Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Infra Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹4.9 Cr
EMD Value
₹9.7 L
Closing Date
26 Aug 2024, 5:30 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Accessories Division, Lucknow
HINDUSTAN AERONAUTICS LIMITED Accessories Division, Lucknow Post Office, Lucknow - 226 016 Uttar Pradesh, India
Supply, Installation, Testing and Commissioning of Chillers, Pumps, and Cooling Tower at HAL Lucknow.
8876
HAL-ADL/CWA-24AC/2
Works
Accessories Complex - Lucknow Divn - Plant Maintenance
₹0
₹9.7 L
26 Aug 2024
23 Jul 2024
23 Jul 2024
26 Aug 2024
WATER COOLED SCREW CHILLER
Supply & installation of Dial type pressure gauge with syphone and cock.
Supply & installation of Industrial type temparature gauge with thermowell.
Supply & installation of GM drain/purging ball valve with fittings of 25mm dia
Supplying, laying, fixing, testing & commissioning of MS class `C' Chilled/ Condenser water piping without insulation confirming to IS 1239 Part 'II' of 1979 up to date for pipe size up to 150 mm dia and IS-3589 for 200 mm dia pipes and above, minimum thickness of pipes 200 mm dia and above shall be 6 mm, complete with all necessary fittings such as bends, tees, reducers, flanges etc. and supports such as channels, clamps, anti-vibration hangers etc.
Supply and installation of TF quality 50mm thick thermocol insulation on Chilled water lines and valves covered with wire mesh, sand & cement plaster.
Supply, installation, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. BUTTERFLY VALVE(MANUAL) with CI body SS disc, nitrile rubber seal & o- Ring PN 16 pressure rating for chilled/ condensor water circulation as specified
Supply, installation, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. BALANCING VALVE WITH BUILT IN MEASURING FACILITY with CI body flanged construction with EPDM coated disc with protected out pipe insulation & PN 16 pressure rating for chilled/ condensor water circulation as specified:
Supply, installation, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. Y – STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled water circulation including insulation as specified :
Supply, fixing, laying & testing of XLPE AL. armoured power cables for Chillers, Cooling Towers, Pumps etc. complete with cable ties, clamps etc.
3.5 core x 240 sqmm
3.5 core x 16 sqmm
SITC of GI perforated 16G cable trays for supporting electric power & control cables including cable ties, supporting MS hangers side supports etc. in following sizes.
EARTHING
Painting of insulated pipe lines, condensor pipe lines and valves etc. as per standard HVAC practice & colour code.
Electrical Panel: Supply & Installation of Electrical panel for Chilled water plant of following incoming and outgoing specifications: Incoming (ACB Microprocessor based): 2500 A, 4P ACB with Voltmeter/Ammeter/Energy meter (Digital Type). - Outgoing (MCCB Microprocessor based): - for 3 Chillers: 630 A for each chiller - Star-Delta Starter for 50 HP Pumps: 8 Nos. - Star-Delta Starter for 15 HP Motor: 6 Nos. - Switchgear Make: L & T/ SIEMENS. - Wires/Cables: Finolex/Polycab. Busbars with RYB sleeve: Copper (Hindalco or reputed make). - Indicating lamp for outgoing and incomer: Teknic Ammeter/Voltmeter: Salzer/L&T. It must be manufactured and painted (color RAL7032/Siemens Grey) by Siemens/L&T/Schneider Electric authorised panel builders or should be CPRI certified. Authorisation certificate of manufacturer must be produced by vendors at the time of drawing clearance. Drawing must be approved by HAL prior to manufacturing. Line diagram alongwith components used must be as per direction of Engineer-In-Charge.
Electrical Panel: Supply & Installation of Electrical panel for Chilled water plant of following incoming and outgoing specifications: Incoming (ACB Microprocessor based): 1200 A, 4P ACB with Voltmeter/Ammeter/Energy meter (Digital Type). - Outgoing (MCCB Microprocessor based): - for 1 Chillers: 630 A for each chiller - Star-Delta Starter for 50 HP Pumps: 6 Nos. - Star-Delta Starter for 15 HP Motor: 6 Nos. - Switchgear Make: L & T/ SIEMENS. - Wires/Cables: Finolex/Polycab. Busbars with RYB sleeve: Copper (Hindalco or reputed make). - Indicating lamp for outgoing and incomer: Teknic Ammeter/Voltmeter: Salzer/L&T. It must be manufactured and painted (color RAL7032/Siemens Grey) by Siemens/L&T/Schneider Electric authorised panel builders or should be CPRI certified. Authorisation certificate of manufacturer must be produced by vendors at the time of drawing clearance. Drawing must be approved by HAL prior to manufacturing. Line diagram alongwith components used must be as per direction of Engineer-In-Charge.
Supply & installation of Horizontal End Suction- Top Discharge- Mechanical sealed- Back Pullout- Centrifugal Pump coupled with Motor. Shaft MOC : Stainless Steel Casing Material: Cast Iron Impeller Material: Brass Pump Type-Foot Mounted Liquid Type/Application-Water Flow rate-300--320 M3/Hr Head-35 meter (Minimum) Motor Power (Rated)-50HP (Min) Motor RPM:- 1450 (Minimum) Power Supply:- 415± 10% 3Phase Effeciency : Min 80% Connection Size: 200 mm x 150 mm or as per manufacturer's standard Insulation class: F IE Efficiency Class: IE3
Supply & installation of Horizontal End Suction- Top Discharge- Mechanical sealed- Back Pullout- Centrifugal Pump coupled with Motor. Shaft MOC : Stainless Steel Casing Material: Cast Iron Impeller Material: Brass Pump Type-Foot Mounted Liquid Type/Application-Water Flow rate-300--320 M3/Hr Head-27 meter (Minimum) Motor Power (Rated)-50HP (Min) Motor RPM:- 1450 (Minimum) Power Supply:- 415± 10% 3Phase Effeciency : Min 80% Connection Size: 200 mm x 150 mm or as per manufacturer's standard Insulation class: F IE Efficiency Class: IE3
Supply, installation, testing & commissioning of FRP induced draft, cross/counter flow, twin fan, direct driven, site erected cooling tower of capacity as mentioned below based on the parameters given below and complete with PVC Fills, louvers, drift eliminator, weather proof IP 55 TEFC Motor (IE3), propeller fan, FRP basin with additional sump in the bottom of the basin on every outlet point to avoid vortex formation in the condenser water pipeline, hot dip galvanised steel ladder, stainless steel hardware including nut, bolt, washer etc. including all supporting structure & civil foundation required for installation of cooling tower and balancing work with existing cooling towers if any. Duty Parameters: Water Flow : 1600 USGPM Desinged Wet Bulb Temperature: 28 Deg C Water Inlet Temperature: 35-40 Deg C Water outlet Temperare: 30-33 Deg C Cooling Tower Capacity: 400 TR Drawing must be approved by HAL prior to manufacturing.
Misc. civil work like wall cutting for erection of new piping and making wall opening for taking chillers in/out the plant room and their refilling with brick, cement+coarse sand, and matching paint. Dismantling of existing chillers (3 nos), Pumps (9 nos), electrical panels (3 nos) and Cooling Tower (3 nos) and their supporting pillars, if required, and cutting/ blanking/ removal of pipes. Removal of scrap & reposition to nearby warehouse. Civil works like construction of Chiller, pump, and cooling tower foundations. Systematically packing of PVC fills in green cloth with weight of one packet of PVC fills in range of 40-45 Kg. After packing, PVC fills packet to be wrapped with polythene sheet. Repositioning of PVC fills packets at a location as directed by EIC.
Supply of tool kit for repair and maintenance of chillers. 1. Stanley Tool Kit (STMT81243), 2. Bosch GIS 500 Temperature Gun, 3. Digital Anemometer, 4. Gas Analyser for multiple refrigerant (R22, R134a, R410a, R407c, R32) with accuracy 1%, User Interface- graphic display, soft keys, built-in printer, Temp range- 10-49 deg C, Test Pr. 30psig - 500psig, Power Requirement: 12VDC@2A via 220 VAC 50 Hz Adaptor, Sample gas extraction- Pressure from cylinder or system, Approval- CE, UL. 5. Dual Stage Vacuum Pump for Regrigerant Gases, Flow Rate: 12 CFM, Ultimate vacuum: 15 micron, Oil Capacity: 580-600 ml, Make-Totaline/ Value 6. General Tool Kit for Refrigeration and Air Conditioning (3 nos). Each tool kit bag should contain flaring tool set, tube cutter, clamp meter (make-Fluke/HTC), Screw driver set, Allen key set, Refrigerant gas charging line (make- Value) etc, Compound Pressure Gauge, Plier, Adjustable spanner(8"), File, Nose Plier, Swaging Tools, Rechargeable High Intensity Torch Light with charger and overcharging protection etc. Above items must be approved by HAL prior to supply.
HAL-ADL/CWA-24AC/2
Description
Installation
WATER COOLED SCREW CHILLER
Supply & installation of Dial type pressure gauge with syphone and cock.
Supply & installation of Industrial type temparature gauge with thermowell.
Supply & installation of GM drain/purging ball valve with fittings of 25mm dia
Supplying, laying, fixing, testing & commissioning of MS class `C' Chilled/ Condenser water piping without insulation confirming to IS 1239 Part 'II' of 1979 up to date for pipe size up to 150 mm dia and IS-3589 for 200 mm dia pipes and above, minimum thickness of pipes 200 mm dia and above shall be 6 mm, complete with all necessary fittings such as bends, tees, reducers, flanges etc. and supports such as channels, clamps, anti-vibration hangers etc.
Supply and installation of TF quality 50mm thick thermocol insulation on Chilled water lines and valves covered with wire mesh, sand & cement plaster.
Supply, installation, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. BUTTERFLY VALVE(MANUAL) with CI body SS disc, nitrile rubber seal & o- Ring PN 16 pressure rating for chilled/ condensor water circulation as specified
Supply, installation, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. BALANCING VALVE WITH BUILT IN MEASURING FACILITY with CI body flanged construction with EPDM coated disc with protected out pipe insulation & PN 16 pressure rating for chilled/ condensor water circulation as specified:
Supply, installation, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. Y – STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled water circulation including insulation as specified :
Supply, fixing, laying & testing of XLPE AL. armoured power cables for Chillers, Cooling Towers, Pumps etc. complete with cable ties, clamps etc.
3.5 core x 240 sqmm
3.5 core x 16 sqmm
SITC of GI perforated 16G cable trays for supporting electric power & control cables including cable ties, supporting MS hangers side supports etc. in following sizes.
EARTHING
Painting of insulated pipe lines, condensor pipe lines and valves etc. as per standard HVAC practice & colour code.
Electrical Panel: Supply & Installation of Electrical panel for Chilled water plant of following incoming and outgoing specifications: Incoming (ACB Microprocessor based): 2500 A, 4P ACB with Voltmeter/Ammeter/Energy meter (Digital Type). - Outgoing (MCCB Microprocessor based): - for 3 Chillers: 630 A for each chiller - Star-Delta Starter for 50 HP Pumps: 8 Nos. - Star-Delta Starter for 15 HP Motor: 6 Nos. - Switchgear Make: L & T/ SIEMENS. - Wires/Cables: Finolex/Polycab. Busbars with RYB sleeve: Copper (Hindalco or reputed make). - Indicating lamp for outgoing and incomer: Teknic Ammeter/Voltmeter: Salzer/L&T. It must be manufactured and painted (color RAL7032/Siemens Grey) by Siemens/L&T/Schneider Electric authorised panel builders or should be CPRI certified. Authorisation certificate of manufacturer must be produced by vendors at the time of drawing clearance. Drawing must be approved by HAL prior to manufacturing. Line diagram alongwith components used must be as per direction of Engineer-In-Charge.
Electrical Panel: Supply & Installation of Electrical panel for Chilled water plant of following incoming and outgoing specifications: Incoming (ACB Microprocessor based): 1200 A, 4P ACB with Voltmeter/Ammeter/Energy meter (Digital Type). - Outgoing (MCCB Microprocessor based): - for 1 Chillers: 630 A for each chiller - Star-Delta Starter for 50 HP Pumps: 6 Nos. - Star-Delta Starter for 15 HP Motor: 6 Nos. - Switchgear Make: L & T/ SIEMENS. - Wires/Cables: Finolex/Polycab. Busbars with RYB sleeve: Copper (Hindalco or reputed make). - Indicating lamp for outgoing and incomer: Teknic Ammeter/Voltmeter: Salzer/L&T. It must be manufactured and painted (color RAL7032/Siemens Grey) by Siemens/L&T/Schneider Electric authorised panel builders or should be CPRI certified. Authorisation certificate of manufacturer must be produced by vendors at the time of drawing clearance. Drawing must be approved by HAL prior to manufacturing. Line diagram alongwith components used must be as per direction of Engineer-In-Charge.
Supply & installation of Horizontal End Suction- Top Discharge- Mechanical sealed- Back Pullout- Centrifugal Pump coupled with Motor. Shaft MOC : Stainless Steel Casing Material: Cast Iron Impeller Material: Brass Pump Type-Foot Mounted Liquid Type/Application-Water Flow rate-300--320 M3/Hr Head-35 meter (Minimum) Motor Power (Rated)-50HP (Min) Motor RPM:- 1450 (Minimum) Power Supply:- 415± 10% 3Phase Effeciency : Min 80% Connection Size: 200 mm x 150 mm or as per manufacturer's standard Insulation class: F IE Efficiency Class: IE3
Supply & installation of Horizontal End Suction- Top Discharge- Mechanical sealed- Back Pullout- Centrifugal Pump coupled with Motor. Shaft MOC : Stainless Steel Casing Material: Cast Iron Impeller Material: Brass Pump Type-Foot Mounted Liquid Type/Application-Water Flow rate-300--320 M3/Hr Head-27 meter (Minimum) Motor Power (Rated)-50HP (Min) Motor RPM:- 1450 (Minimum) Power Supply:- 415± 10% 3Phase Effeciency : Min 80% Connection Size: 200 mm x 150 mm or as per manufacturer's standard Insulation class: F IE Efficiency Class: IE3
Supply, installation, testing & commissioning of FRP induced draft, cross/counter flow, twin fan, direct driven, site erected cooling tower of capacity as mentioned below based on the parameters given below and complete with PVC Fills, louvers, drift eliminator, weather proof IP 55 TEFC Motor (IE3), propeller fan, FRP basin with additional sump in the bottom of the basin on every outlet point to avoid vortex formation in the condenser water pipeline, hot dip galvanised steel ladder, stainless steel hardware including nut, bolt, washer etc. including all supporting structure & civil foundation required for installation of cooling tower and balancing work with existing cooling towers if any. Duty Parameters: Water Flow : 1600 USGPM Desinged Wet Bulb Temperature: 28 Deg C Water Inlet Temperature: 35-40 Deg C Water outlet Temperare: 30-33 Deg C Cooling Tower Capacity: 400 TR Drawing must be approved by HAL prior to manufacturing.
Misc. civil work like wall cutting for erection of new piping and making wall opening for taking chillers in/out the plant room and their refilling with brick, cement+coarse sand, and matching paint. Dismantling of existing chillers (3 nos), Pumps (9 nos), electrical panels (3 nos) and Cooling Tower (3 nos) and their supporting pillars, if required, and cutting/ blanking/ removal of pipes. Removal of scrap & reposition to nearby warehouse. Civil works like construction of Chiller, pump, and cooling tower foundations. Systematically packing of PVC fills in green cloth with weight of one packet of PVC fills in range of 40-45 Kg. After packing, PVC fills packet to be wrapped with polythene sheet. Repositioning of PVC fills packets at a location as directed by EIC.
Supply of tool kit for repair and maintenance of chillers. 1. Stanley Tool Kit (STMT81243), 2. Bosch GIS 500 Temperature Gun, 3. Digital Anemometer, 4. Gas Analyser for multiple refrigerant (R22, R134a, R410a, R407c, R32) with accuracy 1%, User Interface- graphic display, soft keys, built-in printer, Temp range- 10-49 deg C, Test Pr. 30psig - 500psig, Power Requirement: 12VDC@2A via 220 VAC 50 Hz Adaptor, Sample gas extraction- Pressure from cylinder or system, Approval- CE, UL. 5. Dual Stage Vacuum Pump for Regrigerant Gases, Flow Rate: 12 CFM, Ultimate vacuum: 15 micron, Oil Capacity: 580-600 ml, Make-Totaline/ Value 6. General Tool Kit for Refrigeration and Air Conditioning (3 nos). Each tool kit bag should contain flaring tool set, tube cutter, clamp meter (make-Fluke/HTC), Screw driver set, Allen key set, Refrigerant gas charging line (make- Value) etc, Compound Pressure Gauge, Plier, Adjustable spanner(8"), File, Nose Plier, Swaging Tools, Rechargeable High Intensity Torch Light with charger and overcharging protection etc. Above items must be approved by HAL prior to supply.
HAL-ADL/CWA-24AC/2
Description
Submission of EMD (Scan Copy & Original both, Refer Section-3). Particulars of EMD i) Demand Draft /Bankers Cheque No/Transaction No ii) Date iii) Name of Bank iv) Address of Bank v) Validity of DD/Bankers Cheque
Bid Securing Declaration Form (Refer Section-2) (Please upload in pdf)
Submission of Documents as detailed below:
Authorization Letter/Power of Attorney (IF APPLICABLE) (Please upload copy in pdf)
Proof of Valid Legal Entity. (Ref: Section -3) (Please upload copy in pdf)
PAN Copy (Ref: Section -3) (Please indicate PAN Number & upload PAN copy in pdf )
GSTIN Registraion Copy. (Ref: Section -3) (Please indicate Goods and Services Tax Registration no & upload copy in pdf)
Copy of EPFO Registration (Ref: Section -3) (Please indicate registration no. & upload copy in pdf)
Copy of ESIC Registartion (Ref: Section -3) (Please indicate registration no. & upload copy in pdf)
Proof of Annual Turnover of Last 3 Years-Profit Loss Account & Balance Sheet (Ref: Section -3). (Please upload copy in pdf)
Latest & Valid Solvency Certificate (within the period of 12 Months from the final date of submission of tender) (Ref: Section -3) (Please upload copy in pdf).
Self declaration containing details of communication (Ref: Section -3). (Please indicate e-mail ID, Name & Designation of Contact Person, Mobile No/Landline No)
Proof of experience and Proof of Work in-hand (Ref: Section -3) (Please upload in 'pdf' format)
Compliance to read and understand the Requirement & Scope of Work of the contract. (Refer Section-4 and Section-5)
Undertaking by competent authority (It is desirable to upload signed copy in pdf format)
An undertaking by the party to the effect that he is not debarred or blacklisted by any Govt. Organization /Govt. Undertaking
Undertaking from Bidder that no conditions are imposed in their price bid.
Acceptance to Complete Tender Requirement, Scope of Work, Terms & Conditions mentioned in the bidding document are properly understood and undertaking to comply with them.
Please confirm that your offer is in conformity with tender documents, wherever your offer is silent.
The rates quoted are valid and binding upon the bidder for the entire period of contract and it is certified that the rates quoted are the lowest rates as quoted in any other institution in India under same Terms and conditions as notified in present tender.
I/We give the rights to the competent authority of the Hindustan Aeronautics Limited to forfeit the Earnest Money/Security money deposit by me/us in case of breach of conditions of Tender/Contract.
I/We hereby undertake to provide services as per the directions given in the tender document/contract agreement.
I/We hereby confirm that all information/attachment/data etc. submitted with the offer are true and correct. I/We will be solely responsible for authenticity of submitted documents/data. In case at any stage, it is found that false declaration has been made suitable action as per norms can be initiated against us.
Acceptance for clause 1.24, 1.25 and 1.26 of section-5 of tender document in respect of supervision of work, disposal of scrap, and Certificate of Conformance respectively.
Acceptance to complete the work within Six months from date of work order, if awarded.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
raw.json
RAW_JSON
NIT.pdf
TENDER_DOCUMENT • 0.03 MB
TechnicalComplianceMatrix.xlsm
TENDER_DOCUMENT • 0.02 MB
TenderDocument.pdf
TENDER_DOCUMENT • 0.20 MB
PriceBid.xlsm
TENDER_DOCUMENT • 0.02 MB
Technicalbid.xlsm
TENDER_DOCUMENT • 0.01 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .