Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.0 LAccepted-AOC | L1 | Accepted-AOC Accepted | |
| 2 | L2₹22.9 L+₹69,857 (3.15%)Rejected-Finance | L2 | Rejected-Finance Rates are high | |
| 3 | L3₹24.3 L+₹2.1 L (9.38%)Rejected-Finance | L3 | Rejected-Finance Rates are high | |
| 4 | L4₹24.7 L+₹2.5 L (11.3%)Rejected-Finance 19 SAINIK COLONY BAIRAGARH BHOPAL MP 462 030 | BHOPAL | MADHYA PRADESH | 462030 | L4 | Rejected-Finance Rates are high |
Tender Value
₹23 L
EMD Value
₹46,000
Closing Date
17 Aug 2020, 6:00 pmClosed
GE MIS MHOW
GE (MAINT) INF SCHOOL, 75 MALL ROAD MHOW
M AND O OF ELECTRIC SUPPLY INSTLATTIONS INCLUDING REPAIR AND MAINT OF LT UG CABLES AND PUMP HOUSE AND WATER SUPPLY SYSTEM INCLUDING MAINT OF WATER SUPPLY DISTRIBUTION NETWORK AND OTHER CONNECTED WORK AT NEW AMMUNITION DEPOT UNDER GE MIS MHOW
2020_MES_356246_2
GE MIS MHOW/19 OF 2020-21
Open Tender
Miscellaneous Works
Item Rate
334 days
GE MIS MHOW
Please refer tender document
8 documents required · 8 mandatory
₹500
GE MIS MHOW
₹46,000
Yes
27 Oct 2020
29 Jul 2020
19 Aug 2020
29 Jul 2020
17 Aug 2020
3 Aug 2020
Amount
Manning and operation of 11 KV/440 Sub Station including all switch gears installed at New FAD, round the clock in three shifts (each of eight hours) from 0600 to 1400 hrs, 1400 hrs to 2200 hrs and 2200 hrs to 0600 hrs including maintenance of Daily Log Sheets of all 11 KV feeders, 100 KVA DG set and other installed equipments:-
(a) Transformer of capacity 315 KVA -01 Nos
(b) VCB 630 Amps - 02 Nos
(c) APFC Panel 100 KVAR -01 No
(d) Two pole structure -03 Nos
(e) LT panels of various capacities -03 Nos
(f) DG Set of capacity 100 KVA with AMF Panel -01 Nos
(g) Street light panel - 02 Nos
(h) Daily, Weekly, Monthly, Quarterly and Half Yearly Maintenance as per OEM's instruction should be done in the presence of MES Rep and recorded & signed by the operator in a register as specimen given by the dept and obtain signatures of JE, AGE and contractor. (The Register shall be provided and maintained by contractor without claiming any extra cost to the Govt.) (j) The operator employed by the contractor is capable to attend the breakdown complaint on receipt of any complaint from user. If any material required to rectify the said complaint shall be measured and paid under relevant items of this schedule.
(k) The contractor is responsible for the following :- (a) Maintenance of Batteries of DG set (The cost of distilled water and electrolyte and other materials required for maintenance of batteries is deemed to be included in the quoted rate) (b) Cleaning and upkeep of complete installation premises and equipments. (c) Replacement of drop out fuse on structures in the installation to restore elect supply of 33/11 KV. (d) Operator should be capable to attend and rectify minor / major compalints in AOR
Manning and operation of New Ammunition Depot pump house at Adm area including installation/ equipments detailed below by employing one FGM, in three shifts of Eight hours duration of each shift (from 0600 hrs to 1400 hrs, 1400 hrs to 2200 hrs and 2200 hrs to 0600 hrs) including maintaining of log sheets. complete all as specified and directed by Engineer-in-Charge.NOTES:- I. Machinery/Equipment to be manned and operated:-
Machinery/Equipment to be manned and operated:- 1. Monoblock Pump sets 5HP with all accessories- 02 Nos.. 2. Altoch Dosing system -02 sets (4 Pcs). 3. Decrin Dosing Pumps-02 Nos 4. Pump house -01 No. 5. RCC Sump Capacity 25000 Gallon -01 No 6. DG Set Cap 100 KVA -01 No 7. Electric panel of pump set including area lightning.
NOTE:- (for item No 2.00 ) 1. The operator employed by the contractor must be a skilled FGM sub to ITI qualified in appropriate trade with five years of experience in concerned operation field and fully concern to maintenance. 2. The operator must adhered the dress code as directed. 3. The operator must be known to attend the telephone calls and to maintain the record. 4. The operator must be smart in conversation and well behaved. 5. The contractor is responsible for cleaning and upkeep of installation premises and equipments. 6. Daily Log sheets shall be provided and maintained by the Contractor as per specimen given by the department without claiming any extra cost from department. 7. Surrounding area inside the installation should be kept clean & tidy. 8. As per Industrial act one person should not be continued on duty more than six days in a week and he should be given weekly off day for his personal maintenance and one reliever off duty should be employed by the contractor without claiming extra cost from the dept. 9. Plant running record, log book & long sheets for DG Sets, Pump Sets and other eqpts etc. at the installation as per specimen given by the department shall be provided and maintained by the operator as per procedure in vogue. 10. If the installation found unclean (i.e. not upto the satisfactory level of the Engr-in-Charge), a penalty of Rs-500/- for that day will be deducted from the RAR/ Bill. 11. Operator should be capable of attending the minor / major complaints.
11. Daily, Weekly, Monthly, Quarterly and Half Yearly Maintenance as per OEM's instruction should be done in the presence of MES Rep and recorded & signed by the operator in a register as specimen given by the dept and obtain signatures of JE, AGE and contractor. (The Register shall be provided and maintained by contractor without claiming any extra cost to the Govt.) 12. The operator employed by the contractor is capable to attend the the breakdown compalint on receipt of any complaint from user. If any material required to rectify the said complaint shall be measured and paid under relevant items of this schedule.
Excavation in trenches not exceeding 1.5m depth for laying cables and getting out in any type of soil for laying cable/erecting poles , laying pipes and stay assembly all as specified.
Returning and filling in soil including spreading levelling watering and well ramming in layers not exceeding 25cm all as specified.
Supply and spread river sand for cable cushioning in trenches all as specified in clause 19.75 of SSR Part-I/
Note:- For the purpose of payment, punned thickness only will be measured
Supply and laying un-reinforced precast concrete cable cover, class LV, type I, flat, size 250 mm x 150 mm x 40 mm laid in trenches for cable protection all as specified and directed.
Removing excavated soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point.
M&L for LT under ground cable XLPE insulated armoured heavy duty electric with aluminium conductor 1100Volts grade in trenches / passing through pipes of following cross sectional area including taking out existing unserviceable cables.
3.5 core 70 sqmm
3.5 core 50 sqmm
3.5 core 35 sqmm
4 core 25 sqmm
Dismantling of existing unserviceable / broken 11 mtr P.C.C poles.
Supply, transportation and erecting of Prestressed concrete pole 11.0 mtr long 152mm X 152mm at top & 152mm X 260 mm at bottom class 9 all as directed.(painting of pole and excavation/earth work/PCC will be measured & paid for separately)
Material and labour for danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size for LT of size 20. x 15 cm all as specified.
Material and labour for danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size for HT of size 20. x 20 cm all as specified.
Material and labour for ZEBRA painting of PCC poles 11/9 Mtr long near road side upto 1.5 mtr height from pedestal, with two coats of synthetic enamel paints in 30 CM height all as directed by Engr-in-Charge
Dismantling and taking down old unserviceable / rusted/ broken anti climbing device of any type from poles for replacement with new one.
Material and labour for anti climbing device, spikes type fabricate out of MS bars (round, square and flat) incl nuts, bolts, washers and welding in two haves made to shape to suit the cross section of the pole all as specified.
Taking down unserviceable/ rusted / broken stay assembly complete with all accessories including breaking PCC complete all as directed by Engr -I - charge.
Material and labour for stay assembly complete with 30x 30 x 6 mm thick plate and 16 mm dia stay rod all as shown in elect plate NO-1 of SSR-part -1 including stay wire of 7/2.50 mm dia of suitable length all as directed by Engr in charge.
Material and labour for stay assembly complete with 30 x 30 x 6 mm thick plate and 20 mm dia stay rod all as shown in elect plate NO-1 of SSR-part -1 including stay wire of 7/4 mm dia of suitable length all as directed by Engr in charge.
Note for item sl no. 17 and 18: Loop type insulator, stay clamps , excavation and PCC shall be measured and paid separately under relevant item of schedule.
Material and labour for loop type insulator, porcelain, white, brown or green small size, with overall dimensions 65 x 90 mm, clearance of hole 16 mm.
Material and labour for loop type insulator, porcelain, white, brown or green small size, with overall dimensions 140 mm, clearance of hole 25.5 mm.
Material and labour in replacement of old unserviceable LA, non linear resistor type surge arrester (lightning arrestors) confirming to IS 3070 (Part I) having voltage rating 12 KV, rated frequency 50Hz, nominal discharge current 65 KA (Heavy duty) complete with all fittings suitable for 11 KV, 3 phase, earth distribution system complete all as specified.
Dismantling old unserviceable rusted switch break gang operating device complete set including insulators any type any capacity.
Supply & fixing of switch air break gang operated triple pole mechanically operated mounted on insulator (09 insulators)& steel frame with operating mechanism including spring loaded mechanism set of three working from ground level ,11000 volt including locking arrangement of current rating up to 200 Amps (Vertical type): (GI tube must be of heavy grade or medium grade) Make : JAIPURIA / RMCO, ATLAS confirming to IS-9921.
Supply and laying of 20 mm thick stone aggregate size in TWO /FOUR poles structure all as directed by Engr- in- charge.
Material and Labour for painting of 11 KV two pole structure steel pole's, channels complete with stay clamps, nuts and bolts with two coats of aluminium paints of max height up to 10 mtr from ground level incl painting of PCC poles/copping/fencing with two coats of synthetic enamel paint after cleaning the surface thoroughly for colouring all as directed at site.
Filtration and dehydration of Transformer oil and removing sludge by continuous circulation through transformers, oil filtration plant with heater strips and improvement of dielectric strength minimum 60 KV at 2.5 mm gap of electrode and improvement of acidity by minimising the % of acidity using suitable chemical reagent direct from existing Transformer 11 KV of capacity 315 KVA and any make including all as directed and specified by Engr- in - charge.
Note :- (i) The job shall be done at site rates is deemed to be included in above quoted rate.
(ii) Transformers Capacity 315 KVA - 1 Nos and installed at New Ammunition dump area.
Supply and laying of fire retardant /extinguishing elect insulated synthetic mat "INSULATICA 2000"of 2.5 mm thick ±10% conforming to IS: 15652 : 2006, meeting requirements of IS:3043,5216 (Part 1, 2 and 3) IS 8437 and 479 Pub-1 tested for break down strength tensile/elongation ageing properties ,insulation resistance, effects of acid alkaline diesel and transformer oil , leakage current test fire test having min width of 1000 mm ± 20 mm. All allied material such as Pu resin, Chemi bound (Hardener) , Spl PVC adhesive , Liquid primer etc in what so every quantity required to complete the work as per site requirement suitable for all voltage not exceeding 11 KV system with HT trolley mounted.
Disconnecting jumpering & opening ACSR binding from insulator and dismantling /running out of OH conductor of any size and type for carrying out restringing / replacement of OH conductor all as directed by Engr-in-Charge(OH conductor earth continuity wire etc shall be measured for each conductor)
Carrying out restringing of OH conductor of any type or size including binding of insulators using aluminium wire all as directed and specified
M&L for aluminium conductor steel reinforced of any type and size for OH conductor including binding of insulators using aluminium wire all as directed and specified.
Dismantling of insulators any type and size from OH conductor poles.
Supply and fixing of 120 KN Disc type porcelain insulator, vitreous white brown , or green insulator including one galvanized mild steel spindle, two galvanised iron washer and one galvanised iron nut of 150 mm height, 150mm dia for 11000 Volts
Supply and fixing of pin type porcelain insulator, vitreous white brown , or green insulator including one galvanized mild steel spindle, two galvanised iron washer and one galvanised iron nut of 150 mm height, 150mm dia for 11000 Volts
Dismantling of cross arms / clamps of MS channel angle section strips etc complete and setting aside for re use on necessary replacement all as directed by Engr - in Charge.
Material and labour for cross arms, bracings, supports, clamps, MS 'C' channels, equal angles and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive one primer coat, one under coat and one finishing coat of synthetic enamel aluminium paint all as directed and required at site.
Carrying out earth testing for earthing provided for lightning protection system using earth megger before under taking repair/Maint work of earthing and lightning protection system and preparation of test sheet.
M&L for earthing with galvanized steel earth plate electrode of size 600 mm x 600 mm x 6.3 mm buried directly in ground (earth pit not less than 2.25 Mtr below normal ground level), connected to galvanized earth lead strip of size 32 x 6 mm by means of bolts, buts, check nuts and washers of galvanized iron on steel including 40 mm dia medium grade GI tubing for protection of earth lead, MS sheet metal funnel with wire mesh, watering pipe medium grade 20 mm dia, charcoal or coke and common salt in alternative layer of 15 cm compacted thickness all around the electrode with concrete earth pit of PCC 1:3:6 type I, 50 mm thick precast RCC (1:2:4) type BI pit cover reinforced with 8 mm dia deformed bar and suitable handle made of 10 mm dia round bar including GI strip of size 32 mm x 6 mm for extension of earth lead and necessary excavation, earth work, in any type of soil and disposal of spoils to a distance not exc 50 mtr and necessary connection and testing complete all as shown in electrical plate No. 3 and all as directed and specified.
Taking down, broken, disconnected, worn out lighting conductor, earth lead from roof, wall or from structures/ transformers and making good the disturbed surface all as directed by Engineer in Charge
Supply and fixing of earth continuity conductor or earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as aluminium strip 25 x 3 mm braced with GI strips of suitable size to get earthed with all conducting materials in the structures for down conductor all as directed and required at site.
Trimming /cutting of trees branches /bushes obstructing the HT/LT lines making clear distance of 3 RM from the outer conductors of OH Lines all around including removing of branches/bushes of trees from site all as directed
Taking out old unserviceable/burnt out service connection cable for street/security lights including old/broken PVC conduit and clamps from pole upto light fitting for necessary replacement all as directed and specified.
M&L for HRFR PVC insulated, unsheathed, stranded copper conductor cable, three run single core of size 2.5 Sqmm and drawn into conduit including necessary connection complete. (Make-Anchor/Havells/Finolex)
M&L for rigid non-metallic PVC conduit heavy duty of size 20 mm external dia, exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc, to be fixed along the pole all as directed and specified. (Make-Plaza/Pressfit/Havells)
Dismantling and taking down unsv street light fitting of 150 from pole /building complete with GI bracket & fixing arrangement all as directed at site.
Refixing of street light fitting complete with HPSV lamp, ballast, igniters and other accessories for 150 watt lamp incl making connection with 3 runs of 2.5 sqmm single core existing copper conductor PVC insulated and PVC unsheathed cable and testing for entire satisfaction of Engr-in-charge.
Supply and fixing of new generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high power LED as lighting source and top opening separate driver compartment with toughened glass having IP 66 protection and impact resistance of IK07 of capacity 90 Watt, powder coated grey finish including control gear (Inbuilt electronic driver with APFC, Lower THD Output short circuit protection, surge voltage protection, over voltage protection& other reliability test as per IS 15885 Part-2/Sec 13 (Model -ENDURAOMNI PLUS OF MAKE: HAVELLS) or equivalent approved by GE
Carrying out cleaning of breather assembly and filling of silica gel in breather suitable for transformer of capacity 315 KVA
M & L for Topping up of Transformer oil suitable for 11 KV, 315 KVA transformer by filling up insulating oil including filtration to meet the required DI-electrical strength not less than 60 KV at 2.5 mm Air gap.
Supply and fixing of Expulsion fuses 11000 volts single pole rating upto 25 amps
Disconnecting existing tanks, setting aside (or lowering if required) for repairs, cleaning, etc. and hoisting if required reconnecting and refixing in position including cleaning and removing all scale and dirt, etc, from tanks and from mouths of circulating pipes, etc of capacity exceeding 250 Ltrs & not exceeding 500 Ltrs.
Disconnecting existing tanks, setting aside (or lowering if required) for repairs, cleaning, etc. and hoisting if required reconnecting and refixing in position including cleaning and removing all scale and dirt, etc, from tanks and from mouths of circulating pipes, etc of capacity exceeding 500 Ltrs & not exceeding 1000 Ltrs.
Disconnecting existing tanks, setting aside (or lowering if required) for repairs, cleaning, etc. and hoisting if required reconnecting and refixing in position including cleaning and removing all scale and dirt, etc, from tanks and from mouths of circulating pipes, etc of capacity exceeding 1000 Ltrs & not exceeding 2000 Ltrs.
Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position of capacity 500 litres capacity all as specified in SSR Part -I.
Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position of capacity 1000 litres capacity all as specified in SSR Part -I.
Supply and fixed Ball valves, high pressure of PTMT with epoxy coated aluminium rod & high density plastic ball screwed for iron pipe and fixed suitable for 20mm bore dia of pipe ( Minimum weight 20 mm-210 gms) including taking down old Unserviceable one(fixed in repairs).
Supply and fixed Ball valves, high pressure of PTMT with epoxy coated aluminium rod & high density plastic ball screwed for iron pipe and fixed suitable for 25mm bore dia of pipe ( Minimum weight 25 mm-455 gms) including taking down old Unserviceable one(fixed in repairs).
Supply and fixed Ball valves, high pressure of PTMT with epoxy coated aluminium rod & high density plastic ball screwed for iron pipe and fixed suitable for 40mm bore dia of pipe ( Minimum weight 40 mm-690 gms) including taking down old Unserviceable one(fixed in repairs).
M&L for cleaning of under ground Sump of capacity 25000 Gallons, by scraping with the help of hard wire steel brushes and physical cleaning of sump after lowering/drying the water with the help of Pump sets/ manual/ washout valves etc. deposit the muddy and other waste materials and taking them out with the help of manual labour and depositing them at a distance of not more than 50Mtrs all as directed and specified and making sump complete clean and washing properly with bleaching mixed in water and applying two coat of thick quick drying lime wash on entire inner surface of the sump including writing of Date of cleaning with white paint on black painted surface at minimum two places out side /top of sump and painting of steel ladder of tank with two coats of synthetic enamel paint including painting and rewriting of water level indicator with existing colour complete all as specified and directed by Engineer- in – charge. Note:- 1. Necessary T & P and material for the Job will be arranged by contractor and ensure uninterrupted water supply to Mhow cantt. 2. The following operation method of cleaning to be followed:- (a) High pressure cleaning (b) Vaccum Cleaning
Dismantling mono block/centrifugal pump set motor from the existing foundation after disconnecting the inlet / out let pipe connections, disconnecting electrically and taking to civil authorised KIRLOSKAR dealer workshop for repair/strip opening and repairing of pumping sets by replacement the worn out defective/unserviceable parts such as bearing, bush, Gland plate, gland rope check nut, shaft sleeves etc. complete. Reassembling including oiling, greasing replacement of worn out nuts, bolts, gasket etc, and re-fixing in its original position at site, making all connections, commissioning and testing for smooth and noise free operation including bringing back the same from workshop after necessary servicing and testing the same after proper mounting/refixing for entire satisfaction of Engr - in - Charge all as directed/specified of capacity 5 HP.
Disconnecting/ removing the defective starter from the LT panel board and Supply & fixing new Cosmic Star-Reversing Starter 415 volts 3 phase with single phase protection feature with overload relay range 7 to 10 Amp and Contactors suitable for 5 HP electric motor at the existing panel board in position and making electric connections complete all as specified and as directed by Engr-in-Charge.
Rewinding the monoblock induction motor of capacity 5 HP using suitable size super enamelled insulated copper wires replacing the worn out bushes bearing etc complete and reassembling pump and motor lowering the complete assembly in the bore well up to the original depth including jointing weather proof cable with water proof sealing kit of M seal make including testing etc complete for satisfactory operation as directed/specified.
Supply only calcium based granular disinfectant for water treatment, available Chlorine 60% to 70% by weight of the compound as per manufacturers instruct ructions and packed in 45 Kg plastic drums complete all as specified & directed. Make :- Aquafit/Decli bac
Supply only Bleaching powder grade -I ISI marked having stable available chlorine % by mass minimum 35% as per IS 1065,1971 and packed in 25 Kg bag complete all as specified and directed. Make : Vikram.
Supply only Alum Crystal
Taking up or down steel tubing along with fittings such as tee, bends etc fixed to walls and ceilings or laid in flours/trenches and connections incl removal from site of following sizes:-
20mm bore
25 mm bore
40 mm bore
50 mm bore
Material and labour for 'Medium grade' galvanised iron tubes with all fittings and fixed complete fixed on walls and ceilings or laid on floors of following sizes:-make- TATA /Jindal
20 mm bore.
25 mm bore.
40 mm bore
Material and labour for 'Medium grade' galvanised iron tubes with all fittings such as tees bends etc laid in trenches of following sizes:-make- TATA /Jindal
20 mm bore.
25 mm bore.
40 mm bore
50 mm bore
Taking out sluice valves refacing, regrinding and refixing of following sizes :-
80 mm bore
100 mm bore
150 mm bore
Suppply and fixing water supply system layout plan of Ammunition depot made of clear acrylic sheet of 2 mm thick with interior lighting arrangement in cubical enclosure of size 2 M x 1.5 M including hanging on wall and connecting to exisinting socket. Note. Rough Layout plan shall be printed and get approved from GE/AGE E/M for final printing on Acrylic sheet.
Notes :- For all Items of BOQ ; If the quoted amount is less than the estimated cost of the work i.e. 23.00 Lakhs, then the lowest bidder will have to deposit FDR/BGB in favour of Accepting Officer within 07 days of opening of finacial bid for the difference in estimated cost i.e. 23.00 Lakhs & quoted amount. In case the said FDR/BGB is not submitted within stipulated period mentioned above, the contractor shall be banned for 06 months & his bid will be rejected. The said Amt deposited by the lowest bidder will be released after completion of work.
Sameer Auto Engineers
RAJPATI CONSTRUCTION
SUNIL ENTERPRISE
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .