| Sl No | Description | Qty | Unit | M/S JIWAN SINGH L2 | KRISHNA ENGINEERING ENTERPRISES L4 | M/S PARSHOTAM KUMAR GUPTA L5 | JAMWAL CONSTRUCTION CO L3 | NATIONAL TRADING COMPANY L1 |
|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply, installation, commissioning and testing of silent diesel engine generating set comprising of diesel engine- cooled (latest IS and CPCB- Norms) & alternator, of output capacity not less than 58.5 KVA at site (DG set to be installed at HAA 950m above MSL and capacity of DG set shall be selected, so as to deliver 58.5 KVA in all adverse conditions) 3 phase 4 wire, 415V, 50 Hz, 0.8pf at 1500 RPM, with control panel having all necessary switch gears for automatic starting on main failure (AMF panel), both coupled and aligned on a common base frame complete with standard accessories like MS Fuel tank (having the minimum fuel capacity for running of DG set continnously for 12 hours), AVM pads fitted on base frame, control panel with digital measurement devices, alongwith accoustic enclosure with the confirmation of latest BS/IS and complete in all respects including lubricating oil filled in engine, DG set manual comprising of following complete all as specified :- | 1 | Each | 10,20,555 ₹10,20,555 | 10,85,000 ₹10,85,000 | 11,50,000 ₹11,50,000 | 9,79,500 ₹9,79,500 | 9,24,000 ₹9,24,000 Lowest |
| 1.01Prime Mover :- Prime mover suitable for driving alternator 58.5 KVA capacity having the suitable BHP at 1500 RPM for rated output for alternator in accordance with latest BS/IS specification with electric starting device with all standard fittings and suitable capacity of lead acid maintenance free battery of 12 volts as per manfucaturer -01 nos with battery charger and engine over speed safety mechanism shall be incorporated. The engine shall be equipped with standard fittings as per manufacturer's recommendations. | ||||||||
| 1.02Engine Control Panel: (a) All relevant parameters shall be conventionally displayed on complete panel thereby providing easy monitoring of lub oil , pressure, coolant temperature, battery charging, ammeter, RPM , Hour meter and starting switch etc. generator set, all as per manufacturer's recommendation. (b) AMF panel with Bye Pass arrangement for Main and DG Both supply, internal wiring and power contactors suitable for 58.5 KVA generator set, all as per manufacturer's recommendation. Bye Pass arrangement Main & DG set suupply along with all the paramenters and accessories as per manufacturer recommendation and CPRI approved & as per relevant IS. | ||||||||
| 1.03Fuel tank: Fuel tank of 12 hours capacity will be installed as per the manufacturer's requirement including all necessary pipe connections from fuel tank to engine and over flow from engine to tank. | ||||||||
| 1.04Engine Alternator : Engine alternator of capacity 58.5 KVA output 3 phase 50 hz 415 Volts 4 wire AC suply 0.8 power factor at 1500 RPM self regulated self excised screen protected and drip type, insulation class "H" continously rated brush less type conforming to relevant BS/IS code as per current manufacturing schedule of standard manufacturer. Engine Alternator shall be mounted on specially designed base plate of rigid welded constructions with anti vibration pads. The DG set shall be placed on foundation including necessary civil works as per the manufacturer's recommendations/site requirement. The output of alternator not less than 58.5 KVA in all adverse conditions, as the DG set to be installed at HAA 950m above MSL. Note:- (a) The unit rate shall deemed to include the cost of diesel and lubrication required for testing and commissioning of DG set as per department procedure and shall be arranged by contractor.(b) Extension of exhaust pipe for DG set along with standard accessories like flange, nut bolts, asbestos rope etc. shall be provided by the contractor and the cost of the same shall be included in the unit rate quoted by contractor. (c) Cost of foundation and necessary civil works as per the manufacturer's recommendation/site requirement shall be included in the unit rate quoted by the contractor. | ||||||||
| 2.00 | Supply,installation commissioning and testing of silent diesel engine generating set enclosed in conopy comprising of diesel engine liquid- cooled (latest IS and CPCB- Norms) & alternator, of output capacity not less than 30 KVA at site (DG set to be installed at HAA 950m above MSL and capacity of DG set shall be selected, so as to deliver 30 KVA in all adverse conditions) 3 phase, 4 wire, 415V, 50 Hz, 0.8pf at 1500 RPM, with control panel having all necessary switch gears for automatic starting on main failure(AMF panel), both coupled and aligned on a cmmon base frame complete with standard accessories like MS fuel tank ( having the minimum fuel capacity for running of DG set continously for 12 hours), AVM Pads fitted on base frame, control panel with digital measurement devices, alongwith accoustic enclosure with the confirmation of latest BS/IS and complete in all respects including lubrication oil filled in engine, DG set manual comprising of following complete all as specified :- | 1 | Each | 7,95,555 ₹7,95,555 | 7,90,000 ₹7,90,000 | 8,50,000 ₹8,50,000 | 7,79,500 ₹7,79,500 | 5,90,000 ₹5,90,000 Lowest |
| 2.01Primer Mover :- Prime mover suitable for driving alternator 30 KVA capacity having the suitable BHP at 1500 RPM for rated output for alternator in accordance with latest BS/IS specification with electric starting device with all standard fittings and suitable capacity of lead acid maintenance free battery of 12 Volts as per manufacturer -01 nos with battery charger and engine over speed safety mechanism shall be incorporated. The engine shall be equipped with standard fittings as per manufacturer's recommendations. | ||||||||
| 2.02Engine Control Panel: (a) All relevant parameters shall be conventionally displayed on complete panel thereby providing easy monitoring of lub oil , pressure, coolant temperature, battery charging, ammeter, RPM , Hour meter and starting switch etc. generator set, all as per manufacturer's recommendation. (b) AMF panel with Bye Pass arrangement for Main and DG Both supply, internal wiring and power contractors suitable for 30 KVA generator set, all as per manufacturer's recommendation. Bye Pass arrangement Main & DG set suupply along with all the paramenters and accessories as per manufacturer recommendation and CPRI approved & as per relevant IS. | ||||||||
| 2.03Fuel tank: Fuel tank of 12 hours capacity will be installed as per the manufacturer's requirement including all necessary pipe connections from fuel tank to engine and over flow from engine to tank. | ||||||||
| 2.04Engine Alternator : Engine alternator of capacity 30 KVA output 3 phase 50 hz 415 Volts 4 wire AC supply 0.8 power factor at 1500 RPM self regulated self excised screen protected and drip type, insulation class 'H' continously rated brush less type conforming to relevant BS/IS code as per current manufacturing schedule of standard manufacturer. Engine Alternator shall be mounted on specially designed base plate of rigid welded constructions with anti vibration pads. The DG set shall be placed on foundation including necessary civil works as per the manufacturer's recommendations/site requirement. The output of alternator not less than 30KVA in all adverse conditions, as the DG set to be installed at HAA 950m above MSL. Note:- (a) The unit rate shall deemed to include the cost of diesel and lubrication required for testing and commissioning od DG set as per department procedure and shall be arranged by contractor. (b) Extension of exhaust pipe for DG set along with standard accessories like flange, nut bolts, asbestous rope etc. shall be provided by the contractor and the cost of the same shall be included in the unit rate quoted by contractor. (c) Cost of foundation and necessary civil works as per the manufacturer's recommendation/site requirement shall be included in the unit rate quoted by the contractor. | ||||||||
Tender Value
₹20.7 L
EMD Value
₹41,320
Closing Date
16 Dec 2025, 6:00 pmClosed
GE 881 EWS
GE 881 EWS, C/O 56 APO
PROVISION OF ONE 58.5 KVA AND ONE 30KVA DG SETS AT KOPRA II AND HAQ FORWARD POST UNDER GE 881 EWS
2025_MES_741364_1
GE/PNH-83/2025-26
Open Tender
Civil Works
Item Rate
180 days
GE 881 EWS, C/O 56 APO
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
Yes
GE 881 EWS
₹41,320
Yes
11 Feb 2026
24 Nov 2025
19 Dec 2025
24 Nov 2025
16 Dec 2025
9 Dec 2025
Amount
Prime Mover :- Prime mover suitable for driving alternator 58.5 KVA capacity having the suitable BHP at 1500 RPM for rated output for alternator in accordance with latest BS/IS specification with electric starting device with all standard fittings and suitable capacity of lead acid maintenance free battery of 12 volts as per manfucaturer -01 nos with battery charger and engine over speed safety mechanism shall be incorporated. The engine shall be equipped with standard fittings as per manufacturer's recommendations.
Engine Control Panel: (a) All relevant parameters shall be conventionally displayed on complete panel thereby providing easy monitoring of lub oil , pressure, coolant temperature, battery charging, ammeter, RPM , Hour meter and starting switch etc. generator set, all as per manufacturer's recommendation. (b) AMF panel with Bye Pass arrangement for Main and DG Both supply, internal wiring and power contactors suitable for 58.5 KVA generator set, all as per manufacturer's recommendation. Bye Pass arrangement Main & DG set suupply along with all the paramenters and accessories as per manufacturer recommendation and CPRI approved & as per relevant IS.
Fuel tank: Fuel tank of 12 hours capacity will be installed as per the manufacturer's requirement including all necessary pipe connections from fuel tank to engine and over flow from engine to tank.
Engine Alternator : Engine alternator of capacity 58.5 KVA output 3 phase 50 hz 415 Volts 4 wire AC suply 0.8 power factor at 1500 RPM self regulated self excised screen protected and drip type, insulation class "H" continously rated brush less type conforming to relevant BS/IS code as per current manufacturing schedule of standard manufacturer. Engine Alternator shall be mounted on specially designed base plate of rigid welded constructions with anti vibration pads. The DG set shall be placed on foundation including necessary civil works as per the manufacturer's recommendations/site requirement. The output of alternator not less than 58.5 KVA in all adverse conditions, as the DG set to be installed at HAA 950m above MSL. Note:- (a) The unit rate shall deemed to include the cost of diesel and lubrication required for testing and commissioning of DG set as per department procedure and shall be arranged by contractor.(b) Extension of exhaust pipe for DG set along with standard accessories like flange, nut bolts, asbestos rope etc. shall be provided by the contractor and the cost of the same shall be included in the unit rate quoted by contractor. (c) Cost of foundation and necessary civil works as per the manufacturer's recommendation/site requirement shall be included in the unit rate quoted by the contractor.
Primer Mover :- Prime mover suitable for driving alternator 30 KVA capacity having the suitable BHP at 1500 RPM for rated output for alternator in accordance with latest BS/IS specification with electric starting device with all standard fittings and suitable capacity of lead acid maintenance free battery of 12 Volts as per manufacturer -01 nos with battery charger and engine over speed safety mechanism shall be incorporated. The engine shall be equipped with standard fittings as per manufacturer's recommendations.
Engine Control Panel: (a) All relevant parameters shall be conventionally displayed on complete panel thereby providing easy monitoring of lub oil , pressure, coolant temperature, battery charging, ammeter, RPM , Hour meter and starting switch etc. generator set, all as per manufacturer's recommendation. (b) AMF panel with Bye Pass arrangement for Main and DG Both supply, internal wiring and power contractors suitable for 30 KVA generator set, all as per manufacturer's recommendation. Bye Pass arrangement Main & DG set suupply along with all the paramenters and accessories as per manufacturer recommendation and CPRI approved & as per relevant IS.
Fuel tank: Fuel tank of 12 hours capacity will be installed as per the manufacturer's requirement including all necessary pipe connections from fuel tank to engine and over flow from engine to tank.
Engine Alternator : Engine alternator of capacity 30 KVA output 3 phase 50 hz 415 Volts 4 wire AC supply 0.8 power factor at 1500 RPM self regulated self excised screen protected and drip type, insulation class 'H' continously rated brush less type conforming to relevant BS/IS code as per current manufacturing schedule of standard manufacturer. Engine Alternator shall be mounted on specially designed base plate of rigid welded constructions with anti vibration pads. The DG set shall be placed on foundation including necessary civil works as per the manufacturer's recommendations/site requirement. The output of alternator not less than 30KVA in all adverse conditions, as the DG set to be installed at HAA 950m above MSL. Note:- (a) The unit rate shall deemed to include the cost of diesel and lubrication required for testing and commissioning od DG set as per department procedure and shall be arranged by contractor. (b) Extension of exhaust pipe for DG set along with standard accessories like flange, nut bolts, asbestous rope etc. shall be provided by the contractor and the cost of the same shall be included in the unit rate quoted by contractor. (c) Cost of foundation and necessary civil works as per the manufacturer's recommendation/site requirement shall be included in the unit rate quoted by the contractor.
Supply,laying ,jointing and testing of Cable XLPE insulated screened PVC bedded,galvanized steel strip or wire armoured,electric power cables(heavy duty) 1100 volts grade with stranded aluminium conductor of size 35 sqmm 3.5 core, laid in trenches/ducts or fixed to poles/walls or laid under roads/paths/drains/culverts including cable gland of suitable sizes and aluminium lugs for connection,complete all as specified and directed.
All as per item No. 3 above but for size 10 sqmm 2 core all as specified and as directed.
Excavation in trenches not exc. 1.5 m wide and not exc. 1.5 in depth for foundation of poles, stay assy etc. and getting out in hard / dense soil complete all as specified and directed
Returning, filling in including spreading, leveling, watering and well ramming excavated soil in layers not exceeding 25 cm thick each, back in trenches after cables have been laid and tested complete all as specified and directed at site
Removing excavated material to a distance not exc. 50 mtr and depositing where directed at a level not exc. 1.5 mtr above the starting point of any type of soil complete all as specified and directed.
Supply and fixing DWC HDPE pipe for protection of power cable (orange in colour) of size 50 mm dia complete with fittings and including cutting, jointing and clamping all as specified and directed
GI pipe light grade 40 mm bore for cable protection fixed on poles or laid in trenches, under floor, ducts etc with fixing clamps, nuts bolts etc complete all as specified and directed.
Earthing complete with galvanized steel earth plate electrode 60cmx 60cmx6mm thick buried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to galvanized iron earth lead strip 32x6mm by means of bolts, nuts and washers of galvanized iron or steel, protected by GI light grade pipe 40mm bore including GI medium grade water pipe 15 mm bore with funnel and testing complete including earth work in any type of soil, PCC 1:2:4 type B-1 as in earthing pit and M30 concrete cover 55mm thick reinforced with XPM (weight not less than 4.0Kg/Sqm), including alternate layers of common salt, charcoal arround plate and testing on completion, all as specified and directed.
Onload changeover switch 415 V in sheet metal enclosures 4 pole of capacity 200 Amps complete all as specified and directed.
Supply and fixing LED flood light 70 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant with driver and lamp complete all as specified and directed.
Inverter LED batten light fitting 1x 20 W 4 feet long ,230 V , with all accessories, including lithium ion battery with charging time 8 to 10 hours and back up time upto 4 hours complete with all fittings and connecting up with PVC insulated and sheathed, 1100Volts grade, flexible, multistranded 1.0 sq mm copper conductor three core cable complete all as specified and as directed
M/S JIWAN SINGH (BID ID -3498186)
JAMWAL CONSTRUCTION CO (BID ID -3496381)
KRISHNA ENGINEERING ENTERPRISES (BID ID -3499865)
M/S PARSHOTAM KUMAR GUPTA (BID ID -3506166)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.36 MB
TENDER83.pdf
Tender Documents • 1.17 MB
BOQ_830148.xls
BOQ • 1.76 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .