Clause Regarding GST: (a) All the Bidders/tenderers should ensure that they are GST Compliant and their quoted tax Structure are as per GST LAW.(b) Tenderer Should Furnish their GSTIN numbers representing the States in Which they are registered GST, along with address of Registered Office.(c)The Contract is under GST Act and rules as applicable time to time.
Financial Eligibility Criteria: The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. Annual Contractual Turnover Data for the Previous 3/4 Years should be submitted as per Annexure-IX.(AnnexureVIB of Tender Documents)
41 conditions · 11 needing a document upload
Check List: The tenderer(s) would fill up the check list, as per Annexure-XXIII to ensure that they are submitting the complete tender offer.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Electrical Work for Provision of Power Supply to Signages/Station Name Board at Stations DBRG,NTSK,MXN,JTTN,SLGR,SRTN,AGI,NAM,DJG,NHK,TSK,GLGT,LEDO & MJN)
LV-T-14-TSK-949
LV-T-14-TSK-949
Open
Works - General
12 Months
Tinsukia, Assam
₹0
₹1.4 L
29 Jul 2026
8 Jul 2026
15 Jul 2026
23 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 71,00,151 | ||
| — | 842.00 | — | — | ||
| Supply, fitting, fixing, testing & commisioning of wiring materials for concealed type wiring 5 A plug point from main/sub-main board to the points by 2.5 mm. sq. single core multi-strand FRLS copper cable through heavy duty PVC pipe complete with modular type switch & socket 5 A ,GI metal box with Suitable modules for fixing switch/socket with 1.0 mm² unsheathed FRLS copper cable in green colour for earth continuity wire. | — | — | — | 3,60,376 | |
| — | 120.00 | — | — | ||
| Supply, fitting, fixing, testing and commissioning of wall mounted 4 way MCB SPN DB Double Door having IP 63 protection, Shrouded Neutral Bar & Bus Bar, Cement Spill Protector & Door Earthing with the following domestic switchgears :- (i) 63 Amps DP MCB "C" Series(2 Module), 240/415 V, 50 Hz, 10 kA BC (In accordance with IS/IEC 60898-1) =2 No | — | — | — | 5,05,200 | |
| — | 15.00 | — | — | ||
| Supply, fitting, fixing of wall mounted VTPN DB, Horizontal TP MCCB as incomer 4 way double door , IP: 43 Protection, Shrounded Neutral Bar and pan assembly with flexible connecting link., cement spill protector, door earthing with the following:(i) MCCB 100 Amps, TPN ,25KA BC= 1 No.(ii) MCB SP 63 Amps, C series, Icn =10KA BC= 4 Nos. (iii) MCB SP 32 Amps, C series, Icn =10KA BC= 3 Nos | — | — | — | 5,11,350 | |
| — | 8500.00 | — | — | ||
| Supply, drawing and connection of single core 6.0 sq. mm PVC insulated & unsheathed multistrand FRLHS copper cable conforming to IS: 694 for voltage grade upto 1100 Volts , as per direction of supervisor incharge at site. | — | — | — | 7,22,500 | |
| — | 15000.00 | — | — | ||
| Supply, drawing and connection of single core 2.5 sq. mm PVC insulated & unsheathed multistrand FRLHS copper cable conforming to IS: 694 for voltage grade upto 1100 Volts , as per direction of supervisor incharge at site. | — | — | — | 5,85,000 | |
| — | 2500.00 | — | — | ||
| Supply,Laying ,testing & commissioning of 10 mm.sq. Single Core HRFR PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, Conforming to IS: 694 for voltage grade upto 1100 Volts , as per direction of supervisor incharge at site. | — | — | — | 5,27,500 | |
| — | 5500.00 | — | — | ||
| Supply and laying of 32 mm nominal diameter heavy-duty rigid PVC conduit pipe conforming to IS 9537 (Part 3) (latest revision), complete with all necessary accessories such as couplers, bends, sockets, inspection/junction boxes (where required), bushes, locknuts, saddles/clamps, solvent cement, screws, rawl plugs and all other incidental materials. The pipe shall be laid true to line and level on wall, ceiling, trench or other specified location, securely fixed with suitable saddles/clamps at regular intervals, including cutting, bending, jointing, making good damages to walls/floors wherever required, testing for continuity of the conduit, and completing the work in all respects as per the direction of the Engineer-in-Charge. | — | — | — | 4,70,250 | |
| — | 4500.00 | — | — | ||
| Supply, laying, connection, testing and commissioning of LT XLPE Insulated, Cores Laid Up, PVC Inner sheathed, Armoured stranded aluminum conductor cable Size 16 SQ MM 2 Core having Galvanized steel Strip, Extruded PVC Type ST2 Sheathed, 650/1100V Grade As Per IS 7098(Part 1) 1988. For cable laying Excavation of earth depth 0.75 Mtrs. into breadth 0.58 Mtrs. below the ground level and a layer of course sand of 7.5 CM thickness shall be spread over the ground before laying the cable and the cable shall be covered with a layer of course sand of 7.5 CM thickness. The bottom of cable trench shall be leveled and got rid of any sharp material. Above the Layer of Course Sand 3 inch Size Brick is to be provided for protection of cable. Cable route markers to be provided at an interval not less than 50 Mtrs. All conditions to be fulfilled as per DRG No : PCEE/ELG/DRG/2024/2 Dtd 04.10.2024. | — | — | — | 13,14,000 | |
| — | 80.00 | — | — | ||
| Supply, fitting, fixing, testing and commissioning of 30W LED Flood Light Pressure Dia cast AL housing, IP 65 , System Efficacy100 lm/W , Impact Protection: IK07 with Short circuit , reverse Polarity Protection, Surge Protection: +/-4KV, THD<10%, operation on 220 240 V/AC, 50Hz to be installed with necessary arrangement as per direction of Engineer-Incharge ar Site suitable for highlighting architectural features or area lighting.For non illuminated boards like notice board,time table,fare table etc as required with necessary arrangements as per direction of Engineer-Incharge. | — | — | — | 4,32,000 | |
| — | 15.00 | — | — | ||
| Supply, installation, testing and commissioning of Single Phase Street Light Panel/Time Light Distribution Board (DB) in CRCA sheet steel enclosure of minimum 1.6 mm thickness, powder-coated, suitable for wall mounting with IP-54 degree of protection, complete with 63 A SPN MCB conforming to IS/IEC 60898-1, 10 kA breaking capacity, C-curve, 240/415 V AC, 50 Hz; 65 A, 3 Pole AC-3 rated power contactor conforming to IS/IEC 60947-4-1, suitable for switching inductive lighting loads, coil voltage 230 V AC; Astronomical Digital Timer Switch with battery provision having minimum 30 programme , inbuilt Real Time Clock (RTC), manual override (Auto/ON/OFF), LCD display, operating supply 230 V AC, 50 Hz, contact rating 16 A,complete with Auto/Manual selector switch, ON/OFF push buttons, LED indication lamps, neutral link, earth terminal, FRLS copper internal wiring with ferruled conductors, with mounting components, terminal blocks, cable glands, gland plate, earthing stud, labels and all necessary accessories, suitable for 230 V, single-phase, 50 Hz supply with maximum connected load of 12 kW, complete in all respects including testing and commissioning as directed by the Engineer-in-Charge. | — | — | — | 6,15,975 | |
| — | 176.00 | — | — | ||
| Supply, installation, testing and commissioning of 40 Watt LED Surface/Wall Mounted Moisture-Resistant Weatherproof LED Batten Luminaire complete with vandal-resistant UV-stabilized polycarbonate housing, high-transmission opal polycarbonate diffuser, integrated constant-current electronic LED driver and all accessories, suitable for illumination of Station Name Boards at station ends. The luminaire shall be suitable for operation on 230 V AC ±10%, 50 Hz single-phase supply and shall be IP-65 protected against ingress of dust and water, making it suitable for outdoor installation under all weather conditions.The luminaire shall have a rated power of 40 W, minimum system efficacy of 120 lm/W, Power Factor (PF) 0.95, Total Harmonic Distortion (THD) 10%, Colour Rendering Index (CRI) 80, Correlated Colour Temperature (CCT) 5700 K ± 300 K (Cool Daylight), surge protection of minimum 4 kV, and an average rated life of not less than 50,000 burning hours (L70). The luminaire shall operate satisfactorily over an input voltage range of 140-270 V AC without noticeable flicker and shall comply with the latest applicable IS 10322 (Part 5/Section 1), IS 16101, IS 16102 (Part 1 & 2), IS 15885, IEC 60598, and relevant BIS standards.The work shall include design, fabrication, supply and installation of a suitable protective shed/canopy arrangement for the luminaire to ensure proper illumination of the Station Name Board while protecting the fitting from direct sunlight, rain, dust and bird droppings. The shed shall be fabricated from minimum 1.6 mm thick hot-dip galvanised (GI) sheet or approved equivalent, adequately stiffened with MS/GI angle or flat supports, and securely mounted on the Station Name Board structure. The canopy shall be of suitable dimensions and projection as required at site to provide effective weather protection without obstructing the light distribution. All MS fabricated components shall be properly cleaned and finished with one coat of red oxide primer and two coats of approved aluminium/synthetic enamel paint where galvanization is not provided. | — | — | — | 10,56,000 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
tenderdocuments949.pdf
ATTACHMENT
AnexxuresSectionVIINew.pdf
ATTACHMENT
GCCACS11_compressed.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .