| 3 | L3₹1.2 Cr+₹8.0 L (7.34%)Admitted-Finance 880 1 SC ROAD BATOR HOWRAH 711104 | HOWRAH | HOWRAH | WEST BENGAL | 711104 | ₹1.2 Cr+₹8.0 L (7.34%) | L3 | Admitted-Finance |
| 4 | L4₹1.4 Cr+₹26.4 L (24.3%)Admitted-Finance NO 2 FIRST MAIN ROAD G K INDUSTRIAL ESTATE ALAPAKKAM CHENNAI KANCHIPURAM TAMIL NADU 600116 | THIRUVALLUR | TAMIL NADU | 600116 | ₹1.4 Cr+₹26.4 L (24.3%) | L4 | Admitted-Finance |
| 5 | L5₹1.9 Cr+₹80.3 L (74.0%)Admitted-Finance | ₹1.9 Cr+₹80.3 L (74.0%) | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | M/S KAY BEE SALES & SERVICES L1 | JANTA ENGINEERS AND CO IRON L6 | Discern Engineering Private Limited L3 | AGNICE FIRE PROTECTION PVT LTD L4 | TECHNICO INDIA PVT LTD L5 | CLASSIC SUPER CONSTRUCTION & DEVELOPERS PRIVATE LIMITED L2 |
|---|---|---|---|---|---|---|---|---|---|
| 1.00( A ) SUPPLY OF GOODS | |||||||||
| 2.00 | UL LISTED/ FM APPROVED horizontal split casing type electrical motor driven main fire pump of discharge capacity 2280LPM 70 Mtrs head with 2950 rpm UL Listed Motor of 55KW/ 2 Poles / 415 V / 50 Hz/ 3 Phase supply / Continuous duty with class ‘F’ insulation. Totally Enclosed Fan cooled in enclosure class IP-55 (Non-FLP). The pump and motor shall be mounted on a common platform. The pump shall be capable of discharging 150% rated discharge capacity at head not less than 65% of the rated head. The pump shall be supplied with auto air release valve/ pressure gauges at delivery and compound gauge at suction side (as per NFPA-20) auto air release valve and all accessories as per the technical specifications complete in all respect. | 1 | Set | 11,50,000 ₹11,50,000 | 10,00,000 ₹10,00,000 Lowest | 12,52,559 ₹12,52,559 | 10,41,619 ₹10,41,619 | 12,10,548 ₹12,10,548 | 13,29,926.02 ₹13,29,926.02 |
| 3.00 | UL LISTED/ FM APPROVED horizontal split casing type diesel engine driven back up fire pump of discharge capacity 2280LPM at 70 Mtrs head with 2100rpm FM Approved diesel engine 77 HP multi cylinder & heat exchange cooling type. The pump should be capable of discharging 150% rated discharge capacity at head not less than 65% of the rated head and shall have pressure gauges on delivery side & compound gauge on suction side as per (NFPA-20) design, auto air release valve . The pump and engine and the pump should be mounted on a common platform and with UL/FM controller with 02 nos. of Dry batteries of 12 Volt each, Wiring harness for the interconnection between engine & controller & battery cables. All other accessories and fittings as per the technical specifications complete in all respect. Additional accessories like 500 Ltr. Fuel tank with magnetic level indicator & oil level gauge. | 1 | Set | 19,70,000 ₹19,70,000 | 8,00,000 ₹8,00,000 Lowest | 22,29,096 ₹22,29,096 | 20,33,220 ₹20,33,220 | 21,48,832 ₹21,48,832 | 21,70,946.06 ₹21,70,946.06 |
| 4.00 | Vertical, inland type multistage electrical motor driven Jockey Pump having discharge capacity 180LPM at head 70 Mtrs. Coupled with a 4 KW motor of 2900 RPM 3 Phase 425 Volt 50 HZ. The pump and motor should be supplied mounted on a common platform and with all accessories as per the technical specifications complete in all respect. | 1 | set | 1,10,000 ₹1,10,000 Lowest | 3,00,000 ₹3,00,000 | 1,49,849 ₹1,49,849 | 1,60,549 ₹1,60,549 | 1,53,156 ₹1,53,156 | 2,94,001.54 ₹2,94,001.54 |
| 5.00 | Motor Control Centre Panel suitable for above mentioned Electric Main Pump UL listed & FM Approved & Jockey Pump (Motor Controller UL Listed / FM Approved & Jockey Controller CPRI approved or UL Listed. | 1 | Set | 6,63,000 ₹6,63,000 | 5,00,000 ₹5,00,000 Lowest | 5,34,629 ₹5,34,629 | 5,38,024 ₹5,38,024 | 9,50,589 ₹9,50,589 | 5,69,591.79 ₹5,69,591.79 |
| 6.00 | UL listed/ FM approved Water Flow meter of 750 USGPM 6" dia venture type. | 1 | Nos | 2,15,000 ₹2,15,000 | 1,00,000 ₹1,00,000 Lowest | 2,67,315 ₹2,67,315 | 2,23,190 ₹2,23,190 | 2,98,039 ₹2,98,039 | 2,50,587.21 ₹2,50,587.21 |
| 7.00 | UL listed/ FM approved Pressure Relief Valve Size 4" with Waste cone 4" x 6" with site glass. | 1 | Nos | 2,35,000 ₹2,35,000 | 50,000 ₹50,000 Lowest | 1,37,476 ₹1,37,476 | 65,527 ₹65,527 | 3,06,514 ₹3,06,514 | 1,97,503.39 ₹1,97,503.39 |
| 8.00 | Pressure gauge of 0-16 Kg/sq.cm range with cut-off bronze ball valves below of suitable size with all accessories. | 4 | Nos | 1,550 ₹6,200 Lowest | 15,000 ₹60,000 | 4,182 ₹16,728 | 2,860 ₹11,440 | 2,384 ₹9,536 | 3,357.4 ₹13,429.6 |
| 9.00C.I. Rising Spindle Sluice Valve as per ISI Mark with matching MS flanges, Pressure rating PN:16 | |||||||||
| 10.00 | a) 200 mm NB | 4 | Nos | 45,700 ₹1,82,800 | 1,00,000 ₹4,00,000 | 37,607 ₹1,50,428 | 48,482 ₹1,93,928 | 43,310 ₹1,73,240 | 31,316.79 ₹1,25,267.16 Lowest |
Tender Value
₹1.3 Cr
EMD Value
₹2.6 L
Closing Date
28 Jun 2022, 5:00 pmClosed
Sunit Lakra,EE(M),PPA
Sunit Lakra,EE(M),PPA
Supply, Installation, Testing and Commissioning of fixed high velocity water spray system for fire protection of two nos 20 MVA Power Transformers at MCHP
2022_MoS_692827_1
EM/MCHP- 22/2022
Open Tender
Machineries/ Mechanical Engg Items
Works
240 days
Paradip
Refer Tender Document and e-TCN
3 documents required · 3 mandatory
₹5,000
Yes
As per Tender Document and e-TCN
₹2.6 L
Yes
In the Conference Room
29 Nov 2022
3 Jun 2022
29 Jun 2022
3 Jun 2022
28 Jun 2022
3 Jun 2022
3 Jun 2022 - 7 Jun 2022
8 Jun 2022
Amount
( A ) SUPPLY OF GOODS
UL LISTED/ FM APPROVED horizontal split casing type electrical motor driven main fire pump of discharge capacity 2280LPM 70 Mtrs head with 2950 rpm UL Listed Motor of 55KW/ 2 Poles / 415 V / 50 Hz/ 3 Phase supply / Continuous duty with class ‘F’ insulation. Totally Enclosed Fan cooled in enclosure class IP-55 (Non-FLP). The pump and motor shall be mounted on a common platform. The pump shall be capable of discharging 150% rated discharge capacity at head not less than 65% of the rated head. The pump shall be supplied with auto air release valve/ pressure gauges at delivery and compound gauge at suction side (as per NFPA-20) auto air release valve and all accessories as per the technical specifications complete in all respect.
UL LISTED/ FM APPROVED horizontal split casing type diesel engine driven back up fire pump of discharge capacity 2280LPM at 70 Mtrs head with 2100rpm FM Approved diesel engine 77 HP multi cylinder & heat exchange cooling type. The pump should be capable of discharging 150% rated discharge capacity at head not less than 65% of the rated head and shall have pressure gauges on delivery side & compound gauge on suction side as per (NFPA-20) design, auto air release valve . The pump and engine and the pump should be mounted on a common platform and with UL/FM controller with 02 nos. of Dry batteries of 12 Volt each, Wiring harness for the interconnection between engine & controller & battery cables. All other accessories and fittings as per the technical specifications complete in all respect. Additional accessories like 500 Ltr. Fuel tank with magnetic level indicator & oil level gauge.
Vertical, inland type multistage electrical motor driven Jockey Pump having discharge capacity 180LPM at head 70 Mtrs. Coupled with a 4 KW motor of 2900 RPM 3 Phase 425 Volt 50 HZ. The pump and motor should be supplied mounted on a common platform and with all accessories as per the technical specifications complete in all respect.
Motor Control Centre Panel suitable for above mentioned Electric Main Pump UL listed & FM Approved & Jockey Pump (Motor Controller UL Listed / FM Approved & Jockey Controller CPRI approved or UL Listed.
UL listed/ FM approved Water Flow meter of 750 USGPM 6" dia venture type.
UL listed/ FM approved Pressure Relief Valve Size 4" with Waste cone 4" x 6" with site glass.
Pressure gauge of 0-16 Kg/sq.cm range with cut-off bronze ball valves below of suitable size with all accessories.
C.I. Rising Spindle Sluice Valve as per ISI Mark with matching MS flanges, Pressure rating PN:16
a) 200 mm NB
b) 150 mm NB
c) 100 mm NB
d) 50 mm NB
150 mm NRV 150 Pressure rating PN : 16
50 mm NRV 50 Pressure rating PN : 16
4 way Fire Inlet connection with 100mm NRV
Control & power cable as required for establishing automation of the pumping system including laying of power cable (4CX95sqmm Aluminium PVC armoured ) from source of power supply (SS#6) to motor control centre & internal wiring of pump hpuse.
1/2" Air Release Valve with cut-off ball valve 1/2"
Heavy grade M.S. ERW BLACK PIPE as per IS:1239 (FOR DOWN STREAM SIDE : PIPING INCLUDING FEED MAIN NOZZLE LOOP, QB DETECTOR LOOP & SUPPORT STAND PIPE FOR NOZZLE LOOP)
a) 200 mm NB
b) 150 mm NB
c) 100 mm NB
d) 80 mm NB
e) 65 mm NB
f) 25 mm NB
Structural Steels (Angle: 25x25 mm & 40x40 mm Channel : 50x100x50mm, Plate 12mm thick etc.) as required for making of supports to make the system complete.
Deluge Valve-A, 100 NB, Flanged to ANSI B16.1, UL Listed Wet pilot Basic Trim for DV-A with test & alarm, drain & drip valves, 100 NB (NTW), Water Motor Gong Bell-GA, Type-A, UL Listed & FM Approved
Sprinkler (QB detector) 68 Deg.C Standard Response Standard coverage 1/2" BSPT K 5.6 pendent Chrome Finish, UL Listed & FM Approved
High Velocity Water Spray Nozzle HV-AS, nickel chrome plated brass, 3/4" BSPT/NPT, K-factor & Spray angle , UL Listed
100 mm dial Pressure Gauge
C.I. butterfly Valve 100 mm NB
100 mm NB C.I. Y-strainer, complete with suitable matching flanges and accessories.
Hydrant Valve with SS Coupling
Hose Box for 2 Nos. 15 mtr. Long hose & 1 branch Pipe
15 mtr. Long RRL Hose with SS Coupling
SS Branch Pipe with nozzle (19 mm) as per IS:903
Initial Spares for the System as per scope of work.
Other left out materials
( B) CIVIL WORKS
Design & Construction of water tank (1,25,000 Litres Capacity) providing positive suction to the pump with supply of all materials and labours.
Design & Construction of Pump House with supply of all materials and labours.( Size:9MX7.2MX4.5M) as per scope of work.
Design & Construction of overflow sump tank ( drainage tank) for transformer with supply of all materials and labours.
( C ) INSTALLATION & COMMISSIONING PART.
UL LISTED/ FM APPROVED horizontal split casing type electrical motor driven main fire pump of discharge capacity 2280LPM 70 Mtrs head with 2950 rpm UL Listed Motor of 55KW/ 2 Poles / 415 V / 50 Hz/ 3 Phase supply / Continuous duty with class ‘F’ insulation. Totally Enclosed Fan cooled in enclosure class IP-55 (Non-FLP). The pump and motor shall be mounted on a common platform. The pump shall be capable of discharging 150% rated discharge capacity at head not less than 65% of the rated head. The pump shall be supplied with auto air release valve/ pressure gauges at delivery and compound gauge at suction side (as per NFPA-20) auto air release valve and all accessories as per the technical specifications complete in all respect.
UL LISTED/ FM APPROVED horizontal split casing type diesel engine driven back up fire pump of discharge capacity 2280LPM at 70 Mtrs head with 2100rpm FM Approved diesel engine 77 HP multi cylinder & heat exchange cooling type. The pump should be capable of discharging 150% rated discharge capacity at head not less than 65% of the rated head and shall have pressure gauges on delivery side & compound gauge on suction side as per (NFPA-20) design, auto air release valve . The pump and engine and the pump should be mounted on a common platform and with UL/FM controller with 02 nos. of Dry batteries of 12 Volt each, Wiring harness for the interconnection between engine & controller & battery cables. All other accessories and fittings as per the technical specifications complete in all respect. Additional accessories like 500 Ltr. Fuel tank with magnetic level indicator & oil level gauge.
Vertical, inland type multistage electrical motor driven Jockey Pump having discharge capacity 180LPM at head 70 Mtrs. Coupled with a 4 KW motor of 2900 RPM 3 Phase 425 Volt 50 HZ.
Motor Control Centre Panel suitable for above mentioned Electric Main Pump UL listed & FM Approved & Jockey Pump (Motor Controller UL Listed / FM Approved & Jockey Controller CPRI approved or UL Listed with 02 nos earthing suitable to the system.
UL listed/ FM approved Water Flow meter of 750 USGPM 6" dia venture type.
UL listed/ FM approved Pressure Relief Valve Size 4" with Waste cone 4" x 6" with site glass.
Pressure gauge of 0-16 Kg/sq.cm range with cut-off bronze ball valves below of suitable size with all accessories.
C.I. Rising Spindle Sluice Valve as per ISI Mark with matching MS flanges, Pressure rating PN:16
150 mm NRV 150 Pressure rating PN : 16
50 mm NRV 50 Pressure rating PN : 16
4 way Fire Inlet connection with 100mm NRV
Control & power cable as required for establishing automation of the pumping system including laying of power cable (4CX95sqmm Aluminium PVC armoured ) from source of power supply (SS#6) to motor control centre & internal wiring of pump hpuse.
1/2" Air Release Valve with cut-off ball valve 1/2"
Heavy grade M.S. ERW BLACK PIPE as per IS:1239 (FOR DOWN STREAM SIDE : PIPING INCLUDING FEED MAIN NOZZLE LOOP, QB DETECTOR LOOP & SUPPORT STAND PIPE FOR NOZZLE LOOP)
a) 200 mm NB
b) 150 mm NB
c) 100 mm NB
d) 80 mm NB
e) 65 mm NB
f) 25 mm NB
Structural Steels (Angle: 25x25 mm & 40x40 mm Channel : 50x100x50mm, Plate 12mm thick etc.) as required for making of supports to make the system complete.
Deluge Valve-A, 100 NB, Flanged to ANSI B16.1, UL Listed Wet pilot Basic Trim for DV-A with test & alarm, drain & drip valves, 100 NB (NTW), Water Motor Gong Bell-GA, Type-A, UL Listed & FM Approved
Sprinkler (QB detector) 68 Deg.C Standard Response Standard coverage 1/2" BSPT K 5.6 pendent Chrome Finish, UL Listed & FM Approved
High Velocity Water Spray Nozzle HV-AS, nickel chrome plated brass, 3/4" BSPT/NPT, K-factor & Spray angle , UL Listed
100 mm dial Pressure Gauge
C.I. butterfly Valve 100 mm NB
100 mm NB C.I. Y-strainer, complete with suitable matching flanges and accessories.
Hydrant Valve with SS Coupling
Hose Box for 2 Nos. 15 mtr. Long hose & 1 branch Pipe
15 mtr. Long RRL Hose with SS Coupling
SS Branch Pipe with nozzle (19 mm) as per IS:903
Installation of other left out materials.
Painting of all the pipe line with 2 coat primer & 2 coat Post Office Red Colour with supply of paints as required.
Testing & Commissioning of the System
CLASSIC SUPER CONSTRUCTION & DEVELOPERS PRIVATE LIMITED
Discern Engineering Private Limited
AGNICE FIRE PROTECTION PVT LTD
TECHNICO INDIA PVT LTD
JANTA ENGINEERS AND CO IRON
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .