REPAIR AND MAINT OF VCB HT PANELS , TRANSFORMERS AND CONNECTED E/M WORKS UNDER GE(AF) ADM AREA, AGRA
2022_MES_537210_2
80022-03/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (AF) Adm Area Agra
As per tender documents
7 documents required · 7 mandatory
₹500
GE (AF) Adm Area, Agra
₹40,000
Yes
31 Oct 2022
20 Aug 2022
17 Sept 2022
20 Aug 2022
10 Sept 2022
27 Aug 2022
Amount
Taking out Transformer from its Position from any location under AF Stn Agra for repair /servicing/ rewinding of capacity 63 to 200 KVA , 11/ 0.433 Volts disconnecting /opening HV, LV Electrical connections, earthing connections complete all as specified and directed along with following other works :- (a) Transportation of transformer to civil workshop at AF Stn to workshop at Agra and back to site by making necessary arrangements of T&P (crane, recovery, vehicle, tripoid to be arranged by firm ) as required at site. (b) Opening of transformer top cover by extraction ,removing of serviceable - unserviceable nuts bolts and washers etc. (c) Draining out of transformer oil and keeping in safe custody for reuse (d) Lifting primary coil (HT) and secondary coil (LT) , dismantaling of transformer complete part by part carefully. (e) Refilling topping up of transformer oil after dehyderation and filteration in transformer. (f) Reassembeling the transformer complete with all existing serviceable parts, and new parts as ordered . (g) Reinstall the Transformer at site in position as directed after repair connecting HV, LV electrical connections, earthing connections and testing to entire satisfaction on load . (h) Replacement of userviceable parts like; Bush insulator, brass studs, cork gasket, breather assembly, tap changer, rewinding , reinsulation of Primary and secondary coil with copper winding wire, dehyderation and filteration of transformer oil etc shall be measured and paid seperately under appropriate Item of schedule. (j) Renewal of adequate size Nut, bolts & washers of transformer top cover shall deemed to be included in UNIT RATE QUOTED.
All as per Srl Item No -01 here-in-before but capacity of transformer 250 KVA to 400 KVA complete all as specified and directed.
All as per Srl Item No -01 here-in-before but capacity of transformer 500 KVA to 750 KVA , complete all as specified and directed.
M & L for rewinding HT coil of 11/ 0.433 KV Transformer any capacity using proper size DPC copper wire and insulation material , heating coils in heat chamber after rewinding including taking out carefully burnt unserviceable copper winding of coils complete all as specified and directed.
M & L for rewinding LT coil of 11/ 0.433 KV Transformer any capacity using proper size DPC copper wire and insulation material , heating coils in heat chamber after rewinding including taking out carefully burnt unserviceable copper winding of coils complete all as specified and directed.
Re-insulation of LT coil of transformer of any capacity using proper size paper insulation material to form DPC Copper wire and insulation material suitable for HT 11 KV transformer complete all as specified and directed. [Note : Item shall be measured only where re-insulation of copper wire is required].
Supply & filling up of transformer oil conforming to IS -335 of 1993 as in topping up / replacement up to desired level of transformer oil capacity complete all as specified and as directed. [Note: Dielectric strength of oil should not be less than 42 KV/cm complete all as specified and directed.
Dehydration and filtration of existing transformer oil of transformers capacity ranging from 63 KVA to 3.15 MVA ( 33 KV System step down to 33/11 KV and 11 KV System step down to 11/0.433 KV) on site at different locations without disturbing the power supply system with filtration machine and heating system in order to achieve Di-electric strength of oil 55KV minimum at 2.5 mm gap complete all as specified and as directed.
Servicing to transformer at site of capacity 63 KVA to 315 KVA installed on Plinth / Pole mounted structure by opening top cover & replacing unserviceable spares / components of transformer ,without lifting core assembely reassembling after repair & testing complete all as specified and directed. Note :- (i) The quoted rates by the contractor includes for fixing the serviceable parts against unsv parts. (ii) The new replaced parts shall be measured and paid seperately under respective items of Sch. A as "Supply only"
Servicing to transformer at site of capacity 400 KVA to 750 KVA installed on Plinth / Pole mounted structure by opening top cover & replacing unserviceable spares / components of transformer ,without lifting core assembely reassembling after repair & testing complete all as specified and directed. Note :- (i) The quoted rates by the contractor includes for fixing the serviceable parts against unsv parts. (ii) The new replaced parts shall be measured and paid seperately under respective items of Sch. A as "Supply only"
Supply only Tap Changer as per existing size, shape and specification complete for capacity 315 KVA to 500 KVA , 11/0.433 Volts transformers complete all as specified and directed.
Supply only Tap Changer as per existing size, shape and specification complete for capacity 250 to 300 KVA, 11/0.433 Volts transformers complete all as specified and directed.
Supply only Tap Changer as per existing size, shape and specification complete for capacity 63 to 200 KVA, 11/0.433 Volts transformers complete all as specified and directed.
Supply only breather assembly as per existing size, shape and specification complete for capacity 63 to 200 KVA , 11/0.433 Volts transformers complete all as specified and directed.
Supply only breather assembly as per existing size, shape and specification complete for capacity 250 to 400KVA, 11/0.433 Volts transformers complete all as specified and directed.
Supply only breather assembly as per existing size, shape and specification complete for capacity 500 to 750 KVA, 11/0.433 Volts transformers complete all as specified and directed.
Taking out the existing silica gel and supplying and filling the new silica gel in the breather of transformer of any capacity complete all as specified and directed by Engineer-in-charge.
Supply only brass stud on HT side as per existing size, shape and specification for capacity 500 to 750 KVA, 11/0.433 Volts transformers complete all as specified and directed.
Supply only brass stud on HT side as per existing size, shape and specification for capacity 250 to 400 KVA, 11/0.433 Volts transformers complete all as specified and directed.
Supply only brass stud on HT side as per existing size, shape and specification for capacity 63 to 200 KVA, 11/0.433 Volts transformers complete all as specified and directed.
Supply only brass stud on LT side as per existing size, shape and specification for capacity 500 to 750 KVA, 11/0.433 Volts transformers complete all as specified and directed.
Supply only brass stud on LT side as per existing size, shape and specification for capacity 250 to 400 KVA , 11/0.433 Volts transformers complete all as specified and directed.
Supply only brass stud on LT side as per existing size, shape and specification for capacity 63 KVA to 200KV transformers complete all as specified and directed.
Supply only 32 mm dia gunmetal drain valve of transformer as per existing one complete all as specified and directed.
Supply only 25 mm dia gunmetal drain valve of transformer as per existing one complete all as specified and directed.
Supply only 20 mm dia gunmetal drain valve of transformer as per existing one complete all as specified and directed.
Supply only Temperature Guage as per existing size, shape and specification complete for capacity 500 to 750 KVA , 11/0.433 Volts transformers.
Supply only Temperature Guage Changer as per existing size, shape and specification complete for capacity 250 to 400 KVA, 11/0.433 Volts transformers.
Supply only Temperature Guage as per existing size, shape and specification complete for capacity 63 to 200 KVA, 11/0.433 Volts transformers complete all as specified and directed.
Supply only top cover gasket set as per existing size, shape and specification complete for capacity 500 KVA to 750 KVA , 11/0.433 Volts transformers complete all as specified and directed.
Supply only top cover gasket set as per existing size, shape and specification complete for capacity 250 to 400 KVA, 11/0.433 Volts transformers complete all as specified and directed.
Supply only set of gasket (rubberized cork ) as per existing size, shape and specification complete for capacity 63 KVA to 200 KVA Volts transformers complete all as specified and directed.
M & L for porviding new cable box made out of MS sheet of thickness not less than 5 mm including fabrication works, welding etc. to suit the existing transformer size, including nuts, bolts, cable glands, termination of existing cables etc., all as directd by the Engineer-in-charge for the following capacity transformers:
250 to 750 KVA
63 to 200 KVA
Supply only Porcelain Bush insulators on HT side as per existing size, shape and specification for capacity 500 to 750 KVA, 11/0.433 Volts transformers
Supply only Porcelain Bush insulators on HT side as per existing size, shape and specification for capacity 250 to 400 KVA, 11/0.433 Volts transformers
Supply only Porcelain Bush insulators on HT side as per existing size, shape and specification for capacity 63 to 200 KVA, 11/0.433 Volts transformers
Supply only Porcelain Bush insulators on LT side as per existing size, shape and specification for capacity 500 to 750 KVA, 11/0.433 Volts transformers
Supply only Porcelain Bush insulators on LT side as per existing size, shape and specification for capacity 250 to 400 KVA, 11/0.433 Volts transformers
Supply only Porcelain Bush insulators on LT side as per existing size, shape and specification for capacity 63 to 200 KVA, 11/0.433 Volts transformers
M & L for preparation of old painted steel or iron surfaces of transformer 11/0.433 Volts capacity by scrapping with steel wire brush/ scrapper emery paper etc and applying two coats of synthetic enamel smoke grey paint over a coat or red oxide primer (painting shall be done by spray machine) including writing of SM No, MES No etc, at prominent place/ location of transformer with black synthetic enamel thick paint in white back ground complete all as specified and directed.
500 to 750 KVA
250 to 400 KVA
63 to 200 KVA
Cleaning of bushes/small plants upto root level around and surroundings areas E/M installations (i.e.Two Pole/ Four structures, outdoor-substation yards & Misc E/M installations etc) including spraying of chemical for anti-vegetation growth as approved, surface dressing n.exc 15 cm deep and removing debris to a distance n.exc 50m complete all as directed.
M & L for shifting of transformers 11/ 0.433 KV installed on 2 pole/PCC plateform/ indoor/ outdoor from one sub stn to another sub stn upto distance 3 Km incl disconnecting elect connection LT/HT side re-installation at site and connect LT/HT connection, commissioning & testing complete all as directied for the following capacities:-
315 to 750 KVA
63 to 250 KVA
M & L for shifting of transformer 11/ 0.433 KV of capacity 500 KVA Trolley Mounted from Main Power house to required location at the AF station incl. making all HT/ LT electric connections and disconnectiong all HT / LT connections of faulty transformer of any capacity and restore the electric supply of affected area complete all as specified and directed.
Repair/ servicing of HT VCB/ RMU 630/400 amps of any make by replacing defective/ worn out parts, adjustment of gap for smooth operation all as detail below:- (a) Cleaning of VCB with air blower and removing dust particles. (b) Cleaning of insulating places of VCB by using CTC/ CRC/ Thinner as required and recommended. (c) Checking the arcing contact gap of vacuum interrupter if gap exceeds the permissible limit, adjust as recommended. (d) Cleaning the main contacts to remove carbon or any other unwanted particles if visible. (e) Dismantling and cleaning the insulated surfaces and arc barrier with CTC and CRC. (f) Checking repair/ replacement of all electric wiring for electrical/ manual operation of panel including measuring IR value. (g) Checking all nuts, bolts, springs, levers, latches, connectors etc and adjustment as required. (h) Recording IR values of CTs and PTs. (j) Cleaning of bus bar spouts. (k) Checking of all moving parts for proper functioning of VCBs and adjustment as per manufacturer recommendations. Make of VCBs :- Alstom/ CG/ Areva or equivalent. Note:- (i) The quoted rates by the contractor includes for fixing the serviceable parts against unsv parts. (ii) The new replaced parts shall be measured and paid seperately under respective items of BOQ as "Supply only".
Supply only 1.5 sqmm flexible PVC stranded copper conductor cable, unsheathed, 1100 V grade for control wiring.
Supply only 2.5 sqmm flexible PVC stranded copper conductor cable, unsheathed, 1100 V grade for control wiring.
Supply only LED Indication Lamps with holder
Supply only LED type push button actuators
Supply only Shunt trip coil 30 V DC/110 V DC
Supply only Closing coil 30 V DC/ 110 V DC.
Supply only CTs epoxy cast wound primary CTs with minimum primary current 400-60/5 + 5 Amps, single/ double ratio, double core (Protection core-5P10 & Metering core- Class 0.5/1.0), 18/21/25 KA for 1 sec of 15 VA Burden.
Supply only Breaker control switch
Supply only Breaker bushing contact
Supply only Vacuum interrupter assembly existing model of VCB.
Supply only Busbar Spout
Supply only Circuit spout
Supply only Control circuit fuses 2 A to 63 A
Supply only HRC fuse (PT HT side)
Supply only PT plug contact
Supply only Spring charging motor with gear assembly. Make: Bosch or as per OEM make
Supply only Multifunction meter, Digital type (Displaying A, V, PF, Hz, KVA, KW, KVAR, KWh, KVARh etc.) Class 0.5 with RS485 port for communication in Modbus protocol.Make : L&T, HPL (SOCOMEC), CG or equivalent as approved by Engr-in-Charge
Supply only Rachet handwheel with gear assembly
Supply only Closing spring assy
Supply only Tripping spring assy.
Supply only Fixed contact block.
Supply only Moving contact block.
Supply only Isolating contact assy.
M&L Space heater 80 watt for HT VCB as per suitable capacity and rating; complete all as specified and directed.
S & F in replacement of Master Trip Relay suitable for 11 KV HT panel for protection system; complete all as specified and directed. . Make: ABB/ Siemens/Areva/Easun/CG
S & F in replacement DC SupervisionRelay suitable for 11 KV HT panel for protection system; complete all as specified and directed. . Make: ABB/ Siemens/Areva/Easun/CG
S & F in replacement Auxiliary Relay suitable for 11 KV HT panel for protection system; complete all as specified and directed. . Make: ABB/ Siemens/Areva/Easun/CG
Disconnect and taking out the Numeric/ Microprocessor based relay/IDMT relay of any type of any Make from 11 KV HT panel, cleaning the contacts, calibrating the relay by conducting secondary injection tests, checking of current transformer, rectification of defects in control wiring for proper tripping of circuit breakers through CTs and relay and tripping coils, adjustment/setting to plug and time multiplier settings of the relay to achieve the descrimination in tripping, tune/synchronise upstream breaker relay settings, re-installation of relay, testing & commissioning etc complete all as specified and as directed. Note: The Contractor has to arrange necessary testing Kits, testing equipments, tools etc and shall also submit detailed test reports, panel wise. Rental rates for the testing/calibration kits & connected equipments are deemed to be included in the quoted rate. Testing & tuning shall be carried out in the presence of representative of the Department, to the satisfaction of the Department.
M & L for spray painting with one coat of smoke Grey Synthetic enamel paint on VCB panel after cleaning dust, dirt and oil including writing the SM/ MES No. on VCB in block letters complete all as specified and directed.
Supply only CRC spray 1.weight 300 gm for cleaning of electrical contact / HT contact
Supply and fixing tri vactor meter (TVM), LCD display, accuracy 0.2S, current 1A to 05 Amps, PT secondary 110V including necessary connection complete all as specified and directed.
Supply and fixing in replacement of power pack with capacitor, input 110/230 V AC supply and out put 24 V DC supply ,over load, S/C protection, for VCB panel as per existing size and make complete all as specified by Engr-in-charge.
M & L in replacement Battery 12 Volt 7.2 AH for existing VCB of same model of; complete all as specified and directed.
Supply & Filling Gas SF6 in Cylinder (9 KGs/CYL) Model No S1 94-5600-103-17 for RMU/SF6 HT 11 KV breakers including repair of any leakage of gas chamber complete all as specified
M & L in replacement Automatic Voltage Regulating Relay(AVR) FX1000 as per existing model complete all as specified and directed. Make :- Pradeep sales and service private limited or equivalent as approved by GE
Removing the existing unserviceable duct cover from site and M/L RCC duct cover of size (70X60 X 7.5) cm by using RCC (1:2:4) type B-1 (20mm graded stone aggregate set in CM (1:4) with providing 10mm dia TMT bar @ 150mm C/C spacing complete all as specified and directed.
M & L in replacement Lightning arresters expulsion type 33 KV complete with all fittings, transmission class, discharge capacity 65 kilo amp
M & L in replacement 33 KV single phase surge moniter with current leakage measurement device classification type -B, mild steel complete all as specified and directed.
M & L in replacement 33 KV Triple pole, mechanically operated, horizental type isolator ,mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating upto 200 amps complete all as specified and directed
M & L for earthing complete with copper plate 60×60cm ×3.15mm thick buried directly in ground(earth pit not less than 3.25 mtr deep below the normal ground level) with top edge of plate not less than 2.5 mtr below the normal ground level connected to 20×3mm thick copper strip by means of nuts, bolts, washers and check nuts , 40 mm bore GI pipe light grade proection pipe up to test point, 20mm dia light grade GI pipe for watering, meshed funnel, alternate layer of charcoal and common salt complete all as per SSR with PCC chamber, 50mm thick RCC cover in (1:2:4) type B-1 using (20mm graded stone aggregate) reinforced with 8mm dia TMT bar @ 80mm c/c both way in lieu of CI pit cover and protection including necessary excavation and earth work complete all as specified and directed.
M & L for Testing of Transformers 33/ 11 KV, 3.15 MVA (02 Nos. Each) OCTC Make:- CG, SL No:- M11990/1 & M1990/2, MFH Year 1996 installed at Main Receiving Station (Top:1) through authorised OEM i.e Crompton Greaves for performance testing as per parameters given below including all required testing equipments at site, including opening / disconnecting all connections of transformers as required for testing and reconnections, assembling and testing after Condition Assessment of Transformers:- OIL TEST:- (a) Dissolved Gas Analysis of Oil Sample. (b) Furan Analysis of Oil Sample. (c) Full oil test as per IS 1866 (BDV, PPM, Resistivity, Tan Delta, Flash Point, Sludge, Viscosity). OFFLINE TEST:- (a) DIRANA Test- Moisture & Di- Electric. (b) Capacitance and Tan Delta for winding. (c) Ratio Test ( at all taps).Magneting current (at all taps) (d) Magnetic balance Test. (e) IR & PI test (Main transformer), insulation resistance- Between core, frame & tank (if connection provided externally) (f) Short circuit current and Impedence Measurement with controlled voltage. (g) Winding resistance test (all taps). (h) SFRA Test. (j) Degree of Polymerization test on paper samples. (k) Magnetizing current ( at all taps).
ON LINE TEST:- (i) Noise Level Test. (ii) Thermography Test. (iii) Vibration.(iv) Partial Discharge. Note:- (i) Actual Test results/ reports of all checked parameters from authorised OEM i.e Crompton Greaves shall be submitted in original to HQ CWE (AF) Agra through GE (AF) Adm Area. (ii) All required T & P at site, to and fro fare of testing team, manpower, Lodging, Boarding, idling charges due to any cause, electricity, water sanitation and food etc shall be provided by contractor and its rates shall be deemed included in quoted rates.
virendera singh
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .