filter for suitable size for 35 KVA to 15 KVA DG set
Removal of self starter motor from the DG Set of capacity 20 KVA to 45 KVA of existing make , strip opening the starter for the renewal of minor parts like bush gear, o ring assy, bush set, sealing kit, brush set including assembling and re fixing at site complete all as specified and directed.after replacement of following major parts if found defected/unserviceable :- Note Following items measured & Paid seperately.
(a) Armature
(b) Solenoied switch
(c) Field Coil
All as per item No 14 here in before but 62.5 KVA to 100 KVA
(a) Armature
(b) Solenoied switch
(c) Field Coil
Removal & Renewal of old unserviceable feed pump for fuel injection pump complete assy for various capacity of DG Sets.
S & F in Renewal of fuel shut down solenoied valve kit including taking outold valve assy and making all connection testing for smooth operation in any type DG Set complete all as specified and directed by Engr-in-Charge.
M & L for 'B' check kit of DG set 20 KVA to 50 KVA
All as per item No 21 here in before but 62.5 KVA to 100 KVA
S & F in Renewal , V belt of DG Set 20 KVA to 50 of as per existing make and capacity complete all as directed.
All as per item No 24. here in before but 62.5 KVA to 100 KVA KVA
M & L for top up of coolent in concentrate form rediator of DG Set of any type/Make and capacity , complete all as directed. Make :-Bosch, feelit guard & equalient Note: Measurement shall be done only in concentrate form of coolant.
S & F in Renewal of Fule hose flexible with matalic type from fuel tank to filter, filter to FIP including allied nut bolt washer and coupling for DG set 20 KVA to 50 KVA with and including taking out old hose and making all connection testing for smooth operation all as directd.
All as per item No 27 here in before but 62.5 KVA to 100 KVA
S & F in Renewal of radiator hose pipe suitable both inlet and outlet of 62.5 KVA to 100 KVA DG Set with including taking out old hose and making all connection , testing for smooth operation complete all as directed .
S & F in Renewal of 12 V 180 AH Battery tubler Make : Exide Express/Amoron
S & F in Renewal of 12 V 150 AH Battery Make : Exide Express/Amoron
S & F in Renewal of 12 V 100 AH Battery Make : Exide Express/Amoron
S & f in Renewal of battery terminals made of brass , suitable for battery of any type /make and capacity , complete all as directd.
S & F in Renewal of PVC insulated multi stranded copper single core unsheathed cable of size 70 sqmm , 1100 volts grade for battery lead Red snd Black colour and all as directed.
S & F Renewal of burnt /UNSV thermostat with new thermostat alongwith complete assy for DG set connection complete all as specified and directed.
Removal & Renewal of old u/s RPM CABLE of any type/make of DG set complete all as specified and directed by Engr -in- Charge .
Removal & Renewal of old U/S WATER TEMP METER of any type and all as specified and directed by Engr -in- Charge .
Removal & Renewal of old U/S OIL PRESSURE METER of any type and all as specified and directed by Engr -in- Charge .
Removal & Renewal t of old U/S OIL TEMP METER of any type and all as specified and directed by Engr -in- Charge .
Removal & Renewal of old U/S HCT Switch of any type and size of DG Set and all as specified and directed by Engr-in-Charge.
Removal & Renewal of old U/S LLOP Switch of any type and size of DG Set and all as specified and directed by Engr-in-Charge.
M & L for taking down of existing fuel from fuel tank by means of removing of sludge and sediments deposited inside the fuel tank by repeatedly washing by useing of chemical & detergent with air compressor including rectifing of leakage if found. and refixing the same position as per direction of engineer in charge by testing all as specified and directed. cap 20 KVA to 100 KVA DG Sets.
Opening and taking out of cylinder head 20 KVA to 180 KVA capcity DG Set Renewal of inlet and exhaust valve , valve guide seats and lapping of valve machining job pressure testing i/c replacement of u/s parts reassembling with complete testing as requd .
S & F in replacement of anti viberation mounting pad B series complete all as directed .
S & F distilled water in sealed packing for DG 12 volts battery.
S & F in Renewal of battery charging sets automatic type , fixed in DG set /panel with transformer and rectifire etc including rewiring of faulty control complte all as specified and directed by Engr-in-Charge.
All as per item No. 46.a but 12 V DC charging set
All as per item No. 46.a but 24V charging set
S & F in Renewal of by reconditioning of DG set panel board by means of painting by power coated with proper fixing of nut, bolts, hinges, welding and fixing of necessary door lock set of DG sets of any capacity with handle including double key complete all as specified and directed by Engr-in-Charge.
S & F in Renewal of Automatic voltage Regulator (AVR) suitable for DG Set of 40 KVA to 125 KVA capacity with and including taking out old AVR and making all connection testing for smooth operation complete all as specified and directed .Make : Tavr-20(k) , Stemford.
S & F in Renewal of Rotating diods suitable for DG set of Cap 40 KVA to 500 KVA with and including taking out old diods and making all connection testing for smooth operation complete all as specified and directed .
M & L for opening /taking out of turbo charger of DG Set of 40 KVA to 200 KVA capacity , disconnection of air supply connection pipe etc complete overhauling serviceing of turbo charger replacement of turbo charger repair kit including calibration /testing of turbo charger system complete and re assembling the same fitted with DG set properly in original position checking the alignment making proper all connection testing for smooth operation complete all as directed.
S & F in replacement of Exhaust Muffler of DG Set any type any cap and all as specified and directed by Engr-in-charge.
S & F in replacement of Expension bellow for exhaust of DG Set any type any cap and all as specified and directed by Engr-in-charge.
S & F of MCCB, 200 Amp, 4 Pole , 415 Volts, 25 KA breaking capacity, adjustable thermal and magnetic setting complete all as specified and directed.
Renewal of MCCB, 100 Amp, 4 Pole , 415 Volts, 25 KA breaking capacity, fixed thermal and magnetic setting complete all as specified and directed.
Renewal of MCCB, 63 Amp, 4 Pole , 415 Volts, 25 KA breaking capacity, fixed thermal and magnetic setting complete all as specified and directed.
S & F Renewal of on line change over switch 200 Amp, 4 pole, front operated complete all as specified and directed.
S & F Renewal of on line change over switch 100 Amp, 4 pole, front operated complete all as specified and directed.
S & F Renewal of off load change over switch 63 Amp, 4 pole, side operated complete all as specified and directed.
S & F Renewal of off load change over switch 100Amp, 4 pole, side operated complete all as specified and directed.
S & F Renewal of off load change over switch 200 Amp, 4 pole, side operated complete all as specified and directed.
M&L Renewal of earthing complete with galvanized steel earth plate electrode 60cm x 60 cm x 6 mm thick buried directly in ground earth pit not less than 4.50 mtr deep below ground level with top edge of the plate not less than 3.75 mtr below ground level connected to galvanized earth strip 32 x 6 mm by means of bolts, nuts, check nuts and washers of GI or steel surrounded with adequate quality of charcoal dust mixed with salt on all side of earth plate including complete earthwork PCC 1:2:4 chamber and RCC 1:2:4 cover all as shown in electrical plate No 5 and all as specified and directed by EIC
S & F Renewal of asbestos rope of 19 mm dia around of the exhaust pipe of diesel engine any cap complete all as specified and directed by Engr-in-Charge.
M & L for Renewal by removal taking out old burnt winding from exhaust fan and winding suitable size of copper wire of exhaust fan, ball bearing motor of any type and size and refixing the same including dismantling and all as specified and directed by Engr-in- charge.
Dismantling alternator assembly of the following capacities incl taking out of worn out windings of Rotor and stator incl rewinding the coils with suitable guage of copper wire, replacement of insulation materials, heat varnishing, replacacement of connecting leads and terminal plates all as required to make serviceable of the DG and including reassembling the same after necessary testing all as directed. The item rate includes shifting of altternatos from location to workshop and back to the installation complete all as directed Note : Copper wire shall be measured & paid separately under relevant item of the schedule.
M&L for copper winding for item No-87 above as per existing guage complete all as specified and directed
M&L and Renewal of Radiator water pump assy 320 kvat to 500 kva capacity complete all as specified and directed
S & F fuel cap suitable lock & key type of 62 to 500 KVA DG sets all as specified.
S & F Renewal of fuel shut down brass solionid valve make : cummines
S & F Renewal of fan with moter size 600mm sweep suitable for 62.5kva air coolded DG set. All as specified and directed by engineer in charge.
Supply and fixing hose pipe
Supply and fixing of over flow pipe set
Supply and fixing of fan belt for 125 KVA, 100 KVA, 62.5 KVA, 35 KVA, 30 KVA, 20 KVA, 15 KVA Genr set
SCHEDULE' A' PART-II (Solar Power Plant) Repair & maint of old existing inverter of system voltage 240/360/480 volt by inspecting, repair of replacement of internal part complete along with DC wiring connection PCBs, indicators volts & AMP meters (Digital/Analogue type) and make the inverter functional by connecting to esisting battery bank all as specified and directed Note:- If the inverter is non-repairable then the same shall be replaced with hybrid type inverter of suitable capacity wrt existing system boltage@ Rs. 14,50,000.00
SCHEDULE' A' PART-III (Solar water heater) M&L for complete servicing and repair of solar water heating system of any capacity, servicing and cleaning of all accessories and re-fixing in the same in position, testing complete all as directed by Engr-in-Charge. (Unsv accessories will be measured and paid seperately under respective items of Sch).
S&F solar collector glass suitable for existing solar water heating system complete all as specified and as directed.
Supply only Glycol for solar water heating system complete all as specified and as directed.
Repair to existing solar collector with copper brazing complete all as specified and as directed.
S&F heating element of capacity 3 KW, ISI marked suitable for existing solar water heating system complete all as specified and as directed.
S&F make up tank 50 Ltr capacity for existing solar water heating system complete all as specified and as directed.
S&F gasket and end joints suitable for existing solar water heating system complete all as specified and as directed.
SCHEDULE' A' PART-IV (Transformers) Repair/Maint of 250 KVA Transformers including dismantling of top cover with nuts & bolts and gasket sets, servicing & maintenance of LT & HT bushings incl replace of gusket sets with nuts, bolts and washer complete all as specified. Checking the dielectric strenght of transformer oil, moist presence of moisture, impurities etc and top up oil if required, providing and fixing of new gusket set, cable terminal lungs re-assemble the same after checking/rectification of whole parts of transformer loose conection etc and testiing with entire satisfaction and as per direction of EIC
Repair/Maint of Transformers of various capacity including painting and disconnecting from LT/HT line and reconnecting properly through Lugs and top up of transformer oil and other defects to be rectify as per direction of EIC
Earthing with G.I. earth plate 600 mm / 600 mm / 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/coke and salt complete all as specified.
supply fixing of lighting arrester three piece nonlinear resistor type for 11 KV overhead line 9 KV (rms) rating 5 KVA
Supply and fixing HT 11 KV, out door type gang operated air-break switch suitable for horizontal or vertical mounting fixed type complete with 9 insulators of rating upto 400 Amps
replacement of silica gel breather of 250 KVA/500KVA transformer
Supply and filling new transformer oil into conservator body/tank of the transformer all as specified and directed(Note:- the transformer oil shall be used for filling of main body tank for toping up as per requirement)
Repair Winding/rewinding with copper coil of transformer, replacement of all meter of various capacity as per directions of EIC Note :- 1. The contractor will attend any breakdown of stand by supply in any location whenever required , rectify the fault and restore the stand by supply with in two days after receipt of complaint. 2. The cost of transportation (to and from) for all kind of necessary eqpt /T&P shall be arranged /brought by contractor to complete the job at site and no extra cost shall be paid to the contractor to this effect.
SCHEDULE OF CREDIT Old U/S engine oil
Old U/S fuel gear pump,shaft fuel drive of any size and capacity
Old U/S Armature, solenoied sweitch, field coil of any size and capacity of selfstarter
Old U/S fuel feeding pump, shut down valve kit
Old u/s B Check kit
Old U/S radiator cap of any size
Old U/S v belt of any size & capacity
Old U/S fuel hose pipe flexible type of any size
Old U/S radiator hose pipe of any size
Old U/S battery of any size
Old U/S battery terminals
Old U/S 70 sqmm copper cable single core
Old U/S thermostate, RPM cable,water temp gauge, oil pressure gauge, oil temp meter, HCT Switch, LLOP Switch of any type
Old U/S battery charging set of any size
Old U/S AVR of any size
Old U/S MCCB of any size
old U/S fan with motor
Used Transformer Oil
breather
Old GOAB
Old earthing material
M/S HEMANT SINGH CONSTRUCTION (BID ID -3224406)
APS GROUP CONSTRUCTION (BID ID -3224079)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .