Cheif Engineer RRCAT
Office of Chief Engineer CSD RRCAT Indore 452013 MP
Electrical maintenance and miscellaneous works in lab and colony area at RRCAT, Indore.
2022_RRCAT_726786_1
RRCAT/E/2022/20 Dt 24/11/2022
Open Tender
Electrical Works
Works
365 days
RRCAT Indore
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹1.8 L
1 Feb 2023
1 Dec 2022
26 Dec 2022
2 Dec 2022
22 Dec 2022
5 Dec 2022
Amount
Supply and installation of PVC Casing-n-Capping/PVC conduit system including all required accessories and material required for installation is in the scope of item.
20 mm PVC Casing-n-caping/conduit
25 mm PVC Casing-n-caping/conduit
Cable management system : Supply and Installation of PVC cable management system with all accessories. All material required for fixing and installation are in the scope of item.
100x50mm PVC body with cover.
50x50mm PVC body with cover.
ERW MS Conduit :- Supply and installation of ERW MS concealed/open conduit system with all accessories and material required for fixing is in the scope of item.
20mm conduit.
25mm conduit.
Supply, installation, termination, testing and commissioning of FRLS Flexible copper/ telephone/ CAT-6 wire/cable.
1.0 Sq. mm FRLS Flexible copper wire.
1.5 Sq. mm FRLS Flexible copper wire
2.5 Sq. mm FRLS Flexible copper wire
4 Sq. mm FRLS Flexible copper wire
6 Sq. mm FRLS Flexible copper wire
Supply,pulling and termination of 2 pair, 0.5ATC telephone Wire/cable.
Supply, pulling and termination of 4 pairs unshieded twisted pair CAT-6 UTP cable including required hardwares.
Supply,installation, testing and commissioning of C-curve, 10kA SP/DP/TP/FP MCBs.
Supply,installation, testing and commissioning of Single Pole MCBs: (Rating of MCB 6 Amp. to 32Amp. C-curve,Ics-10KA).
Supply,installation, testing and commissioning of double Pole MCBs: (Rating of MCB 6 Amp. to 32Amp. C-curve,Ics-10KA).
Supply,installation, testing and commissioning of tripple Pole MCBs: (Rating of MCB 6 Amp. to 32Amp. C-curve,Ics-10KA).
Supply,installation, testing and commissioning of four Pole MCBs: (Rating of MCB 6 Amp. to 32Amp. C-curve,Ics-10KA).
Supply,installation, testing and commissioning of four Pole MCBs: (Rating of MCB 40 Amp. to 63 Amp. C-curve,Ics-10KA).
Only installation of 2x11watt CFL / 2x18 watt CFL/ 2x36 watt FTL /Bulk head /LED luminaires etc.(upto 7 mtr. height).
Supply and installtion of three point ceiling rose/round block/square block.
Supply and Installation of Batten/Angle Holders.
Upkeeping of LT electrical systems as per tender specifications.
Maintenance and replacement of Geyser / Geyser components viz. heating element, thermostat etc. in 2 KW/3KW storage/Instant type geysers.
Dismantaling of 4X20W flouroscent lamp luminaire or 2x36/1x36W fluorescent lamp luminaire or 2x11W CFL luminaire or 2x18W CFL luminaire or 2x36W CFL luminaire /HPSV /HPMV/ MH luminaire/Bulk head luminaire (upto 7 mtr height) from existing installation.
Repairing / Replacement of LED luminaire driver & PCB.
Repairing LED luminaire upto 10 Watt, 230 volt including repalcement of driver/PCB.
Replacement of LED driver from 11 watt to 35 watt in exiting luminaire.
Replacement of LED driver from 36 watt to 40 watt in exiting luminaire.
Replacement of LED driver from 41 watt to 80 watt in exiting luminaire.
Replacement of LED driver from 81watt to 120 watt in exiting luminaire.
Replacement of LED driver from 121 watt to 160 watt in exiting luminaire.
Replacement of LED driver from 161 watt to 320 watt in exiting luminaire.
Replacement of PCB fitted with 11 watt to 35 watt.
Replacement of PCB fitted with 36 watt to 40 watt.
Replacement of PCB fitted with 41 watt to 80 watt.
Replacement of PCB fitted with 81 watt to 120 watt.
Replacement of PCB fitted with 121 watt to 160 watt.
Replacement of PCB fitted with 161 watt to 320 watt.
Dismantaling of old wiring and acessories on walls/ roof /ceilings from existing installation and stored within 2 kM radious area with proper marking as directed by Deprtment official.
conduits/ casing-n-capings/ducts/Cable management system/cable tray and associated all type of wires/cables etc.
Dismantaling of Panels/DBs/Switch boards
Dismantaling of Switch boards/AC Point/MCB/SFU etc. from walls from existing installation and stored within 2 kM radious area with proper marking as directed by Deprtment offcial.
Dismantaling of Panel/DBs upto 0.5x0.5x0.3 Mtr size.
Dismantaling of Panel of size more than 0.5x0.5x0.3 Mtr to less than 1.0x1.0x0.3 Mtr. size.
Dismantaling of Panel of size more than 1.1 x 1.1 x 0.3 Mtr to less than 2.0x2.0x0.4 Mtr. size.
Dismanteling of Panel of size more than 2.1 x 2.1 x 0.4 Mtr to less than 4.0x4.0x0.5 Mtr size..
Supply,installation, testing and commissioning of ready made VTPN MCB/MCCB DB with protective metal door (IP-42/43) Suitable for MCB/MCCB Incomer and MCB outgoing as under:
Supply,installation, testing and commissioning of IP 43, 4 way vertical TPN DB with metal door fitted with 100 A, Ics 10 kA MCB. The feeders configuration shall be as under. Incoming :- 100 A, Ics 10 kA TP MCCB. Outgoing :- (i) C-6/10/16/20/25/32A,Ics-10KA Single Pole MCBs- 6 Nos (ii) C-40/50/63A,Ics-10KA Three Pole MCBs - 02 Nos
Supply,installation, testing and commissioning of IP 43, 8 way vertical TPN DB with metal door fitted with 100 A, Ics 10 kA MCB. The feeders configuration shall be as under. Incoming :- 100 A, Ics 10 kA TP MCB. Outgoing :- (i) C-6/10/16/20/25/32A,Ics-10KA Single Pole MCBs- 12 Nos (ii) C-40/50/63A,Ics-10KA Three Pole MCBs - 04 Nos
Supply,installation, testing and commissioning of IP 43, 8 way vertical TPN DB with metal door fitted with DPX 160 A, Ics ≥25 kA with electronic release MCCB. The feeders configuration shall be as under. Incoming :- DPX 160 A, Ics ≥25 kA with electronic release TP MCCB. Outgoing :- (i) C-6/10/16/20/25/32A,Ics-10KA Single Pole MCBs- 18 Nos (ii) C-40/50/63A,Ics-10KA Three Pole MCBs- 02 Nos
Supply,installation, testing and commissioning of IP 43, 8 way vertical TPN DB with metal door fitted with DPX 250 A, Ics ≥25 kA with electronic release MCCB. The feeders configuration shall be as under. Incoming :- DPX 250 A, Ics ≥25 kA with electronic release TP MCCB. Outgoing :- (i) C-6/10/16/20/25/32A,Ics-10KA Single Pole MCBs- 18 Nos (ii) C-40/50/63A,Ics-10KA Three Pole MCBs- 02 Nos
Supply, installation, testing & commissioning of ready made SPN DB'S -8 ways having IP-42/43 and protecting metal door without MCB's
Supply,fabrication (by using CR sheet steel) and installation of sheet steel bus duct,cable trays,panel and MS boxes with complete chemical and mechanical process on MS sheet or angle etc.powder coated,rubber gasket,locking arrangement,earthing bolt etc. will be provided on the fabricated item as per requirement and specifications.
Structural steel work at all levels including supply ,cutting, fabricating , welding, surfacing including necessary scaffolding erecting & fixing in position, including painting with primer coat of approved steel primer(Structural steel channels upto and inclusive of 300mm joists upto and inclusive of 350 mm,angle,flats and tees.etc)
Replacement of various types of lamps/ballasts/starters/holders etc. from existing installation above 3 mtr. height in 9-36 watt CFL/18-40 watt tube light fixture.
Power Cabling :
Power Cabling :- (In Ground) Only Installation, testing and commissioning of XLPE/PVC (FRLS) heavy duty power cable 1100V grade aluminium / copper conductor installed 900 mm below in ground by using over burnt bricks including excavation , sand cushioning, protective covering and refilling the trench compacting including watering , leveling the trench, removing the excess soil etc. Size of cable - up to 3/3½/4 core 25 sq.mm
On Wall and trench : Only installation,testing and commissioning of heavy duty power cable/control cable 1100 volt grade upto 3/3½/4core x 25 sqmm. XLPE/PVC insulation aluminium conductor steel armoured.
Supply,installation,testing and commissioning of end joints/termination of power cable by using nickel plated brass double compression gland.
4 corex10sqmm
4 corex16sqmm
4 corex25sqmm
Supply,installation,testing and commissioning of straight through Joints by using push on termination kit.
3½core X 240 Sqmm
3½core X 120/150 Sqmm
4 coreX10/6 sqmm
Supply and installation of Switches/sockets/fan regulators, door bells/bell push switches in existing switch boards etc :
6 Amp. 250 Volts one way switches.
6 Amp. 250 Volts 5 Pin sockets
16/20 Amp.250 Volts one way switches
16/20 Amp.250 Volts 6 PIN Sockets/Universal Power Point
Step type electronic fan regulators for energy efficient fan (two module)
Bell push Switch 6A, 250V.
Supply,installation,testing & commissioning of Door Bells.
Power outlets/Switch Boards : Supply,Installation,testing and commissioning of following modular type switch, socket, RJ-11/RJ-45 sockets etc. Including all acceessories and interconnection of them.
6A SPT modular Switch
16/20A SPT modular Switch.
6A SPT modular Socket.
16A 5 pin modular Socket.
RJ-11 telephone sockets.
RJ-45 network (CAT-6) sockets.
Supply and installation of ISI mark Hylem sheet including cutting of switches/sockete/fan regulators as directed by Department official.
Luminaire : - Supply,Installation,testing and commissioning/Replacement of following LED luminaires and complete with elctronic ballasts, lamps and all accessories with required fixing material or down rod or reinforced PVC pipe (if required).
LED bulk head 10W luminaire, having Lumen out put - ≥ 600 Lumens, Colour temperature- Cool white, IP- 66, Housing- High pressure die cast aluminium, IK - 09, Cover- UV stablized polycarbonate front diffuser, THD- ≤ 10% at full load and Power factor- ≥ 0.90 and as per detail specifications. Removal of existing luminaire with all accessories and storing within RRCAT campus is in the scope of item.
Surface mounted 10 to 13 watt LED integral luminaire with driver in one compact housing. Luminaire should have nominal efficacy ≥ 120 lm/watt, nominal output as 1500 lumen, Colour temperature : 5700K, CRI ≥ 80, IP:65, THDi: < 10% at full load, 2.5 kV surge protection minimum, Optics: exposed lens optics policarbonate, Life Class: L70 @ 50K hrs. & complete with all accessories and driver. Removal of existing luminaire with all accessories. and stored in within RRCAT campus.
Suitable for outdoor surface mounting LED 70 watt, lumen output 7000 lumen, IP65, CRI>70 in compact housing with driver. (Philips BVP281 LED085 CW FG SY5WB 70W PSU or equivalent) or having matching specifications from list of prefered make. Scope shall include removal of existing luminaire with all accessories. and stored RRCAT campus.
Suitable for highbay surface mounting with all accessories, nominal wattage 100 to 105 Watt and lumen output 13000 lumen, IP65, CRI>70 (Philips BY225P LED100S CW NB PSU FG GR V1 or equivalent) or having matching specifications from list of prefered make. Removal of existing luminaire with all accessories. and stored in within RRCAT campus.
Suitable for outdoor installation of 350 watt LED integral flood light with driver in one compact housing. Luminaire should have nominal efficacy ≥ 120 lm/watt, nominal output as 42000 lumen, Colour temperature : 5700K, CRI ≥ 70, IP/IK: 66/8, THDi: < 10% at full load, 4 kV surge protection minimum, Optics: exposed lens optics policarbonate, Life Class: L70 @ 50K hrs. & complete with all accessories and driver. Removal of existing luminair with all accessories and storing within RRCAT campuss is also in the scope of this item.
30 watt, 2X2feet LED integral recess mounted with driver in one compact housing. Luminaire should have nominal efficacy ≥ 100 lm/watt, nominal output as 3000 lumen, Colour temperature : 6500K, CRI ≥ 80, THDi: < 10% at full load, 2.5 kV surge protection minimum, Optics: exposed lens optics policarbonate, Life Class: L70B50 @ 40K hrs. & complete with all accessories and driver. Removal of existing luminaire with all accessories, false ceiling repair and storing within RRCAT campus is also in the scope of this item.
Recess mounted LED type downlighter meeting the following specifications: Luminous flux : 1500 lm +/- 10% , Efficacy(min) : 100 lm/W, Colour tempreture: 6500K, pf: 0.9(min) , THD : less than 10%, CRI: >80 , Optics: High quality diffuser. Removal of existing luminair with all accessories and storing within RRCAT campus is in the scope of item.
Indoor decorative surface/suspended mounted, high efficiency linear (4 feet) 2X22W LED luminaire, with CRCA powder coated housing with nominal efficacy > 100 lm/watt and nominal output as 4000 lumen, Colour tempreture: 6500K, pf: 0.9(min) , THD: < 10%, CRI: >80 , Optics: High quality diffuser complete with all accessories, driver, lamp etc. All required fixing accessories & hardware etc is in the scope of item. Removal of existing luminair with all accessories and storing within RRCAT campus is in the scope of item.
Supply and replacement of 36 watt conventional fluorencent lamp with LED tube light including modification in wiring. Lumen output ≥ 2100, CRI ≥80, Efficacy ≥100 lumen/watt minimum, CCT- 6500K and as per detail specifications. Removal of existing lamp and accessories shall be stored within RRCAT campus.
Supply and installation of GI strip/ bare wire of required size under ground at a depth of 600mm from FGL including excavation,black bitumin painting,backfilling and consolidation og soil. Installation of GI strip along cable tray/wall using GI clamps at interval of 500mm as per site requirement including required hardware as per tender specifications.
G.I Cable Trays:- Supply and installation of 300mm wide having 75mm side channel. ladder type GI cable tray, made out of 2mm MS sheet with rungs 35X15X15 mm with CC spacing of 250mm with coupler plates, prefabricated GI cover on tray, including other required hardware on existing MS support.
SARAF ELECTRICALS
FLASHCUNSULTANT & CONTRACTOR
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .