Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Admitted-Finance 135 CHAKRANA TIWARI CHAKA NAINI PRAYAGRAJ 211008 UTTAR PRADESH | PRAYAGRAJ | UTTAR PRADESH | 211008 | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹30,000
Closing Date
21 Jul 2022, 4:00 pmClosed
Executive Engineer
Electric Division JPDCL Udhampur
Augmentation of substation of various capacities
2022_PDD_176393_1
ED/UDH/55 of 2022-23, dt 30-06-2022
Open Tender
Electrical Works
Turn-key
30 days
In different location of Udhampur District
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
Executive Engineer Electric Division JPDCLUdhampur
₹30,000
16 Sept 2022
1 Jul 2022
23 Jul 2022
1 Jul 2022
21 Jul 2022
1 Jul 2022
1 Jul 2022 - 8 Jul 2022
Amount
SUPPLY, ERECTION, TESTING & COMMISSIONING FOR Augmentation of 25KVA to 63 KVA SUB STATION (On partial Turn Key basis)
63 KVA 11/0.433 KV, 3 Phase Distribution Transformer with Bi-mettalic Terminal Connectors Energy Level-2 Alluminum wound with LV Cable Box Having detachable Aluminium Gland plate (Transformer shall be provided by the Department)
95 mm sq single phase cable 1.1kv grade pvc insulated Aluminium stranded conductor FRLS type including thimbling
GI Channel / Angle including clamps
LT Distribution Box for 63 KVA DTR with with MCCB for incomer & Switch Fuse Units for Outgoing Circuits.
Earthing of Sub-Station- Excavation of Earth pit of Dia 60 mm & depth 3000 mm, installation of earthing pipe of 40 mm Normal bore & 4 mm wall thickness & length 2.5 mtr long as per IS 1239, GI Strip for neutral earthing of size 75 mm x 100mm & 50 mm x 6 mm for connection of transformer body, GO set & lightening Arrestor as per IS 2629/85, GI nuts & earth Chamber with RCC Slab cover.
11 KV GO AB Switch, 3- Phase, 3 Pole 200 Amp. Vertical type
11KV Horn gap fuse set 3-phase 200 Amp.
Gapless Surge Arrestor ,9KV, 10 KA, LA with polymer housing, station type
9 mtr Long Pole (ST-410 SP33) (Poles shall be provided by the Department)
Cement bottoming 1:2:4 Mix as per REC Standards 0.5 cum /pole
Painting of ST poles with one coat of red oxide and two coats of Al Paint
Danger Plate with clamp
Dismantling, loading, carriage back of 25KVA X-mer and allied material (write back) to Divisional store Udhampur
Description of Work / Item(s)
Amount
SUPPLY, ERECTION, TESTING & COMMISSIONING FOR Augmentation of 63KVA to 100 KVA SUB STATION (On partial Turn Key basis)
100 KVA 11/0.433 KV, 3 Phase Distribution Transformer with Bi-mettalic Terminal Connectors Energy Level-2 Alluminum wound with LV Cable Box Having detachable Aluminium Gland plate . (Transformer shall be provided by the Department)
120 mm sq single phase cable 1.1KV grade pvc insulated Aluminium stranded conductor FRLS type including thimbling
GI Channel / Angle including clamps
LT Distribution Box for 100 KVA DTR with with MCCB for incomer & Switch Fuse Units for Outgoing Circuits.
Earthing of Sub-Station- Excavation of Earth pit of Dia 60 mm & depth 3000 mm, installation of earthing pipe of 40 mm Normal bore & 4 mm wall thickness & length 2.5 mtr long as per IS 1239, GI Strip for neutral earthing of size 75 mm x 100mm & 50 mm x 6 mm for connection of transformer body, GO set & lightening Arrestor as per IS 2629/85, GI nuts & earth Chamber with RCC Slab cover.
11 KV GO AB Switch, 3- Phase, 3 Pole 200 Amp. Vertical type
11KV Horn Gap fuse set 3-phase 200 Amp.
9 mtr Long Pole (ST-410 SP33) (Poles shall be provided by the Department)
Painting of ST poles with one coat of red oxide and two coats of Al Paint
Danger Plate with clamp
Cement bottoming 1:2:4 Mix as per REC Standards 0.5 cum /pole
Gapless Surge Arrestor, 9 KV , 10 KA, LA with polymer housing Stn. type
Dismantling, loading, carriage back of 63KVA X-mer and allied material (write back) to Divisional store Udhampur
Description of Work / Item(s)
Amount
SUPPLY, ERECTION, TESTING & COMMISSIONING FOR Augmentation of 100KVA to 250 KVA SUB STATION (On partial Turn Key basis)
250 KVA 11/0.433 KV, 3 Phase Distribution Transformer with Bi-mettalic Terminal Connectors Energy Level-2 Copper wound with LV Cable Box Having detachable Aluminium Gland plate (Transformer shall be provided by the Department)
GI Channel / Angle including clamps
300 mm sq single phase cable 1.1KV grade pvc insulated Aluminium stranded conductor FRLS type including thimbling
LT Distribution Box for 250 KVA DTR with with MCCB for incomer & Switch Fuse Units for Outgoing TWO Circuits.
Earthing of Sub-Station- Excavation of Earth pit of Dia 60 mm & depth 3000 mm, installation of earthing pipe of 40 mm Normal bore & 4 mm wall thickness & length 2.5 mtr long as per IS 1239, GI Strip for neutral earthing of size 75 mm x 100mm & 50 mm x 6 mm for connection of transformer body, GO set & lightening Arrestor as per IS 2629/85, GI nuts & earth Chamber made of with RCC Slab cover.
11 KV GO AB Switch, 3- Phase, 3 Pole 200 Amp. Vertical type
11KV Horn Gap fuse set 3-phase 200 Amp.
9 mtr Long Pole (ST-410 SP33) (Poles shall be provided by the Department)
Painting of ST poles with one coat of red oxide and two coats of Al Paint
Danger Plate with clamp
Cement bottoming 1:2:4 Mix as per REC Standards .5 cum /pole
Gapless Surge Arrestor, 9 KV , 10 KA, LA with polymer housing Stn. type
Dismantling, loading, carriage back of 100KVA X-mer and allied material (write back) to Divisional store Udhampur
Description of Work / Item(s)
Amount
SUPPLY, ERECTION, TESTING & COMMISSIONING FOR Augmentation of 250KVA to 400 KVA SUB STATION On partial Turn Key basis
400 KVA 11/0.433 KV, 3 Phase Distribution Transformer with Bi-mettalic Terminal Connectors Energy Level-2 Copper wound with LV Cable Box Having detachable Aluminium Gland plate. (Transformer shall be provided by the Department)
400 mm sq single phase cable 1.1KV grade PVC insulated Aluminium stranded conductor FRLS type including thimbling
GI Channel / Angle including clamps
LT Distribution Box for 400 KVA DTR with with MCCB for incomer & Switch Fuse Units for Outgoing two Circuits.
Earthing of Sub-Station- Excavation of Earth pit of Dia 60 mm & depth 3000 mm, installation of earthing pipe of 40 mm Normal bore & 4 mm wall thickness & length 2.5 mtr long as per IS 1239, GI Strip for neutral earthing of size 75 mm x 100mm & 50 mm x 6 mm for connection of transformer body, GO set & lightening Arrestor as per IS 2629/85, GI nuts & earth Chamber with RCC Slab cover.
11 KV GO AB Switch, 3- Phase, 3 Pole 200 Amp. Vertical type
Gapless Surge Arrestor, 9 KV, 10 KA, LA with polymer housing Stn. type
11KV Horngap fuse set 3-phase 200 Amp.
9 mtr Long Pole (ST-410 SP33) (Poles shall be provided by the Department)
Painting of ST poles with one coat of red oxide and two coats of Al Paint
Danger Plate with clamp
Cement Concerete bed size 2.5X2.5X1.96=12.25 cum
Cement bottoming 1:2:4 Mix as per REC Standards 0.5 cum /pole
Dismantling, loading, carriage back of 250KVA X-mer and allied material (write back) to Divisional store Udhampur
Description of Work / Item(s)
Amount
SUPPLY, ERECTION, TESTING & COMMISSIONING FOR Augmentation of 400KVA to 630 KVA SUB STATION On partial Turn Key basis
630 KVA 11/0.433 KV, 3 Phase Distribution Transformer with Bi-mettalic Terminal Connectors Energy Level-2 Copper wound with LV Cable Box Having detachable Aluminium Gland plate (Transformer shall be provided by the Department)
GI Channel / Angle including clamps
630 mm sq single phase cable 1.1KV grade PVC insulated Aluminium stranded conductor FRLS type including thiimbling
LT Distribution Box for 630 KVA DTR with with MCCB for incomer & Switch Fuse Units for Outgoing Circuits.
Earthing of Sub-Station- Excavation of Earth pit of Dia 60 mm & depth 3000 mm, installation of earthing pipe of 40 mm Normal bore & 4 mm wall thickness & length 2.5 mtr long as per IS 1239, GI Strip for neutral earthing of size 75 mm x 100mm & 50 mm x 6 mm for connection of transformer body, GO set & lightening Arrestor as per IS 2629/85, GI nuts & earth Chamber with RCC Slab cover.
11 KV GO AB Switch, 3- Phase, 3 Pole 200 Amp. Vertical type
11KV Horngap fuse set 3-phase 200 Amp.
9 mtr Long Pole (ST-410 SP33) (Poles shall be provided by the Department)
Gapless Surge Arrestor, 9 KV , 10 KA, LA with polymer housing Stn. type
Painting of ST poles with one coat of red oxide and two coats of Al Paint
Danger Plate with clamp
Cement bottoming 1:2:4 Mix as per REC Standards 0.5 cum /pole
Cement Concerete bed size 2.5X2.5X1.96=13.45 cum
Dismantling, loading, carriage back of 400KVA X-mer and allied material (write back) to Divisional store Udhampur
M R ENGINEERS & TRADERS
ADITYA SHARMA
M/s R.S CONSTRUCTIONS
vijay builders
M R ENGINEERS & TRADERS
ADITYA SHARMA
vijay builders
M/s R.S CONSTRUCTIONS
M R ENGINEERS & TRADERS
AJAY KAPOOR
ADITYA SHARMA
M/s R.S CONSTRUCTIONS
M R ENGINEERS & TRADERS
AJAY KAPOOR
ADITYA SHARMA
M/s R.S CONSTRUCTIONS
AJAY KAPOOR
M R ENGINEERS & TRADERS
ADITYA SHARMA
M/s R.S CONSTRUCTIONS
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .