Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹85.1 LAccepted-AOC COLABA MUMBAI | L1 | Accepted-AOC ACCEPTED | |
| 2 | L2₹99.3 L+₹7.8 L (8.50%)Rejected-Finance COLABA MUMBAI | YAVATMAL | MAHARASHTRA | 445001 | L2 | Rejected-Finance Being other then lowest | |
| 3 | L3₹1.2 Cr+₹31.0 L (33.9%)Rejected-Finance COLABA MUMBAI | L3 | Rejected-Finance Being other then lowest |
Tender Value
Refer Docs
EMD Value
₹1.8 L
Closing Date
25 Nov 2020, 6:00 pmClosed
CWE NW Mumbai
Commander Works Engineer NW Dr Homi Bhabha Road Navy Nagar ColabaMumbai 05
SPECIAL REPAIRS/REPLACMENT OF 04 NOS BER LIFTS OF DHANUSH AND BRISHAB 08 13 PASSENGERS INCLUDING COMPREHENSIVE MAINTENANCE OF 4 YEARS IF LIFT AT NAVY NAGAR COLABA MUMBAI UNDER GE NW NAVY NAGAR
2019_MES_294833_2
8167/CWE(NW)MUMBAI/E8
Open Tender
Electrical and Maintenance Works
Item Wise
275 days
GE (NW) Navy Nagar
Class B and above and category c ii
9 documents required · 9 mandatory
₹1,000
Yes
GE (NW) Navy Nagar
₹1.8 L
Yes
16 Dec 2020
21 Oct 2020
30 Nov 2020
21 Oct 2020
25 Nov 2020
11 Nov 2020
21 Oct 2020 - 10 Nov 2020
Amount
Dismantling the existing BER Lift of capacity 8 PS (544 Kgs) of any make complete with all accessories such as reduction gear assembly ,Traction machine, electric motor control panel, guide rails and cabins, landing door and car door wire rope etc serving G+14 upper floor installed in bldg at Navy Nagar complete all as specified and directed by Engineer-in-Charge Note :- Before carrying out dismantling work of a particular lift the contractor shall first produce the Order Copy of material required for installation of new lift after the contractor shall obtain permission from Engineer-in-charge to carryout dismantling of the existing lift in bldg nos Brishab & Dhanush.
Dismantling the existing BER Lift of capacity 13 PS (884 Kgs) of any make complete with all accessories such as reduction gear assembly ,Traction machine, electric motor control panel, guide rails and cabins, landing door and car door wire rope etc serving G+14 upper floor installed in bldg at Navy Nagar complete all as specified and directed by Engineer-in-Charge Note :- Before carrying out dismantling work of a particular lift the contractor shall first produce the order Copy of material required for installation of new lift after the contractor shall obtain permission from Engineer-in-charge to carryout dismantling of the existing lift in bldg nos Brishab & Dhanush.
Supply, install, testing & commissioning 13 Passengers(884Kgs) Lifts suitable to serve G+14 upper floors in bldgs Brisabh & Dhanush (13 PS) suitable to serve G+14 upper floors with AC variable voltage & variable frequency (VVVF drive) drive with closed loop complete with all standard accessories, simplex down collective operation with or without attendent stainless steel doors with hairline finish, automatic rescue device (ARD) system, full beam infra red sensor in full height of door & built in announcing system without hand set (02 Nos, one each for car & ground floor and with one set in machine room ) all as specified below in Bldg No Brisabh & Dhanush Group-I make :- (i) M/s Kone India (ii) M/s Schneider India Pvt Ltd (iii) M/s Kinetic Hyundai Elevator and Movement Technologic Ltd (iv) M/s Hitachi Lifts India Pvt Ltd (v) M/s Mistubishi Elevators Ind Pvt Ltd (vi) M/s OITS Elevator Company Ltd (vii) M/s Fujitech India Pvt Ltd Group-II make :- (i) M/s Jonnson lift Pvt Ltd (ii) M/s Thyssenkrupp Elevator India Pvt Ltd (iii) M/s Omega Elevators (iv) M/s Escon Elevators Pvt Ltd (v) M/s LT Elevators Pvt Ltd (vii) M/s IES Elevators (viii) M/s Monarch Enterprises
(a) Type of Lifts : 13 Passengers. (b) Load capacity : 884 Kgs. (c) Speed : 1.75 mtr/sec with single speed motor. (d) Power Supply : 400 volts, 3 phase AC, 50 Hz. (e) Type of Drive : AC variable voltage & variable frequency drive. (f) Type of Machine : Gearless & directly coupled Horizantal traction machine. (g) Car size (Inside) : Not less than 2.20 Sqm and allowed tolerence as per IS : 14665. (h) Car door and landing door at all floor : Automatic center opening with VVVF door drive, opening size 900mm x 2000mm, sliding type, fabricated bystainless steel sheet not less than 18 gauge having hairline finish (N-304). (j) Car enclosure : Standard manufacturing with MS frame & stainless steel sheet not less than 18 gaze with hair line finish (N-304), having stainless steel false ceiling with hairline finish, internal lighting arrangement with LED light fitting complete, internal vantilation system provided with concealed arial flow/cross flow fan with auto cut of system and stainless steel grill/wire mesh for protection. (k) Terminal buffers : Metal special spring buffers as per manufacturer specification. (l) Door opening (Inside) : Protected by automatic centre opening stainless steel doors with hairline finish doors with clear opening size 900 x 2000mm. (n) Clear Hoist size : As per appendix enclosed ( Tenderer to inspect the same at site before quoting) (m) Car & counter weight Guide : Guide rails of `T' Section Mild steel as per OEM design counter weight shall be cast iron as recommended by OEM. (o) Flooring : Aluminum chequered plate 5mm thick.
(P) Signals :- (i) Combined luminous hall buttons with digital hall position indicators at all floor. (ii) Vaccum filled display (VFD) for car position indicator of stainless steel and overload warning in car. (iii) One No car operating panel with Luminious buttons in car (stainless steel) (iv) Car direction indicator in car & Landing. (v) Battery operated alarm bell & emergency light (rechargeable) along with suitable maintenance free battery. (vi) Overload warning feature in car cabine (display and announcing type both). (vii) Fireman’s switch one No per lift to be installed at ground Floor near landing door. (viii) All signal fixture & car operating panel on stainless steel face plate with hair line finish. (ix) Full beam infra red sensor safety edge of door for entire height. (x) Built in announcing system without hand set 02 Nos.( One each in car& near ground floor landing door & one announcing system with hand set in machine room). (xi) The interior of the car should be provided with a device that audibly indicates the floor position of lift car has reached and indicates that car entrance/exit door is open or closed. (xii) stainless steel hand rail 40 mm dia all around 3 inside the car cabin. (p) Stops & Opening : 15-15 ( All opening on same side). (q) Safety device : As per OEM design Automatic rescue device (ARD) /automatic landing device to be operating with maintenance free batteries for landing as specified.Make: As per OEM specifications and approved drawing and design. Make :-Thyessenkrupp/Johnson /Schindler/OTIS/ESCON/Monarch
(r) Operation : Simplex full collective, automatic operation with/without attendant. (s) Two seperate earthing complete all as specified in SSR Part-I,Plate No 3 and With GI Plate 600x600x6mm chamber all as specified in SSR Part-I Using GI Strip 32x6mm from ground to lift machine room to be terminated to the control panel, machine and other equipement installed in machine room. (t) Machine Room : Located above the hoist way. (Details as per appendix attached, however tenderer to inspect the sight before quoting). (u) Hoist-Way Constn : Existing at site, details as per Appendix attached however tenderer to inspect the site before quoting. (v) Regenerating AC- VVVF drive shall be of make:Yaskawa/Mitsubish uji/OTIS/Schindler /ESCON/ Monarch (w) Control system shall be enclosed loop type. (x) Door shall have AC-VVVFcontroled close loop operated. (za) Civil work : Necessary civil work such as making good disturbed surfaces, modification to landing space to suit to car size,necessary foundation to machine and one coat of white wash to lift shaft etc. (y) Face plate shape shall be rectangular and stainlees steel in hairline finish. (z) counter weight shall be of cast iron as recommended by OEM. (zb) One number electrically operated siren, operating voltage 240 volts having audible range of 0.3 Km including independent switch inside of car cabin and connecting cables from car cabin to machine room. The siren shall be installed at appropriate place. (i) One toughened looking mirror(of best quality) of size 1500mmx1000mmx4mm thick with silvered sheet frame. (ii) One number LED light to be connected with UPS for emergency lighting purpose.
Supply, install, testing & commissioning 8 Passengers(544Kgs) Lifts suitable to serve G+14 upper floors in bldgs Brisabh & Dhanush (8 PS) suitable to serve G+14 upper floors with AC variable voltage & variable frequency (VVVF drive) drive with closed loop complete with all standard accessories, simplex down collective operation with or without attendent stainless steel doors with hairline finish, automatic rescue device (ARD) system, full beam infra red sensor in full height of door & built in announcing system without hand set (02 Nos, one each for car & ground floor and with one set in machine room ) all as specified below in Bldg No Brisabh & Dhanush. Group-II make :- (i) M/s Kone India (ii) M/s Schneider India Pvt Ltd (iii) M/s Kinetic Hyundai Elevator and Movement Technologic Ltd (iv) M/s Hitachi Lifts India Pvt Ltd (v) M/s Mistubishi Elevators Ind Pvt Ltd (vi) M/s OITS Elevator Company Ltd (vii) M/s Fujitech India Pvt Ltd Group-II make :- (i) M/s Jonnson lift Pvt Ltd (ii) M/s Thyssenkrupp Elevator India Pvt Ltd (iii) M/s Omega Elevators (iv) M/s Escon Elevators Pvt Ltd (v) M/s LT Elevators Pvt Ltd (vii) M/s IES Elevators (viii) M/s Monarch Enterprises
(a) Type of Lifts : 8 Passengers. (b) Load capacity : 544 Kgs. (c) Speed : 1.75 mtr/sec with single speed motor. (d) Power Supply : 400 volts, 3 phase AC, 50 Hz. (e) Type of Drive : AC variable voltage & variable frequency drive. (f) Type of Machine : Gearless & directly coupled Horizantal traction machine. (g) Car size (Inside) : Not less than 2.20 Sqm and allowed tolerence as per IS : 14665. (h) Car door and landing door at all floor : Automatic center opening with VVVF door drive, opening size 800mm x 2000mm, sliding type, fabricated bystainless steel sheet not less than 18 gauge having hairline finish (N-304). (j) Car enclosure : Standard manufacturing with MS frame & stainless steel sheet not less than 18 gaze with hair line finish (N-304), having stainless steel false ceiling with hairline finish, internal lighting arrangement with LED light fitting complete, internal vantilation system provided with concealed arial flow/cross flow fan with auto cut of system and stainless steel grill/wire mesh for protection. (k) Terminal buffers : Metal special spring buffers as per manufacturer specification. (l) Door opening (Inside) : Protected by automatic centre opening stainless steel doors with hairline finish doors with clear opening size 800 x 2000mm. (m) Car & counter weight Guide : Guide rails of `T' Section Mild steel as per OEM design counter weight shall be cast iron as recommended by OEM. (n) Clear Hoist size : As per appendix enclosed ( Tenderer to inspect the same at site before quoting) (o) Flooring : Aluminum chequered plate 5mm thick.
(P) Signals :- (i) Combined luminous hall buttons with digital hall position indicators at all floor. (ii) Vaccum filled display (VFD) for car position indicator of stainless steel and overload warning in car. (iii) One No car operating panel with Luminious buttons in car (stainless steel). (iv) Car direction indicator in car & Landing. (v) Battery operated alarm bell & emergency light (rechargeable) along with suitable maintenance free battery. (vi) Overload warning feature in car cabine (display and announcing type both). (vii) Fireman’s switch one No per lift to be installed at ground Floor near landing door. (viii) All signal fixture & car operating panel on stainless steel face plate with hair line finish. (ix) Full beam infra red sensor safety edge of door for entire height. (x) Built in announcing system without hand set 02 Nos.( One each in car& near ground floor landing door & one announcing system with hand set in machine room). (xi) The interior of the car should be provided with a device that audibly indicates the floor position of lift car has reached and indicates that car entrance/exit door is open or closed. (xii) stainless steel hand rail 40 mm dia all around 3 inside the car cabin. (p) Stops & Opening : 15-15 ( All opening on same side). (q) Safety device : As per OEM design Automatic rescue device (ARD) /automatic landing device to be operating with maintenance free batteries for landing as specified.Make: As per OEM specifications and approved drawing and design. Make :-Thyessenkrupp/Johnson /Schindler/OTIS/ESCON/Monarch
(r) Operation : Simplex full collective, automatic operation with/without attendant. (s) Two seperate earthing complete all as specified in SSR Part-I,Plate No 3 and With GI Plate 600x600x6mm chamber all as specified in SSR Part-I Using GI Strip 32x6mm from ground to lift machine room to be terminated to the control panel, machine and other equipement installed in machine room. (t) Machine Room : Located above the hoist way. (Details as per appendix attached, however tenderer to inspect the sight before quoting). (u) Hoist-Way Constn : Existing at site, details as per Appendix attached however tenderer to inspect the site before quoting. (v) Regenerating AC- VVVF drive shall be of make as prescribed by OEM (w) Control system shall be enclosed loop type. (x) Door shall have AC-VVVFcontroled close loop operated. (y) Face plate shape shall be rectangular and stainlees steel in hairline finish. (z) counter weight shall be of cost iron as recommended by OEM. (za) Civil work : Necessary civil work such as making good disturbed surfaces, modification to landing space to suit to car size,necessary foundation to machine and one coat of white wash to lift shaft etc. (zb) One number electrically operated siren, operating voltage 240 volts having audible range of 0.3 Km including independent switch inside of car cabin and connecting cables from car cabin to machine room. The siren shall be installed at appropriate place. (i) One toughened looking mirror(of best quality) of size 1500mmx1000mmx4mm thick with silvered sheet frame. (ii) One number LED light to be connected with UPS for emergency lighting purpose.
Dismantling and taking out old archtrave from landing door complete and disposing of the same to outside MD Land complete all as specified and directed by Engineer - in - charge.
Material & labour for 18mm thick mirror polished black granite slab, machine cut mirror polished cladding with chamfered/rounded edges approved decorative design including necessery PCC work granite slab & jointing in cement slurry and pointed in white cement mixed with pigement to match with shade of granite for lifts architrave at all floors complete all as specified and directed by Engineer-in-Charge
Comprehensive maintenance and repair of fully automatic electrically operated passenger lifts of any make and installed capacity against Sch'A' Item 3 with a carrying capacity of 13 passenger (884 Kg) to serve 15th floor (G+14 floors) with a speed of 1.75 mtr/sec with gearless permanent magnet type single speed motor & AC variable voltage and variable frequency(VVVF) control automatic leveling device to bring the lift car to exact landing level.Simplex automatic operation with or without attendent including power operated,center opening stainless steel sliding door, Automatic rescue device ( ARD) system full beam infra red sensor in full height of door & built in announcing system without hand set ( 02 Nos, one each in car & near ground floor landing door) landing door with stainless steel hair line finish & indicators at each floor,total 02 Nos Lifts in bldg No Brisabh & Dhanush G+14 storey for four years all days including Sunday and holiday after expirey of defect liability period as shown below and all as speicified and directed by GE. Note :- Contractor shall carryout comprehensive maintenance( routine maintenance, daily, weekly, monthly, quarterly, half yearly and yearly) as per attached performa and maintain all the lifts in serviceable condition 24 hrs x 365 days with out any extra cost.
(a) First Year after expiry of defect liability period
(b) Second Year after expiry of defect liability period
(c) Third Year after expiry of defect liability period
(d) Fourth Year after expiry of defect liability period
Comprehensive maintenance and repair of fully automatic electrically operated passenger lifts of any make and installed capacity against Sch'A' Item 7 with a carrying capacity of 8 passenger (544 Kg) to serve 15th floor (G+14 floors) with a speed of 1.75 mtr/sec with gearless permanent magnet type single speed motor & AC variable voltage and variable frequency(VVVF) control automatic leveling device to bring the lift car to exact landing level.Simplex automatic operation with or without attendent including power operated,center opening stainless steel sliding door, Automatic rescue device ( ARD) system full beam infra red sensor in full height of door & built in announcing system without hand set ( 02 Nos, one each in car & near ground floor landing door) landing door with stainless steel hair line finish & indicators at each floor,total 02 Nos Lifts in bldg No Brisabh & Dhanush G+14 storey for four years all days including Sunday and holiday after expirey of defect liability period as shown below and all as speicified and directed by GE. Note :- Contractor shall carryout comprehensive maintenance( routine maintenance, daily, weekly, monthly, quarterly, half yearly and yearly) as per attached performa and maintain all the lifts in serviceable condition 24 hrs x 365 days with out any extra cost.
(a) First Year after expiry of defect liability period
(b) Second Year after expiry of defect liability period
(c) Third Year after expiry of defect liability period
(d) Fourth Year after expiry of defect liability period
Escon Elevators Pvt Ltd
Veer High Tech Solution
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .