Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.7 LAdmitted-Finance | L1 | Admitted-Finance | |
| 2 | L2₹10.2 L+₹50,150 (5.17%)Admitted-Finance | L2 | Admitted-Finance | |
| 3 | Rejected-Technical CW 545 SANJAY GANDHI TRANSPORT NAGAR NEW DELHI 110042 | NORTH | DELHI | 110042 | - | Rejected-Technical Due to not full fill the term and condition of NIT | |
| 4 | Rejected-Technical | - | Rejected-Technical Due to not full fill the term and condition of NIT |
| Sl No | Description | Qty | Unit | HYDROCON ENGINEERS L1 | M/S CHAITANYA CONSTRUCTION CO. L2 |
|---|---|---|---|---|---|
| 1.01 | Dismantling of existing pump, motor from the base frame by cutting of rusted M.S nut bolts and foundation bolts by gas cutter set and electric welding machine, removing all the nut bolt and worm out M.S Base frame from the RCC foundation suction and delivery side by gas cutter set and electric welding set job also includes dismantling the suction & delivery side sluice valve, NRV, taper bend, Cable, tray etc. as per side requirement and lifting of pump and motor on safe place. Breaking of RCC foundation by pneumatic power hammer chisel and electric compressor machine etc. the job includes removing the broken material from P/H and disposing the same at suitable place. | 1 | Job | 9,500 ₹11,210 Lowest | 10,000 ₹11,800 |
| 1.02 | Supply of Horizontal Split casing pump for clear water applications having minimum discharge 170 m3/hr, Approx head 42 meter with bronze impeller & neck ring, SS 410 Shaft & bronze sleeve, CI body, Pump suction/delivery size 150mmx100 mm. Make:- KBL/M&P/Jyoti/DJB Approved. | 1 | Each | 2,20,000 ₹2,59,600 Lowest | 2,25,000 ₹2,65,500 |
| 1.03 | Supply of 40 HP, 3 phase AC, 1450 rpm TEFC squirrel cage induction motor with tyre/ Pin bush coupling. Complete fitted. Make. Motor- KEC/Crompton/ABB/Jyoti/DJB approved make. | 1 | Each | 2,75,000 ₹3,24,500 Lowest | 3,00,000 ₹3,54,000 |
| 1.04 | Supply of M.S pipe of all size. | 60 | Kg | 4,200 ₹4,956 Lowest | 4,500 ₹5,310 |
| 1.05 | Supply of M.S Specials of all size. | 40 | Kg | 2,800 ₹3,304 Lowest | 3,000 ₹3,540 |
| 1.06 | Providing and fixing bolts including nuts and washers complete. | 30 | Kg | 3,750 ₹4,425 Lowest | 4,500 ₹5,310 |
| 1.07 | Supply of star delta starter suitable for 40 HP Pump set as required. | 1 | Job | 53,000 ₹62,540 Lowest | 55,000 ₹64,900 |
| 1.08 | Supply of rubber packing sheet 100% Neoprene rubber. Make: Jyoti/national/any DJB approved. | 25 | Kg | 13,750 ₹16,225 Lowest | 15,000 ₹17,700 |
| 1.09 | Supply of NRV of size 200 mm IS: 5312 part 1 PN 1.0 Make - Kirloskar / IVC/DJB Approved | 1 | Each | 61,500 ₹72,570 Lowest | 62,500 ₹73,750 |
| 1.10 | Supply of Non-Rising Sluice valve of size 200 mm, IS: 14846 PN 1.0 Make - Kirloskar / IVC/DJB Approved | 2 | Each | 1,38,000 ₹1,62,840 Lowest | 1,40,000 ₹1,65,200 |
Tender Value
Refer Docs
EMD Value
₹19,600
Closing Date
31 Jul 2025, 12:00 pmClosed
Executive Engineer (EM) M-I
Chitra Vihar BP Station Laxmi Nagar Delhi-110092
Providing and fixing of Pump Set no. 4 at Janta Flats Mayur Vihar Phase III BPS.
2025_DJB_275047_6
NIT No-05 EE (EM) M-I/ (25-26)
Open Tender
Electrical Works
Works
120 days
Chitra Vihar BP Station Laxmi Nagar Delhi-110092
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
sab paisa
₹19,600
19 Aug 2025
5 Jul 2025
31 Jul 2025
5 Jul 2025
31 Jul 2025
5 Jul 2025
Dismantling of existing pump, motor from the base frame by cutting of rusted M.S nut bolts and foundation bolts by gas cutter set and electric welding machine, removing all the nut bolt and worm out M.S Base frame from the RCC foundation suction and delivery side by gas cutter set and electric welding set job also includes dismantling the suction & delivery side sluice valve, NRV, taper bend, Cable, tray etc. as per side requirement and lifting of pump and motor on safe place. Breaking of RCC foundation by pneumatic power hammer chisel and electric compressor machine etc. the job includes removing the broken material from P/H and disposing the same at suitable place.
Supply of Horizontal Split casing pump for clear water applications having minimum discharge 170 m3/hr, Approx head 42 meter with bronze impeller & neck ring, SS 410 Shaft & bronze sleeve, CI body, Pump suction/delivery size 150mmx100 mm. Make:- KBL/M&P/Jyoti/DJB Approved.
Supply of 40 HP, 3 phase AC, 1450 rpm TEFC squirrel cage induction motor with tyre/ Pin bush coupling. Complete fitted. Make. Motor- KEC/Crompton/ABB/Jyoti/DJB approved make.
Supply of M.S pipe of all size.
Supply of M.S Specials of all size.
Providing and fixing bolts including nuts and washers complete.
Supply of star delta starter suitable for 40 HP Pump set as required.
Supply of rubber packing sheet 100% Neoprene rubber. Make: Jyoti/national/any DJB approved.
Supply of NRV of size 200 mm IS: 5312 part 1 PN 1.0 Make - Kirloskar / IVC/DJB Approved
Supply of Non-Rising Sluice valve of size 200 mm, IS: 14846 PN 1.0 Make - Kirloskar / IVC/DJB Approved
Making of RCC foundation of suitable size as per existing for M.S. base including providing fixing of foundation bolt as per site requirement.
Fixing of new M.S. base frame made of M.S. channel of size 100 mm x 50 mm complete with on the RCC foundation the job includes proper leveling and alignment. Installation of the pump set with proper alignment and also making of all electrical connections, fitting all valves, bends etc. as required.
Testing / commissioning of the pump set on NO load & full load after making of all connections.
M/S CHAITANYA CONSTRUCTION CO. (BID ID -1607565)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .