Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Infra Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 154 A BARASIROHI NEAR IIT KANPUR KALYANPUR KANPUR NAGAR UTTAR PRADESH 208016 | KANPUR NAGAR | UTTAR PRADESH | 208016 | Admitted-Finance |
| 2 | Admitted-Finance 67D EXECUTIVE PO IZZAT NAGAR SUNCITY VISTAR BAREILLY UTTAR PRADESH 243122 | BAREILLY | UTTAR PRADESH | 243122 | Admitted-Finance |
| 3 | Admitted-Finance 98 PANIYARE PURWA MAKRAND NAGAR SARAIMEERA KANNAUJ KANNAUJ UTTAR PRADESH 209726 | KANNAUJ | UTTAR PRADESH | 209726 | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹9,000
Closing Date
5 Jan 2024, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE ETC Shahjahanpur
Electy. Trans. Circle Shahjahanpur
Work
2023_UPTCL_871961_1
31 ETC(S)/2023-24
Open Tender
Electrical Works
Fixed-rate
60 days
Shahjahanpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
A/c No. 0423002100107147 IFSC Code No. PUNB0042300
₹9,000
16 Jan 2024
18 Dec 2023
6 Jan 2024
18 Dec 2023
5 Jan 2024
18 Dec 2023
18 Dec 2023 - 5 Jan 2024
Amount
Bay Integration work of 02nos. 220 KV Bay ie., 220 kV Hardoi bay and 160 MVA T/F II bay in existing busbar Protection scheme Work Includes: A) Adding data of 02 nos. Bays to Busbar Protection relay provided by UPPTCL. B) Re-configuration work of Busbar Protection relay as per substation requirement. C) Wiring work of 02 Bays from CT, Breaker. Isolators and C&R Pannel to relay. D) Providing all yard status to the relay like: Breaker, Isolator and CT of 2 nos bay ie., 220 kV Hardoi bay and 160 MVA T/F II bay
Opening of trench covers, laying termination and dressing of control cable on the cable racks in trenches from Bus Bar Protection Pannel to various equipments of 2 nos bay ie., 220 kV Hardoi bay and 160 MVA T/F II bay including shifting of cable drums from store to switcyard & shifting Back the Balance Cables to stores again placing back the opened trench covers.
2CX2.5 Sq. mm.
4CX2.5 Sq. mm.
6CX2.5 Sq. mm.
Re-configuration work of Busbar Protection relay as per substation requirement. Work includes A) Checking and rectification of Wiring work of 10 nos Bays ie 220 kV Azizpur Bay, 220 kV Gola bay,200 MVA T/F bay, 220 kV TBC Bay, 160 MVA T/F I bay, 220 kV Faridpur bay, 220 kV Roza ckt I, 220 kV Roza ckt II bay, 220 kV PGCIL bay, 220 kV Bus coupler bay from CT, Breaker. Isolators and C&R Pannel to relay. D) Providing all yard status to the relay like: Breaker, Isolator and CT. E) Testing to Busbar Protection Scheme. F) Checking stability of relay after rectification of defects of 10 bays and integration of 2 nos. Bays. G) Analog status of all 220 KV Bays. H) Tripping Test of all 220 KV Bays through Busbar Protection Scheme.
Opening of trench covers checking of damaged cables and , laying termination and dressing of control cable on the cable racks in trenches from Bus Bar Protection Pannel to various equipments of 10 bays ie 220 kV Azizpur Bay, 220 kV Gola bay,200 MVA T/F bay, 220 kV TBC Bay, 160 MVA T/F I bay, 220 kV Faridpur bay, 220 kV Roza ckt I, 220 kV Roza ckt II bay, 220 kV PGCIL bay, 220 kV Bus coupler bay including shifting of cable drums from store to switcyard & shifting Back the Balance Cables to stores again placing back the opened trench covers.
2CX2.5 Sq. mm.
4CX2.5 Sq. mm.
6CX2.5 Sq. mm.
Work Includes: A) Flashing of relays card to remove the errors in the Busbar Protection relay or providing a new-card if the old card cannot be rectified. B) Upgrading the Busbar Protection Relay with latest version if required. C) Checking healthhiess of the bay.
Providing all digital data of existing 12 Bays to the relay which is not availiable in the relay. Rectification of all yard issues Breaker and isolators status which includes providing of spare parts & Rectification work of defective isolator switches. and (metering) related to Busbar relay. Checking healthiness of all yard wiring, status. metering and tripping contacts.
ELECTRO POWER SERVICES AND SOLUTIONS
EMC Associates
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .