Loading…
Loading…
Tender Value
₹47.9 L
EMD Value
₹96,000
Closing Date
11 Jul 2026, 6:00 pm7d left
GE Golconda
GE GOLCONDA LANGER HOUSE ROAD OPP MILITARY HOSPITAL HYDERABAD TELANGANA-500 008
SPL REPAIR/ REPLACEMENT TO OVERHEAD LT CABLE TO UG CABLE AT IB LINE UNDER GE GOLCONDA
2026_MES_773318_1
8139/E8
Open Tender
Civil Works
180 days
GE GOLCONDA
As per Tender
9 documents required · 9 mandatory
₹500
GE Golconda
₹96,000
Yes
18 Jun 2026
18 Jun 2026
14 Jul 2026
18 Jun 2026
11 Jul 2026
4 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Dismantling old ACSR conductor of any size from over head lines complete all as specified and directed | 3.75 | Qtl | - | - |
| 2 | Dismantling old Cross-arms of MS channel including clamps, nuts and bolts or angle sections etc. of any size from over head lines complete all as and directed | 1.42 | Qtl | - | - |
| 3 | Dismantling old insulators of any type and size from over head lines complete all as specified and directed | 80 | Each | - | - |
| 4 | Dismantling old service wire of any type and size from over head lines complete all as specified and directed | 2,400 | RM | - | - |
| 5 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size185 sq. mm 3.5 core in trenches/ fixed to walls/ poles etc. including taking out of existing cable complete all as specified and directed. | 500 | RM | - | - |
| 6 | All as per item No.5 but 120 Sqmm x 3.5 Core | 165 | RM | - | - |
| 7 | All as per item No.5 but 95 Sqmm x 3.5 Core | 1,030 | RM | - | - |
| 8 | All as per item No.5 but 25 Sqmm x 3.5 Core | 280 | RM | - | - |
| 9 | All as per item No.5 but 10 Sqmm x 2 Core | 4,800 | RM | - | - |
| 10 | Supply, install, testing and commissioning of new Out door LT feeder panel, factory fabricated, CPRI approved and tested , cubicle type, 3.15 mm thick CRCA sheet vermin proof with 3 phase and neutral Aluminium bus bar of current capacity 400 A of suitable size, phase and neutral colour coded with heat shrinkable PVC sleeves, with necessary supports, angle iron frame work and stand, front and rear opening double door locking arrangements and painting with one coat of red oxide primer and two coats of powder coated paint, suitable size of panel control copper wiring, accessories fitted on suitable insulator all housed in suitable bus bar chamber and fixing of digital Voltmeter, Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps (R,Y,B) along with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable cable glands etc. , including PCC foundation and necessary earth work complete all as specified and directed and consisting and including of the following :-
(a) 4 Pole MCCB 320 Amp 50 Hz 415 V with rupturing capacity 36 KA,Adjustable thermal & Magnetic setting(Incoming ) - 01
(b) 4 Pole MCCB 100A 50 Hz 415 V with rupturing capacity 25 KA,Adjustable thermal & Fixed Magnetic setting - 05 Nos ( 01 Stand by for Sub Panel)
(c) Three phase Digital voltmeter 0-500 Volts with selector switch - 01 Set
(d) Three phase digital Ammeter 0-500 Amps with selector switch and CTs - 01 Set
(e) Phase Indicating lamp LED type for Red, Yellow and Blue - 01 Set | 2 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.34 MB
BOQ_865901.xls
BOQ • 0.27 MB
8139Tender.pdf
Tender Documents • 0.59 MB
8139NIT.pdf
Additional Documents • 0.33 MB
Download all tender documents and submit your bid