| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹33.7 LAccepted-AOC WZ 1000 NANGAL RAYA PANKHA ROAD SOUTH WEST DELHI DELHI 110046 | DELHI | SOUTH WEST DELHI | DELHI | 110046 | L1 | Accepted-AOC BEING L1 | |
| 2 | L2₹35.9 L+₹1.3 L (3.85%)Rejected-Finance | L2 | Rejected-Finance Not Being L1 | |
| 3 | L3₹38.8 L+₹4.2 L (12.1%)Rejected-Finance 1 225 5 6 SADAR BAZAR DELHI CANTT 110010 | NEW DELHI | DELHI | 110010 | L3 | Rejected-Finance Not Being L1 | |
| 4 | L4₹41.1 L+₹6.5 L (18.8%)Rejected-Finance NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | L4 | Rejected-Finance Not Being L1 | |
| 5 | L5₹42.1 L+₹7.5 L (21.7%)Rejected-Finance A 303 VEENA CGHS LTD PLOT NO 5D SECTOR 22 DWARKA NEW DELHI 110077 | NEW DELHI | SOUTH WEST DELHI | DELHI | 110077 | L5 | Rejected-Finance Not Being L1 |
Tender Value
₹48.6 L
EMD Value
₹97,500
Closing Date
30 Dec 2024, 6:00 pmClosed
GE UTILITY ELECTRIC SUPPLY
GE UTILITY ELECTRIC SUPPLY DELHI CANTT
SPL REPAIR REPLACEMENT OF OLD UNSV UNDERGROUND HT LT CABLES MCCBS LED FLOOD LIGHTS STREET LIGHTS ALONGWITH CONNECTED ITEMS AT MANEKSHAW CENTRE AND PROVN OF 08 NOS STEEL TUBULAR POLES LED FLOOD LIGHTS XLPE UG CABLE AND CONNECTED ALLIED WORKS AT
2024_MES_686639_1
GE ELECT/D-79/2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE UTILITY ELECTRIC SUPPLY
AS PER TENDER DOCUMENT
7 documents required · 7 mandatory
₹500
Yes
GE UTILITY ELECTRIC SUPPLY
₹97,500
Yes
3 Feb 2025
2 Dec 2024
1 Jan 2025
2 Dec 2024
30 Dec 2024
16 Dec 2024
Amount
Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft/loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom suface to required level complete all as specified and directed by Engineer- in- Charge.
Returning filling in,. Including spreading, levelling,. Watering and well ramming soil in layers not exceeding 25 cm thick complete all as specified and directed by Engineer- in- Charge.
Removing excavated material (ie soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point complete all as specified and directed by Engineer- in- Charge.
M&L for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc, complete all as specified and directed by Engineer- in- Charge. Note : Measurement shall be taken after punning down.
S&F sub class B bricks having minimum compressive strength 75 Kg/ Sqcm laid in trenches for cable protection etc complete all as specified and directed by Engineer- in- Charge.
Supplying and laying un-reinforced precast concrete cable cover, class HV, type 1, flat size 300mmx 180mm x 40mm for cable protection complete all as specified and directed by Engineer- in- Charge.
All as per srl item No 6 here-in-before but using old cable cover complete all as specified and directed by Engineer- in- Charge.
Supply, laying, jointing, testing and commissioning in replacment of LT underground cables 1100 volts grade, PVC insulated XLPE and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, IS-1554 marked, laid in trenches complete all as specified and directed Cables of the following sizes:- Note Excavation, earth work ,cable protection , sand fillings , cable joint shall be measured and paid separately.
50 Sqmm 3.5 core
95 Sq mm 3.5 core.
120 Sq mm 3.5 core.
150 Sq mm 3.5 core.
185 Sq mm 3.5 core.
240 Sq mm 3.5 core.
Supplying, laying, jointing testing and connecting in replacement XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 11 KV grade, IS 7098 marked, suitable for HT 11 KV(E) system, laid in trenches / ducts / encased in GI pipe / fixed to pole, including jointing & testing of size 240 sqmm 3 core complete all as specified and directed by Engineer- in- Charge.
Supply, Jointing and testing of Cable jointing kit for 11 KV (Earthed) grade cable for Indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 Sqmm to 400 Sqmm 3 core complete all as specified and directed by Engineer- in- Charge.
Supply, Jointing and testing of Cable jointing kit for 11 KV (Earthed) grade cable for Straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 Sqmm to 300 Sqmm 3 core complete all as specified and directed by Engineer- in- Charge.
Boring of hole under road/pavement/hard standing or any other situation by trenches Technology using ultra sounding Technique and necessary machine including HDPE pipe of 160mm dia suitable for 0.6 MPA working pressure complete all as specified and directed by Engineer- in- Charge.
Earthing complete in replacement with galvanized steel earth plate electrode of size 60cmx60cmx6 mm thick, buried directly in ground (earth pit not less than 3.5 m below normal ground level) with top edge of earth plate not less than 2.5m below normal ground level, connected to galvanized iron strip 32X6 mm by means of electric arc welding of galvanised iron or steel as shown in electrical plate No 3 of SSR Part I, connected to earth test point and the equipment on the other side complete all as specified, including testing and commissioning complete all as specified and directed by Engineer- in- Charge. Note : - (a) The unit rates quoted against this item shall be deemed to include the cost of excavation and earth work in any type of soil, common salt & charcoal dust in alternate layers, PCC 1:3:6 as in pit, precast RCC 1:2:4 type B-1 with necessary reinforcement as in cover & frame for pit, funnel, watering pipe 20 mm bore GI pipe light grade, protection pipe 40 mm bore GI pipe light grade etc. (b) The quoted rates shall also deemed to include the cost of earth test point and earth strip/GI earthing and protection pipe upto 7.5 meter beyond the earth plates electrode.
Supply installation & commissioning in replacement of 24V, 40A Float Cum Boost Battery Charger unit including battery bank comprising 02 Nos of 12 Volts, 00 AH sealed maintenance free batteries. The CCCV battery charger consisting of copper wound, air cooled transformer, 01 Set single phase full wave bridge rectifier consisting of diodes and SCRs, liberally rated mounted on heat sink and complete with resistor/condenser network for surge supperssion . During auto float mode automatic changeover shall take place from float mode to boost mode and vice versa, 01 Set of solid state constant potential controller to stabilize the DC output voltage of the float cum boost charger, 01 No electronic controller , DC digital ammeter , DC digital voltmeter, Potentiometer , DC, MCB for reverse battery protection . The charger should have alarm annunciation with visual and audible alarm with manual reset facility for fuse fail alarm. Float cum boost battery charger and DC distribution board shall be housed in powder coated sheet steel cubicle with panels of 1.6mm thickness , louvers for ventilation , gland plate will be provided for cable entry from bottom . The battery charger shall be divided into two compartments. The upper compartment shall house the battery charger & DCDB with all necessary controls. The lower compartment shall be suitable for housing the batteries. Tech specification shall be as under:- (a) Input working voltage-180 -270 Volts (b) Nominal Input Voltage - 230 V , AC , 50 Hz,1 (c) On load input power factor - > 0.8 (d) On load unit watt efficiencies-> 80% (e) No load losses of complete charge-< 10%(f) Ripple contents on the load (RMS)= 1% to 5% (g) Over load - 110% for 30 minutes and will give visual indication for over load condition. (h) Boost charging - 2.4 V/Cell . (j) Float charging -2.15 V/Cell (k) Float cum boost charging-Automatically changes from one state to another state as per battery condition and will give the visual indication for either float or boost based on charging mode. (l) Reverse polarity -No damage will caused. A visual indication for reverse polarity will appear with an audio alarm. (m) Short circuit-MCB protecton provided.
S&F in replacement GI Pipe (light grade) with necessary accessories/ fittings for cable protections/pole for crossing of culverts/nallah complete all as specified and directed by Engineer- in- Charge of following bore sizes :-
S&F in replacement of LED street light fitting fitting 90 Watt made up of pressure die cast housing with toughned glass and individual high power LEDs with secondary optics, IP66 protection complete all as specified and directed by the Engg-in-Charge. Make: Havells Cat Part No.ENDURASU NDOWNSL90WLED765PASYBOTG or equivalent in Cropton/Phillips/Wipro as approved by GE.
S&F in replacement LED street light fitting fitting 60 Watt made up of pressure die cast housing with toughned glass and individual high power LEDs with secondary optics, IP66 protection complete all as specified and directed by the Engg-in-Charge. Make: Havells Cat Part No.ENDURASU NDOWNSL60WLED765PASYBOTG or equivalent in Cropton/Phillips/Wipro as approved by GE.
S&F in replacement LED Flood light Watt 100 Watt made up of pressure die cast housing with toughned glass and individual high power LEDs with secondary optics, IP66 protection complete all as specified and directed by the Engg-in-Charge. Make: Havells Cat Part No.JETAADORNNXTFL S100WLED757P60DT0TG or equivalent in Cropton/Phillips/Wipro as approved by GE.
S&F in replacement LED Flood light Watt 120 Watt made up of pressure die cast housing with toughned glass and individual high power LEDs with secondary optics, IP66 protection complete all as specified and directed by the Engg-in-Charge.Make: Havells Cat Part No.JETAADORNNXTFL S120WLED757P60DT0TG or equivalent in Cropton/Phillips/Wipro as approved by GE.
S&F in replacement LED Flood light Watt 200 Watt made up of pressure die cast housing with toughned glass and individual high power LEDs with secondary optics, IP66 protection complete all as specified and directed by the Engg-in-Charge.Make: Havells Cat Part No.JETAADORNNXTFL S200WLED757P60DT0TG or equivalent in Cropton/Phillips/Wipro as approved by GE.
(b) Outgoing :- (i) MCCB 4 pole , 160 Amps,50 Hz,415 Volts, 36 KA with microprocessor release - 03 Nos (ii) MCCB 4 pole , 100 Amps,50 Hz,415 Volts, 36 KA with microprocessor release - 02 Nos (c) Platform of Panel :- Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. Note:- (i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacture.
S&F in replacement MCCB 4 Pole ,200Amps 36 KA with thermal and magnetic release fixeds in any type of existing LT panel/Feeder piller complete all as specified and directed by the Engg-in-Charge.
S&F in replacement MCCB 4 Pole ,250Amps 36 KA with thermal and magnetic release fixeds in any type of existing LT panel/Feeder piller complete all as specified and directed by the Engg-in-Charge.
S&F in replacement MCCB 4 Pole ,400Amps 36 KA with thermal and magnetic release fixeds in any type of existing LT panel/Feeder piller complete all as specified and directed by the Engg-in-Charge.
S&F in replacement MCCB 4 Pole ,630Amps 50 KA with thermal and magnetic release fixeds in any type of existing LT panel/Feeder piller complete all as specified and directed by the Engg-in-Charge.
S&F in replacement 40 Watt LED Post Top for 360 degree indirect light with IP 66 protection, Resistant to impact and corrosion, Glare free and better uniformity complete all as specified and directed by the Engg-in-Charge. Make: Crompton cat part No LPTO-40-WW-M or equivalent in Havells/Orient.
Supply and Laying for GI Tubes of size 40 mm dia light grade, galvanised, with all fitting, laid in trenches for protection of cable in road /drain crossing complete all as specified and directed by the Engg-in-Charge.
Supply, laying, jointing, testing and commissioning of LT underground cables 1100 volts grade, PVC insulated XLPE and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, IS-1554 marked of 16 sqmm 4 Core laid in trenches complete all as specified and directed by the Engg--in-Charge.
Supply & installing Steel tubular swaged poles type 410 SP-31 (9 mtr long) of apprx wt.147 kg conforming to IS 2713 (Part-II) including excavation, earth work, PCC foundation, base plate, PCC coping,GI pipe for cable protection etc. and GI bracket for fitting mounting, complete all as per manufacturer's instructions and as specified and as directed by the Engg-in-charge. NOTE:- The unit rate in this item is deemed to be included the cost of exacavation and earth work in any type of soil, PCC foundation 1:4:8 type D-2 , PCC coping 1:2:4 type B-1 as in steel tubular pole and GI bracket made of GI pipe medium grade 40 mm bore, 1.5 mtr long for fixing of street light fitings . The steel pole shall be painted by bituminious paint in total lenth inside and up to planting depth outside. (b) Along with fixed frame on top of the pole of required materials for fixing of 04 Nos flood light made up of angle iron with dimensions of 50×50×6 mm and flat iron with dimensions of 25×10 mm. The cost of frame is deemed to be included in the quoted rates.
S&F IP66/IP67/IP69 Thermoplastic PC-GFS Polycarbonate Weatherproof Junction Box having size (155x210x92mm) for upto 16sqmm cable size fixed on existing pole with 1No. 16Amp C Curve series, 10KA SP MCB with pole mounting kit for clamping the box on pole, earthing the body connection, inter-connection, suitable terminal blocks, glands, locknuts etc. complete set as reqd. for pole lighting complete all as specified and directed by the Engg-in-Charge. Note:- The junction box shall fulfill the following standards;- Weatherproof : UV resistant due to solar radiation, Rainwaterproof, temperature resistant. IEC 60670-22: particular requirements for connecting boxes and enclosures. IEC 60695-2-11: Flame-retardant & self-extinguishing. Glow wire tested at minimum 960 deg C. IEC 60529: IP66/IP67/IP69 degree of protection.
Supply, drawing, connecting & testing of 3 core, 2.5 Sqmm PVC insulated and PVC rounded sheathed, copper conductor (flexible) industrial cable 1100 Volts grade conforming to IS-694 in steel tubular pole from KIOSK/Junction box to light fittings including providing suitable copper lugs complete all as specified and directed by the Engg-in-Charge.
Outgoing:- (a) 100A FP 25 KA MCCB -1No Note:-. 1. The manufacturer of board / panel shall submit a copy of type test report of a board made out of Polycarbonate thermoplastic panel in accordance with IEC 60 439-1 and IEC 61 439-2 for power switchgear and control gear assembly. The contractor must be submitted routine test certificate from manufacturer/principal company in accordance with IEC 60 439-1. The type test report as per CPRI (in accordance with IEC 60 439-1) should consist with following: i) Degree of protection of system ii) Temperature Rise Limit iii) Dielectric Properties iv) Short Circuit Withstand Strength v) Effectiveness of protective circuit vi) Clearance and creepage distance vii) Mechanical Operation 2. For better safety the Polycarbonate encl shall be fire retardant & self-extinguishing in accordance with IEC 60 695-2-1, DIN VDE 0304 Part 3, UL Subject 94 for Flammability V-2. It should be tested at Glow Wire test for 960 deg. Cent. 3. The impact strength of polycarbonate enclosures / boards i.e. the Degree of Protection against Mechanical load shall be in accordance with EN 50298-98 for IK 08. 4. The board manufacturer must submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS will not be applicable. 5.The quoted rate includes the excavation, earth work and required base for fixing the complete panel.
S&F 90 Watt LED Street light fittings made up of pressure die cast housing with toughned glass and individual high power LEDs with secondary optics, IP66 protection complete all as specified and directed by the Engg-in-Charge. Make Crompton Model No LFLN-120-CDL/60-M or equivalent make of Havells/ Orient.
Supply and fixing of LED Flood lights 150 Watt made up of pressure die cast housing with toughned glass and individual high power LEDs with secondary optics, IP66 protection complete all as specified and directed by the Engg-in-Charge.
Supplying, fabrication, installation, testing and commissioning in replacement of LT panel not less than 3mm thick of modular polycarbonate thermoplastic enclosures Outdoor type with copper bus bar of capacity 630A, factory made, CPRI approved, floor mounting type, environment friendly, recyclable, UV resistant, halogen and silicon free, anti-acid and anti corrosive, enclosure should be IP-65 Protection in accordance with IEC 60529.The gasket material shall be polyurethane while the gasket shall be internally embedded including suitable working space in bus bar chamber suitable for 3 phase 4 wire system 415V,50HZ,AC supply and fixed on raised PCC 1:2:4,type B1 (20mm graded aggregate) raised base with cable glands, phase indicators, internal wiring, CT of suitable Ratio, digital voltmeter and ammeter, air passing holes with proper spacing to accommodate to all control switches and other accessories, cable connections with suitable size of lugs/thimble etc including suitable size canopy to cover the panel with proper fixing arrangement including excavation and earth work including dismantling the unserviceable panel and comprising the followings. Incoming:- (a) MCCB 4 POLE, 400 Amps, 50HZ, 415 Volts, 36ka - 01 No (b) Rotary handle- 01 No (C) spreader Link- 01 set( 08 Pcs) (d) RYB Indicating lamps (e) Digital Voltmeter and ammeter of suitable rating (f) set of CT of ratio - 400/05 Amps Outgoing:- (a) 250A FP 36 KA MCCB - 01 No (b) 160A FP 36 KA MCCB - 01 No (c )125A FP 36 KA MCCB - 02 No (d) Rotary handle- 04 No (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level.
Note:-. 1. The manufacturer of board / panel shall submit a copy of type test report of a board made out of Polycarbonate thermoplastic panel in accordance with IEC 60 439-1 and IEC 61 439-2 for power switchgear and control gear assembly. The contractor must be submitted routine test certificate from manufacturer/principal company in accordance with IEC 60 439-1. The type test report as per CPRI (in accordance with IEC 60 439-1) should consist with following: i) Degree of protection of system ii) Temperature Rise Limit iii) Dielectric Properties iv) Short Circuit Withstand Strength v) Effectiveness of protective circuit vi) Clearance and creepage distance vii) Mechanical Operation 2. For better safety the Polycarbonate encl shall be fire retardant & self-extinguishing in accordance with IEC 60 695-2-1, DIN VDE 0304 Part 3, UL Subject 94 for Flammability V-2. It should be tested at Glow Wire test for 960 deg. Cent. 3. The impact strength of polycarbonate enclosures / boards i.e. the Degree of Protection against Mechanical load shall be in accordance with EN 50298-98 for IK 08. 4. The board manufacturer must submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS will not be applicable. 5.The quoted rate includes the excavation, earth work and required base for fixing the complete panel.
Earthing complete with galvanised steel earth plate electrode 60 cm x60 cm x 6 mm thick buried directly in ground ,(Earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 meter below normal ground level ,connected to and including galvanised iron earth wire 32 X 6 mm by means of nut, bolts, check nuts and washers of galvanised iron or steel and provision of charcoal dust and common salt packed all around the earth plate including necessary excavation and earth work in any type of soil and testing complete all as specified and directed and shown in electrical plate number 3 of MES SSR part-I (1991) .
Note : contractor should procure and provide 50 % of the material as listed above within 15 days of the placing of work order and shall be verified by the Engr-in-charge
M/s JAIMAA ASSOCIATES (BID ID -3201753)
M P TYAGI ENGINEERS AND CONTRACTORS (BID ID -3195514)
Vijay Electricals (BID ID -3193583)
Ridhi engineers and builders (BID ID -3195945)
S K ENGINEERS AND CONTRACTOR (BID ID -3194986)
MV Engineers And Contractors (BID ID -3194944)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .