Tender Value
₹43.3 L
EMD Value
₹87,000
Closing Date
17 Jun 2026, 11:00 amClosed
Executive Engineer MHD SKIMS/JVC
SKIMS Soura
Creation of Central Lab and Canteen in Stilt floor of IPD Block at SKIMS MCH Bemina (Mechanical Component-SITC of VRV/VRF System)
2026_PWDJK_310605_2
MHD/SKIMS/JVC/03 0F 2026-27 DATED.21.05.2026
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
30 days
SKIMS MCH Bemina
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,500
Executive Engineer MHD SKIMS/JVC
₹87,000
9 Jul 2026
21 May 2026
17 Jun 2026
21 May 2026
17 Jun 2026
21 May 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, Installation, Testing & Commissioning of Modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling/heating having 100% hermetically sealed inverter type twin Rotary/Scroll Compressor(s),minimum two compressors (with individual separate PCB) for above 14HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R-410-A Refrigerant or equivalent, vibration Isolators with suitable foundation etc. complete as required. To have better efficiency condenser fan shall be capable to operate at different speed with respect to load. The unit shall deliver the rated capacity and in confirmation as per IS 18728:2024 The system shall be able to deliver 100% of the rated capacity upto 39 Degree Celcius.The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply and BMS compatible. The unit shall be filled with first charge of the refrigerant and ready for use as required. The condenser should be coated with a hydrophilic film to prevent water accumulation on the surface of the heat exchanger, enhance water dispersion, and reduce the risk of degradation, thereby improving overall performance and durability. The Indian Seasonal Energy Efficiency Ratio (ISEER) of the unit shall be 6.4 as per Energy Conservation and Sustainable Building Code (ECSBC) 2024 and complete
the ODU must deliver a COP of minimum 3.5 at full load and shall be suitable to operate within an abmbient temperature of range of 5 deg. C to 40 deg.C in cooling mode to 15 deg. C in heating mode | - | - | - | - |
| 2 | Outdoor Unit- 18HP (Hot And Cold) Top Discharge
Canteen= 1w | 1 | Job | - | - |
| 3 | Outdoor Unit- 16HP (Hot And Cold) Top Discharge
labs and allied rooms = (2w +1s) | 3 | Job | - | - |
| 4 | Design,Supply, Installation, Testing and Commissioning of following minimum capacity 4 way Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump,drain pipe, grill, necessary supports, vibration Isolation, Corded remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The Indoor units must shut down upon receiving a singal from the BMS System/Fire Signals. The system shall be capable to adjust air flow as per room requirement in auto mode. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make will be same as of Outdoor) | - | - | - | - |
| 5 | 1 TR
Room2 = 01 No. | 1 | each | - | - |
| 6 | 1.6 TR
Room1 = 01 No.
Room3 = 02 No
Room5 = 02 No
Room6 = 01 No
Room9 = 01 No.
Paramedic Canteen = 04 No. | 11 | each | - | - |
| 7 | 2 TR
Central Lab = 04 No.
Room4 = 01 No.
Room7 = 02 No.
Room8 = 01 No.
Doctor's Canteen = 04 No. | 12 | each | - | - |
| 8 | Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : | - | - | - | - |
| 9 | 6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm | 150 | Mtr | - | - |
| 10 | 9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm | 170 | Mtr | - | - |
stage.html
html • 0.03 MB
cancelled_1.pdf
pdf • 0.27 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.03 MB
BOQ_1004607.xls
BOQ • 0.29 MB
extnsion.pdf
PDF • 0.38 MB
extnit0002.pdf
PDF • 0.34 MB
extnit333.pdf
PDF • 0.25 MB
extnit3.pdf
PDF • 0.38 MB
extensions.pdf
PDF • 0.25 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .