Electrical works in connection with "Kulpi- New Block-Station at KULPI."
ELEG-OT-1355-2026-27
ELEG-OT-1355-2026-27
Open
12 Months
24 Paraganas South, West Bengal
₹0
₹91,300
2 Jul 2026
2 Jul 2026
13 Jul 2026
1-NS Schedule - (Cabling and Wiring works)
"Trenching and laying of LT cable(4-core, 50 mm² to 120 mm², 1100V grade) underground by soil cutting 1 through 75 mm dia HDPE pipe along with supply of HDPE pipe (PE100, PN10, IS:4984), without sand and bricks including refilling of trench by excavated soil and make good of surface as its original condition, (The cable trench should be of minimum 1000 mm depth). (The cable trench should be of minimum 1000 mm depth).. (HDPE Pipe Make: Skipper/ Capital Polyplast/ Chaika Polymers/ Utkarsh/ Ashirvad/Arpan/Ori Plast) (L.T. Cable will be supplied by Railway)"
"Cable laying through 2" dia. GI Pipe along with supply of GI Pipe as per General Specification. (G.I. Pipe Make: TATA/ Jindal / Bansal ) (L.T. Cable will be supplied by Railway)"
"Drawing of L.T. cable through PF wall / Structure by cleating / clamping etc as per General Specification. (L.T. Cable will be supplied by Railway)"
"Drawing of LT cable in Concealed way through PF wall / structure / building wall etc. as per General specification. 'L' hook should be provided at approx. every half meter length. (L.T.Cable will be supplied by Railway)"
"Drawing of LT cable through inside of GI octagonal/tubular pole for loop in & loop out. (L.T.Cable will be supplied by Railway)"
"Cable laying upon supplied/existing cable tray with necessary binding/clamps etc. (L.T.Cable will be supplied by Railway)"
Supply, installation, and commissioning of FRP cable trays (Min: 300 mm width) conforming to relevant IS/IEC standards, inclusive of all accessories, support structures, anchoring hardware, and labour charges for complete and secure erection at designated locations.(RMC Switchgears/Sintex/Fiber Tech Composite/ Ferrotech/Grasp/OBO Betterman)
Wiring of light point with 1.5 sq.mm PVC copper wire FRLSH through PVC conduit pipe from inside JB with porcelain fuse kit-kat / MCB of rating 16 A to top of G.I Octagonal pole 5.5 mt. long along with copper ECC of size 1.5mm2 as per General specification of IE Rule. (PVC Wire Make: Havells/ Gloster/ Polycab/ RR Kabel/ KEI/Mescab)"
"Wiring/Re-wiring of Light and Fan points with 1.5 sq.mm., PVC insulated 1100V grade FRLSH single core, 9 M/Strand copper wire through suitable size (ISI marked) PVC conduit pipe/casing/concealed way along with ECC of 1no. 1.5 sq.mm. , PVC insulated single core, M/Strand FRLSH copper wire as per General specification of IE Rule. (PVC wire Make: Havells/Gloster/Polycab/RR Kabel/KEI/Mescab) (Switch & Plug Socket Make: Panasonic/ Anchor/ GM Modular/ Legrand/Crabtree/ Havells/Hager)"
"Supply and fixing of 3 pin, 5 amp, ceiling rose on the supplied metal box of size (75 mm x 75mm x 60 mm deep) on surface or in recess with suitable size of phenolic laminated sheet cover in front, painting etc. as required including 10 electrical connection for Light & Fan points with 2 nos. 1.5 sq.mm, 1100V grade Copper PVC FRLSH, Single core, Multi-strand wire(for phase and neutral) along with 1 no. single core FRLSH PVC insulated copper wire of size 1.5 sq.mm, 1100V grade for ECC through flexible PVC conduit from ceiling rose connected with Sub-main as per General specification of IE Rule (PVC wire Make: Havells/Gloster/Polycab/RR Kabel/KEI/Mescab) (Switch & Plug Socket Make: Panasonic/ Anchor/ GM Modular/ Legrand/Crabtree/ Havells/Hager)"
"Supply, laying, and termination of sub-main wiring comprising 3 run of 4mm² single-core copper conductor PVC FRLSH insulated wires, along with one run of 2.5mm² copper Earth Continuity Conductor (ECC), through G.I. conduit pipe, for PF shed/Car Shed/Shed of FOB etc. as per General specification of IE Rule (PVC wire Make: Havells/Gloster/Polycab/RR Kabel/KEI/Mescab)"
"Supply, laying, and termination of sub-main wiring comprising 2 run of 6mm² single-core copper conductor PVC FRLSH insulated wires, along with one run of 2.5mm² copper Earth Continuity Conductor (ECC), through G.I. conduit pipe, for shed etc. as per General specification of IE Rule (PVC wire Make: Havells/Gloster/Polycab/RR Kabel/KEI/Mescab)"
"Supply, laying, and termination of main/sub-main wiring comprising 2 run of 6mm² multi-stranded single- 13 core copper conductor PVC FRLSH insulated wires, along with one run of 2.5mm² copper Earth Continuity Conductor (ECC), through suitable size (ISI marked) PVC conduit pipe/casing/ concealed way as per General specification of IE Rule (PVC wire Make: Havells/Gloster/Polycab/RR Kabel/KEI/Mescab)"
"Supply, laying, and termination of sub-main wiring comprising 2 run of 4mm² single-core copper conductor 14 PVC FRLSH insulated wires, along with one run of 2.5mm² copper Earth Continuity Conductor (ECC), through suitable size (ISI marked) PVC conduit pipe/casing/ concealed way as per General specification of IE Rule (PVC wire Make: Havells/Gloster/Polycab/RR Kabel/KEI/Mescab)"
"Supply, laying, and termination of sub-main wiring comprising 2 run of 4mm² single-core copper conductor 15 PVC FRLSH insulated wires, along with one run of 2.5mm² copper Earth Continuity Conductor (ECC), through G.I. conduit pipe, for PF shed/Car Shed/Shed of FOB etc. as per General specification of IE Rule (PVC wire Make: Havells/Gloster/Polycab/RR Kabel/KEI/Mescab)"
"Wiring of 6 Amp plug board consisting with one 6A plug socket and one 6 amp switch by 2 nos. single core FRLSH grade, PVC insulated, copper conductor wire of size 1.5 mm2, 1100V grade for phase and neutral alongwith 1 no. 16 single core FRLSH grade, PVC insulated, copper conductor wire of size 1.5 mm2, 1100V grade for Earth Continuty Conductor (ECC) through suitable size (ISI marked) PVC conduit pipe/casing/ concealed way as per General specification of IE Rule. (PVC wire Make: Havells/Gloster/Polycab/RR Kabel/KEI/Mescab) (Switch & Plug Socket Make: Panasonic/ Anchor/ GM Modular/ Legrand/Crabtree/ Havells/Hager)"
"Wiring of 16 Amp./ 6 pin plug board consisting with one 16A plug socket and one 16 amp switch by 2 nos. single core FRLSH grade, PVC insulated, copper conductor wire of size 4 mm2, 1100V grade for phase and neutral alongwith 17 1 no. single core FRLSH grade, PVC insulated, copper conductor wire of size 2.5 mm2, 1100V grade for Earth Continuty Conductor (ECC) through suitable size (ISI marked) PVC conduit pipe/casing/ concealed way as per General specification of IE Rule. (PVC wire Make: Havells/Gloster/Polycab/RR Kabel/KEI/Mescab) (Switch & Plug Socket Make: Panasonic/ Anchor/ GM Modular/ Legrand/Crabtree/ Havells/Hager)"
"Supply and fixing of 4 core x 2.5 mm2 PVC insulated, sheathed flexible copper conductor cable for power connection between outdoor and indoor unit of split A.C. unit complete as required. (PVC Wire Make: Havells/ Gloster/ Polycab/ RR Kabel/ KEI/ Mescab)"
"Copper Cable - 6 Core X 2.5 Sqmm. [RM= Running Foot] ( Make: Havells/ Gloster/ Polycab/ RR Kabel/KEI/Mescab)" Unit
2-NS Schedule - ( LED Luminaires ) (LED luminaries should cover a warranty of 60 Above/
"Design of mounting layout ,Supply, installation for LED street light luminaires of approximately 60W rating, 1 having a minimum luminous efficacy of 120lm/W as per General Specification. The luminaires shall be housed in pressure die-cast aluminium enclosures and conform to minimum IP65 protection rating or higher. Installation/fixing of street light fitting should be made with suitable dia. G. I. bend pipe with G. I. clamps made of G. I. Flat of suitable size & G. I. Nut, bolts etc. (Make - Bajaj/ Philips/ Havells/ Crompton/ Panasonic/ Orient/ Signify/Ecolink) "
"Design of mounting layout ,Supply, installation for LED street light luminaires of approximately 90W rating, 2 having a minimum luminous efficacy of 120lm/W as per General Specification. The luminaires shall be housed in pressure die-cast aluminium enclosures and conform to minimum IP65 protection rating or higher. Installation/fixing of street light fitting should be made with existing/supplied arm bracket of G.I. pole / Rail pole. (Make - Bajaj/ Philips/ Havells/ Crompton/ Panasonic/ Orient/ Signify/Ecolink) "
"Design,Supply, installation and mounting layout for integrated LED TUBE LIGHT 4ft. luminaires 1 X 20W 3 (approx.) (Extruded Aluminium LED Batten) (IP:20) (indoor type)as per General Specification including fixing with G. I. clamps made of G. I. Flat of suitable size & G. I. Nut, bolts etc. (Make - Bajaj/ Philips/ Havells/ Crompton/ Panasonic/ Orient/ Signify/Ecolink)"
"Design of mounting layout, supply, connection, fixing, testing, and commissioning of integrated LED trunking light fixtures, 40W, 4-ft (1200 mm)/80W, 8 ft (2400 mm)/ 120 W, 12-ft (3600 mm) length, with linear extruded aluminium housing, sturdiness & excellent corresion resistance powder coated, LED lumen efficacy 110 lm/W, 4 Polycarbonate Diffuser, IP>54 luminaire, BuiltIn industrial grade Constant Current electronic LED driver, suitable for Seamless surface or suspended mounting includes all required accessories and suitable installation arrangement for complete functional deployment as per General Specification. (Quantity of this item will be assessed in multiple of 1200 mm, i.e; 4 ft = 1 nos/ 8 ft = 2 nos/ 12 ft = 3nos.) (Make - Bajaj/ Philips/ Havells/ Crompton/ Panasonic/ Orient/ Signify/Ecolink)"
"Designing of mounting layout, Supply, installation, connection and commissioning of LED luminaire 4ft., 5 2X18W or above (min. IP:20, indoor type) as per General Specification including batten complete with all accessories including fixing with G. I. clamps made of G. I. Flat of suitable size & G. I. Nut, bolts etc. (Make - Bajaj/ Philips/ Havells/ Crompton/ Panasonic/ Orient/ Signify/Ecolink)"
"Designing of mounting layout, Supply, installation, connection and commissioning of LED Tube Light 4ft. 6 luminaires 2X18W or above (indoor type) as per General Specification complete with tubes and all accessories. (LED luminaires should conform to min IP:65 ) including fixing with G. I. clamps made of G. I. Flat of suitable size & G. I. Nut, bolts etc. (Make - Bajaj/ Philips/ Havells/ Crompton/ Panasonic/ Orient/ Signify/Ecolink)"
Supply and fixing of LED Buffer Light fitting 1 x 10W red in colour complete with all accessories. (LED luminaires should conform to min IP65)
Supply, installation, testing & Commissioning of energy efficient, maintenance free Diamond Boards with imported translucent Fibre material 3mm acrylic outdoor material 28 gauge GI sheet with spray print LED fittings, ACP sheet 3mm, 1"X 1" MS pipe with red oxide complete square Signage with all accessories. Unit Above/
3-NS Schedule - (General Electrical Works)
Supply and fixing of GI fabricated cable end box, 4 way as per Sr. DEE (G)/SDAH's Drg. No. SDAH/G/MISC/40 dt. 10.12.07.
"Supply, concrete foundation & erection of GI Octagonal Pole 5.5mtr. Pole section bottom dia 150mm, top 2 dia 75mm, pole thickness-3mm with base plate 240 x 240x16mm with 4nos. foundation bolts having 25mm dia & of length 700mm along with single/double arm bracket as per General Specification. Loop in & loop out box to be provided inside the pole. Foundation and erection of G.I octagonal pole along with grouting of supplied 4 nos. foundation bolts as per Drg. No. Sr. DEE(G)'s Drg. No. SDAH/G/SS/115 dt. 23.10.09. (Make-B. P. Projects/Transrail/ Crompton/ Bajaj/ Utkarsh)"
"Supply, fixing, testing and commissioning of star rated BLDC Ceiling fan, 1200mm sweep, 3 blade (Blade 3 material :High grade Aluminium alloy),Service value:Minimum 7.5, 230V, 50 c/s, and all other accessories as per General Specification (Without Remote) including fixing of ceiling fan with suitable clamping arrangement &'S' hook etc. (Make: Havells/ Usha/ Anchor/ Orient/ Crompton/ Bajaj/Atomberg)"
"Supply, fixing, testing and commissioning of star rated BLDC Ceiling fan, 1200mm sweep, 3 blade (Blade 4 material :High grade Aluminium alloy),Service value:Minimum 7.5, 230V, 50 c/s, and all other accessories as per General Specification(With Remote) including fixing of ceiling fan with suitable clamping arrangement &'S' hook etc. (Make: Havells/ Usha/ Anchor/ Orient/ Crompton/ Bajaj/Atomberg)"
"Supply, Fixing, connection & commissioning of A.C. Exhaust Fan, 300 mm sweep, 230V, 50 c/s complete with all accessories including fixing with G. I. clamps made of G. I. flat of suitable size & G. I. Nut, Bolts alongwith necessary Masonry works. (Make: Havells/ Usha/ Anchor/ Orient/ Crompton/ Bajaj)"
"Supply, Fixing with suitable G.I clamping arrangement, connection and commissioning of AC Wall Bracket Fan,3 blades, 400mm sweep, approx 55W, 230V, 50Hz complete with all accessories. (Make: Havells/ Usha/ Anchor/ Orient/ Crompton/ Bajaj)"
"Supply, installation, testing, and commissioning of 1 Phase, [2+4] way Distribution Board (Single door, 7 Prewired type) comprising of the following: a) MCB SPN 32A, B/Cap - 10 kA - 1 No. b) MCB SP 10/20A, B/Cap - 10 kA - 4 Nos. Work shall include complete wiring terminations, provision of all necessary mounting hardware, accessories, and interconnections, executed as per site conditions and in compliance with IS/IEC standards. (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager)"
"Supply, installation, testing, and commissioning of single-phase 8-way MCB distribution board (surface/concealed mounting type), comprising the following components: a) 1 No. Double Pole MCB, 32A, 10kA breaking 8 capacity (incoming) b) 6 Nos. Single Pole MCB, 10A, 10kA breaking capacity (outgoing) Work shall include complete incoming and outgoing wiring terminations, provision of all necessary mounting hardware, accessories, and interconnections, executed as per site conditions and in compliance with IS/IEC standards (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager)"
"Supply, installation, testing, and commissioning of single-phase 4-way MCB distribution board 9 (surface/concealed mounting type), comprising the following components: 4 Nos. Single Pole MCB, 10/20A, 10kA breaking capacity Work shall include complete incoming and outgoing wiring terminations, provision of all necessary mounting hardware, accessories, and interconnections, ex ecuted as per site conditions and in compliance with IS/IEC standards (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager)"
"Supply, installation, testing, and commissioning of 3-phase, 4-way TP&N vertical type distribution board 10 (metal double door enclosure, IP:43 rated), comprising the following components: a) 1 No. MCCB, 4-pole, 50-63A, breaking capacity 25kA b) 12 Nos. MCB, single-pole, 16-32A, breaking capacity 10kA The distribution board shall be fixed using suitable ISI-marked G.I. fixtures and accessories, complete in all respects as per site conditions and conforming to relevant IS/IEC standards (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager) "
"Supply and fixing of Mobile Charging points with hylam sheet cover consisting of a) Plug Socket 5Pin/6Amp. - 3 nos. b) Piano Switch 6 Amp - 3 nos. c) MCB SP 6Amp, B/cap10KA. - 1 no. d) LED indication lamp - 1no, including wiring with 11 2.5 mm2 single core, multi strand, PVC FRLS Cu wire through suitable size (ISI marked) PVC conduit pipe/ casing/ concealed way and along with copper ECC of size 1.5 mm2 as per General Specification of I.E. Rule. (PVC Wire Make: Havells/ Gloster/ Polycab/ RR Kabel/ KEI/Mescab) (Switch & Plug Socket Make: Panasonic/ Anchor/ GM Modular/ Legrand/Crabtree/ Havells/Hager) (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager)"
"Supply,fixing and connection of Multi mobile charging point board made of 12mm ply and sunmica size 12 8inchesX15inchesX3inches with wooden tray for resting mobile phones consisting of 4 nos. piano type switch 6A, 4nos 2-in- 1 socket 6A, 01 no LED indicator, 01 no MCB SP 10A including internal wiring with 1.5sq.mm copper wire.Fixing and connection of mobile charging point board etc should be done with wooden tray by necessary GI fixtures as per General Specification of I.E. Rule. (PVC Wire Make: Havells/ Gloster/ Polycab/ RR Kabel/ KEI/Mescab) (Switch & Plug Socket Make: Panasonic/ Anchor/ GM Modular/ Legrand/Crabtree/ Havells/Hager) (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager)"
"Supply and fixing of modular type multi-plug board for Computer power points consisting of: a) Plug Socket 6/16Amp- 3 nos. b) Piano Switch 6 Amp- 3 nos. c) Plug Socket 20 Amp.- 1 no. d) Piano Switch, 16 Amp.-1 no. e) MCB SP 13 16/20 Amp, B/cap- 10kA- 1 no. f) LED indication lamp- 1 no. including wiring with 2.5 mm2 single core, multi strand, PVC FRLS Cu wire through suitable size (ISI marked) PVC conduit pipe/ casing/concealed way and along with copper ECC of size 1.5 mm2. as per General Specification of I.E. Rule. (PVC Wire Make: Havells/ Gloster/ Polycab/ RR Kabel/ KEI/Mescab) (Switch & Plug Socket Make: Panasonic/ Anchor/ GM Modular/ Legrand/Crabtree/ Havells/Hager) (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager)"
"Supply,fixing,testing and commissioning of light control panel with contactor and electro mechanical timer comprising of the following - 1) MCB 32A, Three pole,10KA,415V,50Hz - 1 No., 2) Timer switch- 2 Nos., 3) Power 14 Contactor,3pole,32A - 2 Nos., 4) Toggle switch 6A - 2 Nos., 5) LED Indicators, Indication R,Y,B - 5 Nos. 6) Enclosure made of 14SWG GI sheet fabrication, Panel paint powder coated colour siemens gray and internal wiring with suitable size copper wire etc. (As per Sr.DEE/G/SDAH's drawing number, SDAH/G/1/2024 Dt. 26.02.2024).Fixing should be done by necessary GI fixture and connection with 70%,30% lighting circuit. (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager)"
"Wiring of separate plug point for UTS system etc. with 2.5 mm2 Cu wire, multistrand, single core through PVC Conduit pipe / casing / concealed way and Earth continuity with 1.5mm2 copper wire, each plug board covered with 15 Hylam sheet having i) Plug socket 16A,3 pin - 1 no., ii) Piano type switch,20 Amp - 1 no, iii) Plug socket 6 A, 5 pin - 3 nos., iv) Piano type switch, 6 Amp - 3 nos, v) Flush type Fuse 16 Amp. - 1 no. and vi) indication lamp - 1 no. (PVC Wire Make: Havells/ Gloster/ Polycab/ RR Kabel/ KEI/Mescab) (Switch & Plug Socket Make: Panasonic/ Anchor/ GM Modular/ Legrand/Crabtree/ Havells/Hager) (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager)"5
"For UPS wiring of separate plug point to be done on suitable size M.S board with Hylam sheet cover consisting of the followings: a) Plug socket, 16 Amp, 3 pin - 2 nos., b) Switch, 20 Amp - 2 nos, c) Flush type fuse 16 Amp - 1 16 no. d) Indication Lamp - 1 no., by 2.5 mm2, 1100 volt grade, PVC FRLS Cu, Single core, multi strand wire through ISI brand rigid PVC conduit pipe/ casing/concealed way along with copper ECC of size 1.5mm2 as per General Specification of I.E. Rule. (PVC Wire Make: Havells/ Gloster/ Polycab/ RR Kabel/ KEI/Mescab) (Switch & Plug Socket Make: Panasonic/ Anchor/ GM Modular/ Legrand/Crabtree/ Havells/Hager) (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager)"
Dismantling of existing damaged Rail Pole/Tubular Pole. Rail Pole/Tubular Pole to be cut by Gas cutter from the least bottom level. Released Rail Pole to be stacked in an isolated area apart from platform. Released Tubular Pole to be deposited to the custody of concerned Sr. SEE (G) by the Firm. Exposed Cables to be cleared or buried in to the ground"
Dismantling of existing old damaged wiring and handing over to consignee store.
Dismantling of existing wiring of light point, 5A plug point, 15A plug point, call bell point & FL fittings with tube and handing over to consignee store.
Dismantling of existing different type old overaged LED light fittings and released fittings handed over to consignee store.
Dismantling of old ceiling fan with all accessories including transportation of dismantled fan and accessories from site to stores.
"Supply, fixing, connection & commissioning of junction Box made of 14 SWG GI sheet of size 450 mm x 300 22 mm x 250 mm on AT Mast, consisting with 1 No. MCB DP 63A with G. I. Channel suitable for fixing of MCB, complete with hinged door with locking arrangement. (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager)"
"Supply and fixing of MCB changeover switch 40A, DP in sheet steel enclosure. (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager)"
Supply of automatic 3 point source supply Change over Panel complete for colour light signaling (CLS) system of Cap. 60 Amp., 240 V, 50 C/S, A.C. in 25KV AC traction system as per RDSO's specification No. TI/SPC/PSI/CLS/0020 or latest.
Supply of automatic 3 point source supply Change over Panel complete for colour light signaling(CLS) system of capacity 30A, 1ph, 240V, 50Hz in 25KV AC traction system as per RDSO's specification No. TI/SPC/PSI/CLS/0020 or latest.
Fixing, connection and testing of above RDSO's CLS panel with suitable clamping arrangement.
"Design, Supply, Installation, testing and commissioning of MS fabricated, wall/floor mounted hinged type cubicle panel board made of (14 SWG) MS sheet duly powder coated, comprising with the following :- a) MCCB, 100-125A, 4 27 Pole, 415V,B/Cap:36kA - 2 nos., b) MCCB, 50-63A, 4 Pole, 415V,B/Cap:25kA - 2 nos., c) MCCB, 32-40A, 4 Pole, 415V, B/Cap:25kA - 2 nos. d) MCCB, 16-20A, 4 Pole, 415V, B/Cap:25kA - 2 nos. e) Copper Busbar 4 bar type, 200A - 1 set including internal electrical connections with suitable size of wire / bar and provision of digital Voltmeters, Ammeters with CT and modular LED indicators etc.along with transportation charges. (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager) (Meter Make: Selec/Secure/Lauritz Knudsen/ HPL/Schneider)"
"Design, Supply, Installation, testing and commissioning of M.S (14 SWG) fabricated, painted, hinged type, cubicle panel board comprising of the following: a) MCB TPN, 63A, B/Cap 10KA - 1 No. as incoming for local supply. b) MCB DP, 63A, B/Cap 10KA - 1 No. as incoming for AT supply. c) MCB DP, 32A, B/Cap 10KA - 3 Nos (2 nos for outgoing and 1 no for 28 AC Machines. d) MCB DP, 20A, B/Cap 10KA - 1 No for UPS. e) MCB SPN, 10A, B/Cap 10KA - 3 Nos. (2 nos as light & fan circuit and 1 no as spare. ) f) Two way center off MCB changeover switch DP, 40 A - 1 No. g) Copper bus bar, 4 bar type, 100A - 1 set for local supply h) Copper bus bar, 2 bar type, 63A - 1 set for common source. along with internal connections etc. and provision of LED indication lamps - 2 Nos. along with transportation charges. (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager)"
"Earthing work using two Nos. of 50 mm dia., 2.5 Mtr. long heavy gauge GI Pipe, including construction of 29 earth pit with all associated works, along with providing and fixing necessary earth connections from pit using 25 mm x 4 mm GI flat with GI nuts & bolts etc., complete with testing and commissioning, strictly in accordance with relevant IS codes, electrical safety standards. (G.I. Pipe Make: TATA/ Jindal / Bansal )"
Supply and installation of G.I. strip of size 25 mm x 3 mm (thick), fixed along walls by grouting suitable size 30 bolts with nuts at 450 mm intervals for earthing, including provision of necessary connections. The G.I. strip shall be separated from the wall using suitable size insulators with the bolts. The work shall be completed with testing and commissioning, strictly in accordance with relevant IS codes, electrical safety standards.
"Supply and installation of GI Standard Earth pipe, 40 mm dia, 2000 mm long, medium gauge complete with 31 provision of Earth pit and there connection with 4 SWG GI wire complete with testing and commissioning, strictly in accordance with relevant IS codes, electrical safety standards.as per Sr. DEE(G)/SDAH's Drg. No. SDAH/G/MISC/47 dt.21.11.2008(Alt-1). (G.I. Pipe Make: TATA/ Jindal / Bansal )"
Supply of basic material to construct unit maintenance free earth as per RDSO specs NO. RDSO/SPN/197 Ver. 1.0 or latest and conforming to RDSO Drg No. SDP/RDSO/E&B/001 or latest. Necessary testing Certificate of UL, IEC to be produced.(1 lot=1 job)
"Installation of unit maintenance free earth as supplied in above item. The installation of this item shall be carried out by the contractor as per RDSO Specs. No. RDSO/SPN/197 Ver. 1.0 or latest and conforming to RDSO Drg No. SDO/RDSO/E&B/001 or latest." Unit Above/
4-NS Schedule - ( AC Works )
"Supply of 5 star rated Inverter type Split Air-conditioner of capacity 2 TR, 230V, 1 Ph. 50 Hz compressor 1 type: Rotary complete with all accessories as per General Specification including Installation/re-installation of indoor unit and outer unit and connection by 3/8"" and 5/8"" or as per machine size copper tube with suitable clamping arrangement and covering the tube with insulation including loading, unloading & transportation of the materials. (Make: Hitachi/ Daikin/ OGeneral/ Mitsubishi / Carrier/ Panasonic/ Voltas/ Samsung/ Haier)"
Supply & fixing of M. S. angle frame on the wall for outer unit of size approx.: 3' x 4' and made from 1½ inch x 1½ inch x 4 mm thick M.S. angle. Frame should be painted with black Japan paint.
Supply of additional copper pipe of dia 1/4" for Air conditioning machine and soldering with existing tube including supply of insulation and inserting the same on additional copper tube.
Supply of additional copper pipe of dia 5/8" for Air conditioning machine and soldering with existing tube including supply of insulation and inserting the same on additional copper pipe.
"Supply & fixing of AC power unit in enclosure with RCCB DP, 25A, sensitivity 30mA Starter rating G/H/J or equivalent. (Switchgear Make: North West/ Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager)"
Supply & charging of fresh Refrigerant gas(R-32/ R410A or similar Eco-friendly Refrigerant).
Supply of 5/8" PVC pipe unbreakable for drainage of water.
"Supply of 5.0 TR DUCTED A.C. Units (1No. IDUs & 1No. ODU) (Imported system) R- 410(A) Green Gas complete with all accessories as per General Specification. (Make: Hitachi/ Daikin/ Mitsubishi / Carrier/ Panasonic)"
Installation, testing, commissioning of Ducted Unit 5 TR
Canvas Connection for Ductable A.C. Units
"Piping & Ducting support with MS Rod Std. sizes & Angle for IDU from true ceiling. (For 2 nos Ducted AC)" (1lot = 1 job)
22 Lite Gauge GI Ducting
24 Lite Gauge GI Ducting
Nitrile Insulation for Ducting
Accoustic Insulation inside of Ducting to protect from sound, sweating & Vibration.
Supply & Fixing of Aluminium powder coated Premier supply/return Air Grill
Volume Control damper for Coller
Supply & Installation of insulated Copper Ref. piping with Nitrile insulation, Copper Elbow, Socket for Ducted units. [RM = Running Foot]
"40MM Thick PVC Drain Piping with Nitrile Insulation. [RM = Running Foot] "
"32MM Thick PVC Drain Piping with Nitrile Insulation. [RM = Running Foot]"
"25MM Thick PVC Drain Piping with Nitrile Insulation. [RM = Running Foot]"
ODU Structure for CASSETTE Unit are chargeable extra
"Loading/Unloading, Lifting & Shifting of outdoor/indoor units, including transportation of materials, Oxygen welding, Nitrogen Flashing, extra Gas Charging for long pipe length, etc. (For 2 nos Ducted AC)"(1 lot=1 job)
"Communication cabling of suitable size between indoor and outdoor unit"
"Nitrogen flushing, vaccumizing, commissioning of the entire system"
Lifting, shifting of indoor and outdoor units at site
Top up gas charging
Water drainage 32 mm.
Water drainage 25 mm. Unit Above/
5-NS Schedule - ( Temporary Illumination )
"Temporary arrangement for illumination for NI work consisting of the following items in operation for the period of 18:00hrs to 06:00 hrs:- i)02 nos of 5KVA(4KW) DG set including fuel and operator. ii) 10 nos of 150W LED fitings 1 with lamp and all other accessories/LED flood light fittings 100W and all accessories. iii) 05 nos of 9W LED Bulb with holder and all other accessories/1X18W LED fittings and all accessories. iv) 02 nos board,each consisting of 02 nos 5/15A plug socket with switch and all accessories. v) Main/Sub-main line with 10/6/4 sq.mm PVC coppper wire of approx 1000 mt length. vi) 02 nos pedestal fan/ceiling fan with connection. (2 set per day X 4 days X 1 location=8 sets)"
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
FormatofGuaranteeBond.pdf
ATTACHMENT
2022_CE-I_CT_GCC-2022Policy14_07_20221.pdf
ATTACHMENT
GCC-April-2022.pdf
ATTACHMENT
LTHTElectricalBooklet.pdf
ATTACHMENT
LEDluminariesSpecifications_2.pdf
ATTACHMENT
OpenTenderDocument_1.pdf
ATTACHMENT
2026_03_13IndianRailwaysStandardGeneralConditionsofContractApril2022AdvanceCorrectionSlipNo_111.pdf Correction
ATTACHMENT
Advance
ATTACHMENT
2025_01_09IIndianRailwaysStandardGeneralConditionsofContractApril-2022AdvanceCorrectionSlipNo_9ACS-9.pdf
ATTACHMENT
2026_03_13IndianRailwaysStandardGeneralConditionsofContractApril2022AdvanceCorrectionSlipNo_111.pdf
ATTACHMENT
Download all tender documents and submit your bid