Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.5 LAccepted-AOC | L1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹29.5 L+₹73,422.45 (2.55%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| Sl No | Description | Qty | Unit | KIRTIMAN TRADERS L2 | KIRTIMAN ENTERPRISES L1 |
|---|---|---|---|---|---|
| 1.00 | Supplying, installation, testing & commissioning CPRI pproved outdoor cubical type LT feeder pillar box suitable for 415V, 3 phase, 4 wire 50 Hz, AC supply system fabricated from CRCA Sheet totally enclosed, dust, weather & vermin proof, 3.0 mm thick for outer shell and 2 mm thick for inner shell having TPN copper busbar of rating 1.5 times that of controlling MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for I second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common aluminum earth bar of size 25 mm x 5 mm at the rear with 02 Nos earth stud, solid connections from main bus bar to switch gears with required size pf copper bus bars and control wiring with minimum 1.5sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half including tamper proof digital energy meter to measure voltage, current, PF, KWH, KVAH, KVARH and general construction confirming to IS:8623 / 93 and mounted on suitable PCC foundation with following detailed specifications & controls.
Cont... item no 1.01 | 1 | Each Job | 4,50,000 ₹4,50,000 Lowest | 4,50,000 ₹4,50,000 Lowest |
| 1.01OUTER SHELL:- The outer shell shall be made of 3.0 mm thick CRCA Sheet & MS angle section 50x50x6 mm frame with front & back openable, single door system lockable/ openable by keys from both sides having flush pattern fancy locks with louvers & air vents gasket for natural flow of air. The bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size with glands. The dimension of the outer shell should be adequate size with glands. The dimension of the outer shell should be adequate to accommodate inner shell described below giving 50 mm space all around & shall be fabricated in such a way that the complete inner shell alongwith its control gears & accessories could be taken outside without disturbing outer shell. The outer shell shall be mounted on a zinc metal coated stand. Provision of threaded earthing stud at bottom & lifting lugs of suitable size at top to lift the feeder pillar box safely shall be made. Computers cut self adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided. The degree of protection of outer shell shall be IP-54. Cont... item no 1.02 | |||||
| 1.02INNER SHELL:- Inner shell made of 2.0 mm thick CRCA Sheet compartmentalized for each control gear, front openable single door system lockable /openable by keys from both sides having chromium plated fancy locks (2 Nos in each compartment) having louvers & air vent gasket for natural flow of air. 'U' type gasket shall be used to make the inner shell completely vermin proof & to accommodate incomer/ outgoing MCCBs and TPN copper bus bar and extension links of rating not less than the 1.5 times the rated capacity of the respective MCCB. The TPN bus bar and extension links shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size 'F' class insulators made of nonhygroscopic, noncombustible, track resistant, high strength SMC material at suitable interval through out the length of the TPN bus bar. Computer cut self adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided on bus bar chamber. All control wires shall be with not less than 1.5sqmm multi strand copper conductors and shall be properly bunched, tied, ferruled for proper identifications and crimped with adequate size of lugs. The cubical shall have a bottom channel of size 75x40 mm duly coated with zinc metal coating. A detachable predrilled gland plate of thickness 3.0mm zinc metal coated should be used at the bottom. Indicating lamps LED type, 230 volts, AC at the incomer of the unit to show three phase availability at the outgoing of incomer. Cont... item no 1.03 | |||||
| 1.03An inspection lamp with I I watt LED shall be fitted on top side of inner shell. The degree of protection for inner shell shall be IP-42 & carry the following controls:- 1. Incoming:- One number MCCB 400 Amp, 4 pole, Ics 36 kA, 415 volts, 50 Hz with thermal magnetic release type, Ics=100% Icu with adjustable overload setting and adjustable short circuit setting 2. Outgoing:- (a) (i) One number MCCB 250 Amp, 4 pole, Ics 25 kA, 415 Volts, 50 Hz, with thermal magnetic release type, Ics=100% Icu with adjustable overload setting and adjustable short circuit setting (ii) Ten numbers MCCB 63 Amp, 4 pole, Ics 25 kA, 415 Volts, 50 Hz, with thermal magnetic release type, Ics=100% Icu with adjustable overload setting and adjustable short circuit setting (b) One number MCB double pole 32 amp 'C' series of breraking capacity 10kA, ISI marked. (c) One number timer 16amp, 230 volts, Astro type. (d) One number contactor 2 pole 40amp with 2 NO contacts. (e) 3 way selector switch for manual ON/OFF/AUTO switching of street light fittings. (f) Digital Ammeter flush pattern type square dial 96 x 96 mm alongwith selector switch - 01 No and suitable CT of ratio 0-500 Amps (g) Digital Voltmeter flush pattern type square dial 96 x 96 mm alongwith selector switch - 01 No and suitable PT of ratio 0-500 Volts. (h) Complete control panel wiring with stranded copper conductor of suitable size along with one set indicator lamp for R,Y & B for each incoming and outgoing feeder. | |||||
| 2.00 | Supplying, installation, testing & commissioning CPRI pproved outdoor cubical type LT feeder pillar box suitable for 415V, 3 phase, 4 wire 50 Hz, AC supply system fabricated from CRCA Sheet totally enclosed, dust, weather & vermin proof, 3.0 mm thick for outer shell and 2 mm thick for inner shell having TPN copper busbar of rating 1.5 times that of controlling MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for I second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common aluminum earth bar of size 25 mm x 5 mm at the rear with 02 Nos earth stud, solid connections from main bus bar to switch gears with required size pf copper bus bars and control wiring with minimum 1.5sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half including tamper proof digital energy meter to measure voltage, current, PF, KWH, KVAH, KVARH and general construction confirming to IS:8623 / 93 and mounted on suitable PCC foundation with following detailed specifications & controls.
Cont... item no 2.01 | 2 | Each Job | 1,85,000 ₹3,70,000 Lowest | 1,95,000 ₹3,90,000 |
| 2.01OUTER SHELL:- The outer shell shall be made of 3.0 mm thick CRCA Sheet & MS angle section 50x50x6 mm frame with front & back openable, single door system lockable/ openable by keys from both sides having flush pattern fancy locks with louvers & air vents gasket for natural flow of air. The bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size with glands. The dimension of the outer shell should be adequate size with glands. The dimension of the outer shell should be adequate to accommodate inner shell described below giving 50 mm space all around & shall be fabricated in such a way that the complete inner shell alongwith its control gears & accessories could be taken outside without disturbing outer shell. The outer shell shall be mounted on a zinc metal coated stand. Provision of threaded earthing stud at bottom & lifting lugs of suitable size at top to lift the feeder pillar box safely shall be made. Computers cut self adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided. The degree of protection of outer shell shall be IP-54. Cont... item no 2.02 | |||||
| 2.02INNER SHELL:- Inner shell made of 2.0 mm thick CRCA Sheet compartmentalized for each control gear, front openable single door system lockable /openable by keys from both sides having chromium plated fancy locks (2 Nos in each compartment) having louvers & air vent gasket for natural flow of air. 'U' type gasket shall be used to make the inner shell completely vermin proof & to accommodate incomer/ outgoing MCCBs and TPN copper bus bar and extension links of rating not less than the 1.5 times the rated capacity of the respective MCCB. The TPN bus bar and extension links shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size 'F' class insulators made of nonhygroscopic, noncombustible, track resistant, high strength SMC material at suitable interval through out the length of the TPN bus bar. Computer cut self adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided on bus bar chamber. All control wires shall be with not less than 1.5sqmm multi strand copper conductors and shall be properly bunched, tied, ferruled for proper identifications and crimped with adequate size of lugs. The cubical shall have a bottom channel of size 75x40 mm duly coated with zinc metal coating. A detachable predrilled gland plate of thickness 3.0mm zinc metal coated should be used at the bottom. Indicating lamps LED type, 230 volts, AC at the incomer of the unit to show three phase availability at the outgoing of incomer. Cont... item no 2.03 | |||||
| 2.03An inspection lamp with I I watt LED shall be fitted on top side of inner shell. The degree of protection for inner shell shall be IP-42 & carry the following controls:- 1. Incoming:- One number MCCB 250 Amp, 4 pole, Ics 36 kA, 415 volts, 50 Hz with thermal magnetic release type, Ics=100% Icu with adjustable overload setting and adjustable short circuit setting 2. Outgoing:- (a) Six number MCCB 63 Amp, 4 pole, Ics 25 kA, 415 Volts, 50 Hz, with thermal magnetic release type, Ics=100% Icu with adjustable overload setting and adjustable short circuit setting (b) One number MCB double pole 32 amp 'C' series of breraking capacity 10kA, ISI marked. (c) 3 way selector switch for manual ON/OFF/AUTO switching of street light fittings. (d) Digital Ammeter flush pattern type square dial 96 x 96 mm alongwith selector switch - 01 No and suitable CT of ratio 0-500 Amps (e) Digital Voltmeter flush pattern type square dial 96 x 96 mm alongwith selector switch - 01 No and suitable PT of ratio 0-500 Volts. (f) Complete control panel wiring with stranded copper conductor of suitable size along with one set indicator lamp for R,Y & B for each incoming and outgoing feeder. | |||||
| 3.00 | Supplying, installation, testing & commissioning CPRI pproved outdoor cubical type LT feeder pillar box suitable for 415V, 3 phase, 4 wire 50 Hz, AC supply system fabricated from CRCA Sheet totally enclosed, dust, weather & vermin proof, 3.0 mm thick for outer shell and 2 mm thick for inner shell having TPN copper busbar of rating 1.5 times that of controlling MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for I second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common aluminum earth bar of size 25 mm x 5 mm at the rear with 02 Nos earth stud, solid connections from main bus bar to switch gears with required size pf copper bus bars and control wiring with minimum 1.5sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half including tamper proof digital energy meter to measure voltage, current, PF, KWH, KVAH, KVARH and general construction confirming to IS:8623 / 93 and mounted on suitable PCC foundation with following detailed specifications & controls.
Cont... item no 3.01 | 2 | Each Job | 1,85,000 ₹3,70,000 Lowest | 1,95,000 ₹3,90,000 |
| 3.01OUTER SHELL:- The outer shell shall be made of 3.0 mm thick CRCA Sheet & MS angle section 50x50x6 mm frame with front & back openable, single door system lockable/ openable by keys from both sides having flush pattern fancy locks with louvers & air vents gasket for natural flow of air. The bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size with glands. The dimension of the outer shell should be adequate size with glands. The dimension of the outer shell should be adequate to accommodate inner shell described below giving 50 mm space all around & shall be fabricated in such a way that the complete inner shell alongwith its control gears & accessories could be taken outside without disturbing outer shell. The outer shell shall be mounted on a zinc metal coated stand. Provision of threaded earthing stud at bottom & lifting lugs of suitable size at top to lift the feeder pillar box safely shall be made. Computers cut self adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided. The degree of protection of outer shell shall be IP-54. Cont... item no 3.02 | |||||
Tender Value
Refer Docs
EMD Value
₹60,444
Closing Date
18 Dec 2025, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE Nasirabad
GE Nasirabad Military Engineer Services Pin 305 601 Rajasthan
SPL REPAIR OLD LT ELECTRIC PANELS AT VARIOUS LOCATION AT NASIRABAD MIL STATION UNDER GE NASIRABAD PROVN OF ALL-WEATHER TOILET AND DRINKING WATER FACILITY WITH PROTECTION FOR TPS OF 475ENGR BDE SIG SEC
2025_MES_742182_1
8613/E8
Open Tender
Civil Works
Item Rate
180 days
GE Nasirabad
As per Tender Documents
6 documents required · 6 mandatory
₹500
Yes
GE NASIRABAD
₹60,444
Yes
19 Jan 2026
29 Nov 2025
20 Dec 2025
29 Nov 2025
18 Dec 2025
13 Dec 2025
29 Nov 2025 - 13 Dec 2025
Amount
Supplying, installation, testing & commissioning CPRI pproved outdoor cubical type LT feeder pillar box suitable for 415V, 3 phase, 4 wire 50 Hz, AC supply system fabricated from CRCA Sheet totally enclosed, dust, weather & vermin proof, 3.0 mm thick for outer shell and 2 mm thick for inner shell having TPN copper busbar of rating 1.5 times that of controlling MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for I second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common aluminum earth bar of size 25 mm x 5 mm at the rear with 02 Nos earth stud, solid connections from main bus bar to switch gears with required size pf copper bus bars and control wiring with minimum 1.5sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half including tamper proof digital energy meter to measure voltage, current, PF, KWH, KVAH, KVARH and general construction confirming to IS:8623 / 93 and mounted on suitable PCC foundation with following detailed specifications & controls. Cont... item no 1.01
OUTER SHELL:- The outer shell shall be made of 3.0 mm thick CRCA Sheet & MS angle section 50x50x6 mm frame with front & back openable, single door system lockable/ openable by keys from both sides having flush pattern fancy locks with louvers & air vents gasket for natural flow of air. The bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size with glands. The dimension of the outer shell should be adequate size with glands. The dimension of the outer shell should be adequate to accommodate inner shell described below giving 50 mm space all around & shall be fabricated in such a way that the complete inner shell alongwith its control gears & accessories could be taken outside without disturbing outer shell. The outer shell shall be mounted on a zinc metal coated stand. Provision of threaded earthing stud at bottom & lifting lugs of suitable size at top to lift the feeder pillar box safely shall be made. Computers cut self adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided. The degree of protection of outer shell shall be IP-54. Cont... item no 1.02
INNER SHELL:- Inner shell made of 2.0 mm thick CRCA Sheet compartmentalized for each control gear, front openable single door system lockable /openable by keys from both sides having chromium plated fancy locks (2 Nos in each compartment) having louvers & air vent gasket for natural flow of air. 'U' type gasket shall be used to make the inner shell completely vermin proof & to accommodate incomer/ outgoing MCCBs and TPN copper bus bar and extension links of rating not less than the 1.5 times the rated capacity of the respective MCCB. The TPN bus bar and extension links shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size 'F' class insulators made of nonhygroscopic, noncombustible, track resistant, high strength SMC material at suitable interval through out the length of the TPN bus bar. Computer cut self adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided on bus bar chamber. All control wires shall be with not less than 1.5sqmm multi strand copper conductors and shall be properly bunched, tied, ferruled for proper identifications and crimped with adequate size of lugs. The cubical shall have a bottom channel of size 75x40 mm duly coated with zinc metal coating. A detachable predrilled gland plate of thickness 3.0mm zinc metal coated should be used at the bottom. Indicating lamps LED type, 230 volts, AC at the incomer of the unit to show three phase availability at the outgoing of incomer. Cont... item no 1.03
Supplying, installation, testing & commissioning CPRI pproved outdoor cubical type LT feeder pillar box suitable for 415V, 3 phase, 4 wire 50 Hz, AC supply system fabricated from CRCA Sheet totally enclosed, dust, weather & vermin proof, 3.0 mm thick for outer shell and 2 mm thick for inner shell having TPN copper busbar of rating 1.5 times that of controlling MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for I second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common aluminum earth bar of size 25 mm x 5 mm at the rear with 02 Nos earth stud, solid connections from main bus bar to switch gears with required size pf copper bus bars and control wiring with minimum 1.5sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half including tamper proof digital energy meter to measure voltage, current, PF, KWH, KVAH, KVARH and general construction confirming to IS:8623 / 93 and mounted on suitable PCC foundation with following detailed specifications & controls. Cont... item no 2.01
OUTER SHELL:- The outer shell shall be made of 3.0 mm thick CRCA Sheet & MS angle section 50x50x6 mm frame with front & back openable, single door system lockable/ openable by keys from both sides having flush pattern fancy locks with louvers & air vents gasket for natural flow of air. The bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size with glands. The dimension of the outer shell should be adequate size with glands. The dimension of the outer shell should be adequate to accommodate inner shell described below giving 50 mm space all around & shall be fabricated in such a way that the complete inner shell alongwith its control gears & accessories could be taken outside without disturbing outer shell. The outer shell shall be mounted on a zinc metal coated stand. Provision of threaded earthing stud at bottom & lifting lugs of suitable size at top to lift the feeder pillar box safely shall be made. Computers cut self adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided. The degree of protection of outer shell shall be IP-54. Cont... item no 2.02
INNER SHELL:- Inner shell made of 2.0 mm thick CRCA Sheet compartmentalized for each control gear, front openable single door system lockable /openable by keys from both sides having chromium plated fancy locks (2 Nos in each compartment) having louvers & air vent gasket for natural flow of air. 'U' type gasket shall be used to make the inner shell completely vermin proof & to accommodate incomer/ outgoing MCCBs and TPN copper bus bar and extension links of rating not less than the 1.5 times the rated capacity of the respective MCCB. The TPN bus bar and extension links shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size 'F' class insulators made of nonhygroscopic, noncombustible, track resistant, high strength SMC material at suitable interval through out the length of the TPN bus bar. Computer cut self adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided on bus bar chamber. All control wires shall be with not less than 1.5sqmm multi strand copper conductors and shall be properly bunched, tied, ferruled for proper identifications and crimped with adequate size of lugs. The cubical shall have a bottom channel of size 75x40 mm duly coated with zinc metal coating. A detachable predrilled gland plate of thickness 3.0mm zinc metal coated should be used at the bottom. Indicating lamps LED type, 230 volts, AC at the incomer of the unit to show three phase availability at the outgoing of incomer. Cont... item no 2.03
Supplying, installation, testing & commissioning CPRI pproved outdoor cubical type LT feeder pillar box suitable for 415V, 3 phase, 4 wire 50 Hz, AC supply system fabricated from CRCA Sheet totally enclosed, dust, weather & vermin proof, 3.0 mm thick for outer shell and 2 mm thick for inner shell having TPN copper busbar of rating 1.5 times that of controlling MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for I second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common aluminum earth bar of size 25 mm x 5 mm at the rear with 02 Nos earth stud, solid connections from main bus bar to switch gears with required size pf copper bus bars and control wiring with minimum 1.5sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half including tamper proof digital energy meter to measure voltage, current, PF, KWH, KVAH, KVARH and general construction confirming to IS:8623 / 93 and mounted on suitable PCC foundation with following detailed specifications & controls. Cont... item no 3.01
OUTER SHELL:- The outer shell shall be made of 3.0 mm thick CRCA Sheet & MS angle section 50x50x6 mm frame with front & back openable, single door system lockable/ openable by keys from both sides having flush pattern fancy locks with louvers & air vents gasket for natural flow of air. The bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size with glands. The dimension of the outer shell should be adequate size with glands. The dimension of the outer shell should be adequate to accommodate inner shell described below giving 50 mm space all around & shall be fabricated in such a way that the complete inner shell alongwith its control gears & accessories could be taken outside without disturbing outer shell. The outer shell shall be mounted on a zinc metal coated stand. Provision of threaded earthing stud at bottom & lifting lugs of suitable size at top to lift the feeder pillar box safely shall be made. Computers cut self adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided. The degree of protection of outer shell shall be IP-54. Cont... item no 3.02
INNER SHELL:- Inner shell made of 2.0 mm thick CRCA Sheet compartmentalized for each control gear, front openable single door system lockable /openable by keys from both sides having chromium plated fancy locks (2 Nos in each compartment) having louvers & air vent gasket for natural flow of air. 'U' type gasket shall be used to make the inner shell completely vermin proof & to accommodate incomer/ outgoing MCCBs and TPN copper bus bar and extension links of rating not less than the 1.5 times the rated capacity of the respective MCCB. The TPN bus bar and extension links shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size 'F' class insulators made of nonhygroscopic, noncombustible, track resistant, high strength SMC material at suitable interval through out the length of the TPN bus bar. Computer cut self adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided on bus bar chamber. All control wires shall be with not less than 1.5sqmm multi strand copper conductors and shall be properly bunched, tied, ferruled for proper identifications and crimped with adequate size of lugs. The cubical shall have a bottom channel of size 75x40 mm duly coated with zinc metal coating. A detachable predrilled gland plate of thickness 3.0mm zinc metal coated should be used at the bottom. Indicating lamps LED type, 230 volts, AC at the incomer of the unit to show three phase availability at the outgoing of incomer. Cont... item no 3.03
M&L Earthing complete with GI strip as earth lead and MS galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate is not less than 1.5 mtr below normal ground level connected to galvanized iron strips 32 x 6 mm with GI pipe, nuts, bolts and washers complete upto and including test point made out of 40 x 3mm GI flat, PCC pit of required size in PCC 1:2:4 type B1 and RCC cover with frame including plastering and white wash, charcoal, common salt 15cm at round the earth plate, watering pipe 20mm med grade/galvanized and 40mm dia GI pipe medium grade for GI strip protection with GI funnel including dismantling old earthing complete all as specified and directed as shown in electrical plate No 3 of SSR Part-I 2009. Notes: (i) The unit rate includes for 40mm diam medium grade protection pipe and earth lead upto 7.50 meter. (ii) Any variation in length of earth lead and protection pipe beyond 7.5 m shall be measured & paid seperately separately. (iii) PCC pit shall be provided at least 500mm away from the pit and not on the earth pit itself and the extra cost of additional height of watering pipe, bends, elbow etc shall be deemed to be included in the unit rate.
Supply and replace 32mm x 6 mm GI strip as in earth continuity conductor fixed to wall or pole or recess or chases or burried in ground or drawn in conduit pipe or any other indicated situation for loop earthing etc as required complete all as specified and directed.
Taking out old unservicible cable and Supply, laying & testing XLPE insulated, armoured, heavy duty electric cable with stranded aluminium conductor, 1100 volts grade, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete of Size 16Sqmm x 4core, complete all as specified and directed.
All as per item No. 6.00 but Size 35Sqmm x 3.5core complete all as specified and directed.
All as per item No. 6.00 but Size 120Sqmm x 3.5core complete all as specified and directed.
S & F Double Wall Corrugated(DWC) HDPE Pipe as per new IS-16205 (for electrical cable uses) in protection of UG Cable laid in trenches of following sizes :- Note : Cost of pipe coupler with rubber ring is deemed to be included in the unit Quoted Rate.
63 mm Outer Dia x 50 mm Inner Dia Pipe
110 mm Outer Dia x 95 mm Inner Dia Pipe
S&F in repair MCCB, 415 Volts, 50 Hz, thermal magnetic release type, Ics=100% Icu with adjustable overload setting and adjustable short circuit setting, including spreader terminals and phase barrier fixed in existing panel board by providing suitable nuts, bolts, washers, etc including taking out old unserviceable one for the following capacity :-
All as per item No 8.00 above MCCB, 4 pole, 250 amps having rapturing capacity 36kA
All as per item No 8.00 above MCCB, 4 pole, 160 amps having rapturing capacity 36kA
All as per item No 8.00 above MCCB, 4 pole, 100 amps having rapturing capacity 36kA
All as per item No 8.00 above MCCB, 4 pole, 63 amps having rapturing capacity 36kA
M & L boaring holes horizontally under Road by trenchless technology without damaging the surface of road as per given/ directed depth below the road surface with the help of boring machine/ or by manual means and laying of DWC Pipe of any dia for passing of UG cable all as specified and as directed. (Note : DWC pipe laid shall be measured seperately).
Repairing and painting of indoor/outdoor type LT panel board mounted on angle / PCC floor of any size with and including replacement of unserviceable switch/control gears, connector, indicator lamps, panel door lock and other minor repairs including rewiring and extension of incoming and outgoing cables (cable excluded) by opening of loops/making joints and providing cable lugs /thimbles as reqd including repairing rusted part of sheet metal door with existing size MS sheets by necessary arc/gas welding and removing all dirt, dust etc. with air blower and painting complete panel board with two coats of synthetic enamel spray painting over a coat of red oxide primer complete all as specified and directed. Note: (i) Cost of providing aluminium thimbles, earth and neutral link, insulator, hylem sheet, any type of screws or any other minor spares of any type as required at site is deemed to be included in the quoted rate. (ii) MCCB, MCB, aluminium bus bar, indicator lamp, Amp / Volt meter or any other major parts required for relacement shall be measured and paid serately in relevent item.
S&F in replacement LED type indicating Lamp for indication of RYB complete all as specified and directed.
S&F in repair Digital LED Voltmeter range 50-520 V flush type all as specified and as directed.
S&F in repair Digital LED Ammeter range 0-100 Amps, flush type all as specified and as directed.
S&F in repair MCB isolator DP 40 Amps 440 volts complete all as specified and as directed.
Cutting unaxious green growth and wild grass, bushes, shrubs by manual labour or by machine at Electrical Installation Premises, around Pole, Electric LT Panel, Bus Bar Chambers, along the boundary Fencing, removing rubbish from the Site of work and deposting where directed not exc. 100 Metre from the starting point, complete all as specified and as directed.
M&L in repair for loose filling with broken stone or boulder aggregates of gauge 40 to 80 mm in soakage pits, soakage wells, on open space etc. and taking out old soiled aggregate complete all as specified and directed.
Surface dressing n exc 15 cm deep in soft/loose soil complete all as specified and directed.
Excavation in trenched n exc 1.50 m in width and n exc 1.50m in depth for foundation , manholes , cesspits, etc n exc 10 sqm on plan and getting out in hard/dense soil complete all as specified and directed
M&l for PCC 1:4:8 type D-2 (40mm graded aggregated) as in foundation and mass concrete complete all as specified and directed.
M&L for brick work with old size fly ash bricks bricks staright or curved on plan exc 6m mean radius built in CM 1:6 complete all as specified and directed.
M&L for brick work with old size fly ash bricks staright or curved on plan to any radius in half brick thick walls built in CM 1:4 complete all as specified and directed.
M&L for broken stone hard core of gauge n exc 63mm deposited spread and levelled in layers n exc 15 cm watered and rammed to a true surfaces complete all as specified and directed
M&L 75mm thick PCC 1:3:6 type C-1 (20mm aggte) as in plinth protection finished fair and even without using extra cement n exc 2m in length and joints filled with bitumen mastic (1:1) complete all as specified and directed
Returning filling hard dense in, including spreading levelling watering and well ramming in layers n exc 25 cm thick complete all as specified and directed
Filling under floor including spreading levelling watering and well ramming in layers n exc 25 cm thick complete all as specified and directed
Removel of surplus hard dense soil to a distance n exc 50m and depositing where directed at a level n exc 1.5m above from the starting point complete all as specified and directed.
M & L for mild steel TMT bars of 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and as directed.
M & L for mild steel TMT bars 5mm dia and over upto including 10mm dia in stirrups, spacers and binders, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and as directed.
M & L for RCC M-25 grade (nominal mix) using 20mm graded aggregates as in foundations, including rafts, footings, foundation beams, plinth beams, bases for columns, etc, basement slabs, under reamed piles and mass concrete complete all as specified and directed.
Use of waste formwork to sides of concrete foundations, footings, bases of columns, raft and beams, sides and soffits (if any) of foundation and plinth beams , and similar work, vertical or to batter, flat surfaces of concrete , surface is required to be fair finished complete all as specified and as directed.
M & L for M-25 grade (nominal mix) using 20mm graded aggregates as in columns, pillars, piers, posts and struts complete all as specified and as directed.
Use of waste formwork to sides of pillars, posts, struts, piers, columns and stanchions, rectangular or polygonal surfaces of concrete , surface is required to be fair finished. complete all as specified and as directed.
M & L for RCC M-25 (nominal mix) using 20mm graded aggregates as in Roof beams, lintel beams/bands, cantilevers, bressummers, lintels over 1.5m span, chajjas etc complete all as specified and as directed.
Use of waste formwork to sides and soffits of floor or roof beams, soffits of lintel beams/ bands, chajjas, beam haunchings, girders, bressum-mers, lintels, cantilevers, shelves including supports overhangs etc, also splays between floors and beams, etc., flat surfaces of concrete , surface is required to be fair finished. complete all as specified and as directed.
M & L for RCC M-25 (nominal mix) using 20mm graded aggregates as in slabs supported on walls, beams and columns in floors, roofs, landings, balconies, canopies, deck slabs and in shelves and the like complete all as specified and directed.
Use of waste formwork to soffits of suspended slabs such as roof slabs, floor slabs, landings and similar work; not exceeding 200mm thick (Horizontal or sloping), flat surfaces of concrete , surface is required to be fair finished. complete all as specified and as directed.
Use of waste formwork to edges of concrete flats, treads, breaks in floors, window cills, concrete railings, openings in concrete walls, floor and roofs n exc 20 cm wide and sides of RCC/PCC bands in walls, horizontal or sloping and similar work exc 10cm but n exc 20cm wide, as roughed finished surface of concrete complete all as specified and as directed.
M&L 15mm thick rendering on brick /concrete work surfaces in CM 1:4 finished fair and even without using extra cement using WPC as per manufactuere instructions complete all as specified and as directed. (WPC is to be measured and paid separately)
M&L 10mm thick redering on brick work surfaces in CM 1:6 finished fair and even without using extra cement complete all as specified and directed
M&L for rendering on brick work or concrete surface in cement mortar (1:4) 10mm thick as in ceiling surfaces finished fair and even complete all as specified and directed.
M&L for preparation of new plaster surfaces applying three coats of lime/ white wash on ceiling complete all as specified and directed.
M & L for preparation of newly plastered surfaces of walls & applying three coat of white wash complete as specified and directed
M&L for preparation of newly plastered surfaces of wall and applying two coats of cement base paint complete all as specified and directed.
S & F Vitreous China squatting pan, `Orissa` pattern, size 580 x 440 mm white, with integral foot rests (excluding flushing cistern and flush pipe) with long body PVC SWR suitable 'P' or 'S' trap complete all as specified and as directed.
S&F PVC valve less syphonic action type, low level flushing cistern, 10 Ltrs capacity . White, with inlet ball valve, float and handle & flush pipe, fixed on walls by drilling holes and using PVC rawl plug of suitable size complete all as specified and as directed.
S & F PVC connection, heavy duty 15 mm bore, 45 cm long with two Nos PTMT nuts at both ends of approved quality complete all as specified and directed
S&F stop cock/angle cock 15 mm dia chromium plated fancy type screwed down light pressure with crutch or butterfly handle screwed both ends for iron pipe or for union complete all as specified and as directed.
S&F Soap dish fixed to plugs with chromium plated brass screws embedded in the wall complete all as specified and as directed.
M&L for 18 to 20mm thick granite ( of any type ) work (table rubbed and polished ) in steps, jambs, pillars, window -cills, cooking platforms and like pointing in white cement (1:2) using marble dust with admixture of pigment to match with shade of granite including laid over 15mm thick screed bed in CM (1:6) complete all as specified and directed.
S&F vitreous china white wash basins, incl waste pipe, brackets, and connecting pipe complete all as specified and as directed. (Make Jaquar KUS WHT 35901 Table top basin Kerovit Mazer KB1086 or equivalent)
S&F pillar taps fancy type cast copper alloy capston headed, chromium plated, screwed down, high pressure with long screwed shank and fly nut, screwed for 15mm bore iron pipe complete all as specified and directed.
S&F Chromium plated bib taps, with capstan heads, screwed down for iron pipe or for brass ferrule & fixed for 15 mm bore pipe complete all as specified and directed.
S&F tubular towel rail aluminium anodised 20mm dia 'D' type 60cm long between flanges complete all as specified and as directed.
M&L PCC 100mm thick (1:4:8) type D-2 using 40 mm graded stone aggregate as in subbase complete all as specified and directed.
M&L non skid ceramic coloured tiles exceeding 0.18 sqm but not exceeding 0.38 sqm 7 to 8mm thick in floors set and jointed in neat cement slurry and pointed in coloured cement to match the shade the tiles over 15mm thick screed bed in CM 1:6 over and including 25mm thick PCC 1:2:4 at B-0 (using 12.5mm graded stone aggregate ) complete all as specified and directed.
M&L for glazed ceramic coloured tiles 300x450x7 to 8mm thick on vertical surfaces of wall such as skirting/ dados ect set and jonted in neat cement slurry and pointed in white cement to match the shade the tiles over and including 10mm thick plaster on stone/brick masonry walls in CM 1:4 complete all as specified and directed.
S&F Anodised aluminiumAnodised aluminium window and ventilator shutters, fixed type without sash bar, aluminium section weighing 0.55 kg/m including necessary joining cleats, glazing clips, rubber packing, anodised aluminium snap beading, screws etc. complete all as specified and as directed.
S & F solid PVC door frame of size 50mm x 47mm made out of 5mm plain colour PVC sheet, reinforced with M.S. square tube and fixing in opening as per specification & drawing complete all as specified and directed.
Supply and fixing of 30mm thick factory made solid panel PVC door shutter (style) consisting of frame made out of MS tubes for top and bottom rail. MS frame shall be covered with heat moulded plain colour PVC 'C' channel having PVC sheet strip of 20mm width stuck inside with solvent cement for stiles and plain colour PVC sheet for top rail, lock rail & bottom rail on either side and as gap insert for top rail and bottom rail, panelling of plain colour PVC sheet to be fitted in the MS frame welded. sealed to the styles and rails with suitable PVC sheet beading and joined together with solvent cement complete all as specified and directed.
S&F figured glass , pin head type 3mm thick fixed with glazing clip or rubber size of glass n exc 0.50 Sqm in each pane complete all as specified and directed.
S&F for aluminium anodised barrel tower bolt 150mm long of extruded section complete all as specified and directed.
S&F for aluminium anodised handle 150mm long fabricated type complete all as specified and directed.
S&F for Butt hinges, extruded aluminium alloy with galvanised mild steel hinge pin, anodised and fixed, type B-21 ISI marked of size 100mm complete all as specified and directed.
Supply only integral water proofing compound @ 3% by weight of cement complete all as specified and directed.
S&F PVC floor trap with grating 75mm dia fixed with cement joint complete all as specified and directed.
S&F rotational moulded synthetic (HDPE) water storage tank 1000 ltrs capacity hoisted and fixed in position all as specified in SSR Part-I complete all as specified and directed.
S & F water tubing 15 mm bore, medium weight, ISI marked galvanized with all fittings and fixed to walls, ceiling or laid in floors complete all as specified and directed.
All as per srl item no 68.00 but 20 mm bore complete all as specified and as directed.
S&F ball valves PTMT with high pressure with epoxy coated aluminium rod and high density plastic ball screwed for iron pipe 20mm bore (min weight 210 gms) complete all as specified and directed.
S & F 110mm bore PVC (SWR) pipes single socketed, in any length with rubber ring joints, laid in trenches or in floors and fixed to wall with clamps complete all as specified and as directed.
S & F 75mm bore PVC (SWR) pipes single socketed, in any length with rubber ring joints, laid in trenches or in floors complete all as specified and as directed.
S & F for 110mm bore PVC (SWR) junction single (Single T) equal or unequal with oval access door complete all as specified and as directed.
S & F 75mm bore PVC (SWR) bends of any radius complete all as specified and as directed.
S & F 110mm bore PVC (SWR) vent cowl complete all as specified and as directed.
S&F mild steel framed work such as grills, grating cooler stands, etc, with ends of bars shouldered and / or riveted, or forged into spikes, framed guard bars, barred iron doors, ladders, framed balusters, walk ways, railing, frame work of water tanks and similar work conforming to Fe 290 Gde E-165 complete all as specified and directed.
M&L for preparation of new steel surfaces over 10 cm width or girth & applying two coats of synthetic enamel paint of 1st quality over a coat of red oxide primer complete all as specified and directed.
M&L roof treatment with APP modified polymeric water proofing membrane, 3mm thick having centre core not less than 100 mircron high molecular high density polyethylene film (HMHDPE) protected on both sides with high polymeric asphaltic mix and 20 mircron HMHDPE film weight not less than 3.0 kg/ Sqm applied with bonding material using blown type bitumen primer Grade 85/25 @ 1.20 Kg/Sqm over bitumen primer conforming to IS -3384 @ 0.40 Kg /Sqm with final coat of bonding bitumen grade 85/25 @ 1.20 Kg /Sqm over APP membrane with all overlaps complete all as specified and directed
Material and labour for 40mm thick (avergae consolidated thickness) PCC (1:2:4) type B-0 using 12.5mm graded stone aggregate laid in slope as in padding, finished even and smooth on existing slope including provision of 'V' shaped groove 6mm wide and 10mm deep at 1.20 metre interval or parts thereof, both ways on top of PCC padding and filled with mastic bitumen of (1:1) proportion complete all as specified and directed.
M&L for Pre-cast cement concrete block masonry with solid blocks type C1 1:3:6 using 20 mm graded aggregate, exc. 10cm in width and setting in CM 1:6 complete all as specified and directed.
M&L for 150mm dia in bore SGSW drain pipes laid in trenches and jointed complete all as specified and directed.
M & L for concrete bed to drain pipes of 150mm bore, including packing under, and haunching against the sides of pipes after they are laid and tested cement concrete 1:4:8 type D-2 complete all as specified and directed
M & L for precast cement concrete (Type B-1, 1:2:4, 20 mm graded aggregate) in landings, cover slabs (for manholes etc.) complete all as specified and directed
M & L for 10 user LLDPE septic tank including excavation in any type of soil for designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, Vent shaft, connection etc., complete for With UPFLOW FILTER INLCUDING MEDIA complete all as specified and directed . Make :- Model No. PWTS-AM-180-01 of Sintex or equivalent.
M & L for soakage wells including excavation in any type of soil, foundation in PCC (1:4:8), walls of honey combed fly ash brick masonry with top ring of RCC 1:1.5:3 type A-1 concrete including intercepting chamber and screen chamber made of fly ash brick masonry in CM (1:6), RCC cover slab in1:1.5:3 type A-1 & SFRC MH cover, interconnecting pipes of RCC/DWC complete filled with brick bats of size 1.80m dia & 3.0 m effective depth all as per drg No. CEBZ/TD/78/2011 sh No 1/2 & 2/2 complete all as specified and directed.
M&L for point wiring with 1.5 Sqmm. (nominal area) single core PVC insulated 1100 Volts, grade multi stranded FRLS copper conductor unsheathed cable in and including PVC rigid non metallic conduit medium grade not less than 20mm dia ISI marked and fittings and accessories concealed in walls/roof/ ceiling with suitable size of sunk type pressed steel modular terminal box and modular white cover plate with frame for suitable module as per site requirements for mounting of modular switches, sockets, fan regulator etc and one green colour cable of 1.5 Sqmm. (nominal area) single core PVC insulated 1100 Volts, grade multi stranded FRLS copper conductor unsheathed as earth wire up to common earth and connected to earth for the following complete all as specified and directed:
One light point/bell point controlled by one way 5 Amps SP switch
One ceiling fan/exhaust fan/Ventillation fan point controlled by one, one way switch.
One 5 pin 5 Amps socket outlet on same board with other switch
S&F of modular switch 1 way 6/10Amp , 1 module, complete all as specified and directed.
S&F of modular socket 6Amp, 2/3 pin combined 2 module complete all as specified and directed.
S&F ceiling rose surface bakelite 3 terminals 63.5 x 17 mm complete all as specified and directed.
S&F exhaust fans AC single phase 230V of size 300mm sweep Steel body with louver including connecting with three core flexible copper wire from ceiling rose to connector of fan including opening for exhaust fan and making good complete all as specified and directed. .
Supply and fixing LED box type tube light fitting 20 watt made up of CRCA sheet with pre wired double sided connections including 1x20 watt retrofit LED tube rod with extruded aluminium body , PC diffuser and inbuilt driver , double sided connection, complete with all accessories internally prewired complete all as specified and directed.
Supply and fixing LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed.
S & F LED light fitting 1x9W/1X10Wbulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable sizecomplete all as specified and directed.
Supply and fixing testing and commissioning energy saving Bldg Security light luminaire 35 watt LED , pressure die cast housing with epoxy powder coated with colour finish and prismatic poly carbonate coverlic cover complete with individual LED lences and complete all as specified and directed..
Supply, installation, commissioning of Water Cooler fully stainless steel, electric driven (single phase), having approx storage capacity 80 Litre and nominal cooling capacity of 40 Litres per hourcomplete all as specified and directed.
S&F of MCB distribution board single pole & neutral with 200 Amps rated bus bar, double door IP-43 DB's , made out of sheet steel enclosure, recessed type, factory made powder coated 4 way, 240 volts suitable for housing MCB's including blanking plate complete all as specified and directed.
S & F of MCB SP, 240 volt, 6 Amp to 40 Amp capacity, 10 KA, 'C' curve complete all as specified and directed.
S & F of MCB SPN, 240 volt, 32 Amp capacity, 10 KA, 'C' curve complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 2 core complete all as specified and directed.
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in soft/ loose soil complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm as in soils complete all as specified and directed.
Removing excavated materials to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5 mtr above the starting point as in soils complete all as specified and directed.
Supply and spread sand in trenches as sand cushioning to underground cable for protection with dry fine river sand and provide required cover after punning down 18CM will be measured and paid complete all as specified and directed.(Note: Thickness of sand cushion after punning down will be measured and paid.)
Supply and laying well burnt sub class ‘B’ bricks ( designated 75) locally available best quality, laid dry in trenches for protection of underground cable all as specified and directed.
Supply and fixing tubes light grade GI tubing 40 mm dia with all fitting laid in trenches, fixed on pole/on wall for cable protection complete all as specified and directed.
Supply & Laying in trenches galvanised steel water tubing of medium grade with all fittings such as bends, elbows, tees, unions, nipples, short pieces etc as required at site of size 20 mm dia complete all as specified and directed.
S&F gun metal gate valves with iron wheel head screwed at both ends for iron pipes complete including dismantling of old unserviceable gate valve fixed at any location of Size 20 mm dia complete all as specified and directed.
KIRTIMAN TRADERS (BID ID -3498921)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.38 MB
GeneralPages8613.pdf
Tender Documents • 0.97 MB
BOQ_831084.xls
BOQ • 2.87 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .