Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.0 LAccepted-AOC 34 B A HOUSE NO 253 3 SECTOR C KALERHARI CHURCH ROAD AMBALA CANTT 133001 | AMBALA CANTT | AMBALA | HARYANA | 133001 | ₹10.0 L Quoted ₹10.4 L | L1 | Accepted-AOC LOWEST |
| 2 | L2₹11.2 L+₹78,116 (7.49%)Rejected-AOC SITE NO 29 30 1ST CROSS NAGAPPA REDDY LAYOUT KAGGADASPURA CV RAMAN NAGAR BANGALORE 560093 | BENGALURU URBAN | KARNATAKA | 560093 | ₹11.2 L+₹78,116 (7.49%) | L2 | Rejected-AOC NOT LOWEST |
| 3 | L3₹14.0 L+₹3.5 L (34.0%)Rejected-AOC SHIV BARI ROAD NEAR KASUMAL HOTEL BIKANER 334003 RAJASTHAN | BIKANER | BIKANER | RAJASTHAN | 334003 | ₹14.0 L+₹3.5 L (34.0%) | L3 | Rejected-AOC NOT LOWEST |
Tender Value
₹10 L
EMD Value
₹20,000
Closing Date
19 Oct 2023, 6:00 pmClosed
Shri S Srinivasa Rao IDSE CWE
HQ CWE ARMY BANGALORE 101 Dickenson Road Bangalore 560042
REPAIR / MAINTENANCE OF DISTRIBUTION TRANSFORMER, HT SWITCH GEARS AND HT DISTRIBUTION SYSTEM UNDER GE (SOUTH) BANGALORE
2023_MES_619124_1
86180/E8
Open Tender
Electrical and Maintenance Works
Item Rate
90 days
HQ CWE ARMY BANGALORE
AS PER TENDER
8 documents required · 8 mandatory
₹500
Yes
GE (SOUTH) BANGALORE
₹20,000
Yes
12 Dec 2023
16 Sept 2023
26 Oct 2023
16 Sept 2023
19 Oct 2023
30 Sept 2023
16 Sept 2023 - 23 Sept 2023
Amount
Disconnecting, diffective Indoor/outdoor HT/LT transformer of following capacity, drain out complete transformer oil storing the same in suitable container to be provided by the contractor, lifting of the top cover, taking out core & core assembly carefully with the help of chain pully/ Crane after disconnecting LT/HT connection to check its condition, cleaning the tank & core taking down & servicing of deffective HT/LT bushes with brass spindle, nuts, bolts, washers insulation lowering back the core assembly after all necessary repair as directed here-in-after refilling filtered transformer dehydration oil taking down & providing the new synthetic rubberised cork sheet making all HT/LT incoming & outgoing connections including testing & commissioning Up to 160 KVAcomplete all as directed.
All as per item No.1 here in before but above 160 KVA up to 250KVA
All as per item No.1 here in before but above 250KVA up to 500KVA
Filtration & Dehydration of transformers oil for transformers, HT/LT OCB, HT VL switches etc through on line filtration equipment to withstand minmum dielectirc strength 40 KV for 1min at 2.5 mm gap and flash at 60 KV without disturbing/switching off system complete all as directed .
Supply and topping up of transformer oil suitable for 11 KV system for transformer/OCBs having 45KV of minimum dielectric strength complete all as directed..
Taking down carefully by Disconnecting all the electrical connections from H.T.and L.T. side, and earthing of unserviceable transformer, from Platform 2/4 pole structure, draining out the transformer oil in clean barrels, loading and unloading of transformer & transportation by vehicle from substation to the repairing workshop for rewinding, reconditioning or any other repairs required, reassembling making the internal H.T. & L.T. connections by fixing the studs, bushings, fitting the top cover by replacing cork sheet including gasket along with conservator including hoisting placing in position and securing properly on 4pole/ 2 pole structure, platform at site, including pouring in the transformer oil in the transformer reinstallation, commissioning and testing Transformer capacity up to 125 KVA complete all as directed. Note: (i) U/S items required for repairs shall be measured and paid under relevant item of this schedule. Transformer oil with die electric strenght not less than 40KV either new or filtered shall be filled and shall be measured and paid separately under respective item.
All as per item No.4 here in before but Transformer capacity Above 125 KVA up to 250KVA
All as per item No.4 here in before but Transformer capacity Above 250KVA up to 500KVA
M&L for opening of top cover of transformer 11/0.433 KV including draining out required transformer oil keeping in safe custody in a dry and clean container, taking out top cover disconnecting HT/LT connnections internally and externally for replacement of unserviceable items(to be paid seperately) reconnecting after replacement of defective parts, re assembling and refitting of top cover and refilling of transformer oil including heating and testing complete for the following capacities of Transformer capacity upto 125 KVA complete all as directed.
All as per item No.5 here in before but Transformer capacity above 125 KVA upto 250 KVA
All as per item No.5 here in before but Transformer capacity above 250 KVA upto 500 KVA
M&L for rewinding of HT coils of different type/capacity and make of transformer with superior quality super enamelled copper winding wire/strip of approved make of suitable gauge and number of turns alongwith allied materials such as cork sheet, fibre glass insulation/paper isulation cotton, empire tape and wooden blocks, bolts, nuts and washers, soldering and other packing materials etc complete all as directed. .
All as per ser Item .6 here in before but for copper winding strip of any size for L.T. coils of transformers.
M&L for heat treatment at the workshop furnance of complete core before and after re-assembly of coil into limps after rewinding for transformer capacity upto 500 KVA complete all as directed. .
Supply & fix LT bushings 433V of suitable size for outdoor/ indoor type transformer of the capacity Upto 100 KVA complete all as directed.
All as per item No.9 here in before but above 100 KVA upto 200 KVA
All as per item No.9 here in before but above 200 KVA upto 500 KVA
Supply of fix HT bushings 11KV of suitable size for outdoor/indoor type transformer of capacities Upto 100 KVA
All as per item No.10 here in before but above 100 KVA upto 200 KVA
All as per item No.10 here in before but above 200 KVA upto 500 KVA
Supply & fix brass stud (for LT433V side)of suitable size complete with one chuck nut, two nuts, washers and rubber seal, all as per sample for outdoor/ indoor type transformer of the capacity Upto 100 KVA complete all as directed.
All as per item No. 11 here in before but above 100 KVA upto 200 KVA
All as per item No.11 here in before but above 200 KVA upto 500 KVA
Supply and installation connecting electrically & commissioning switch air break, gang operated, tripple pole mounted on insulators 12 Nos and steel frame with operating mechanism in worked from ground level, drop out fuse, for current rating upto 200 amps and working voltage 11000 volts all as required at site all as directed. Make: Jaipuria/BHEL
M&L for cross arms, bracings, supports, clamps and back plates fabricated from steel section including nuts, bolts, washers, welding bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of alumn paint complete all as specified and directed.
Taking out U/S HT cables safely from trenches of size 95 sqmm to 150 sqmm and depositing to MES store yard for reuse after removing faults complete all as specified and directed by Engr in Charge.
Laying fixing or passing through pipe only HT cables of size 95 sqmm to 150 sqmm in trenches after removing faults and jointing properly ( Joint will be measured and paid separatlely under respective items of BOQ) Complete all as directed. ( Serviceable old cable retrieved under ser item above will be used )
Excavation in trenches in any type of soil n exc 1.5 mtr in width and n. exc 1.5 mtr in depth and getting out all as required for laying of cables complete all as specified and as directed..
Returning filling, in including spreading ,leveling, watering and well ramming in layers not exc 25 cm each all as required complete all as specified and as directed...
Removing excavated material to a distance not exceeding 50 meters and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and as directed.
M&L for sand cushioning to under ground cables 8 cm thick before laying the cable and 15 cm, thick after laying, stretching and testing the cable complete all as specified and as directed..
Unreinforced precast concrete cable cover HV type size 380mm x 180mm x40mm , laid flat across the cable length all as per specification and directed
M&L for XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty ) with aluminium conductor, 11/6.35KV grade, suitable for earthed system, with aluminium conductor, 3 core 95 Sqmm complete all as specified and as directed. Make: Havells/Paragon/Polycab/Gloster
Taking out U/S Vacuum Circuit Breaker 630A rating having working voltage 11000V from HT panel for repairs and strip opening complete all as required. Seggregating serviceable and un serviceable parts.Cleaning to remove complete carbon contents from the dismentled parts. Reassembling after replacement of u/s parts and adjustment for smooth functioning of the circuit breaker. Testing complete after installation of vacuum cicuit breaker in HT panel to the satisfaction of Engr in Charge complete all as specified and as directed. ( Unserviceable parts required to make VCB serviceable will be measured separately under respective items detailed here in after.)
Supply only vacuum intereputer 630A 11KV rating suitable for VCB as per Sample per phase per intereputer all as required.
Supply only porcelain bush for connection stud complete with insulating rubber sleeve as per sample for VCB of 630A 11KV rating.
Supply only rose contact assy as per sample for VCB of 630A 11KV rating.
Supply only fixed contact assy as per sample for HT panel of 630A 11KV rating.
Supply and fix indicating lamp LED type suitable for any working voltage as per site requirement, red, yellow, white or green all as required or directed.
Supply and fix in replacement motor & gear assembly for spring charging suitable for VCB 11000 Volts matching with existing complete all as specified and directed.
Supply and fix in replacement power pack with battery back up suitable for VCB 11000 Volts matching with existing complete all as specified and as directed.
Supply and fix in replacement closing coil assembly suitable for VCB 11000 Volts matching with existing complete all as specified and directed.
Supply and fix in replacement tripping coil assembly suitable for VCB 11000 Volts matching with existing complete all as specified and directed.
M&L for indoor type 11KV/110V potential transformer for VCB, 50Hz solidly grounded, accuracy class 0.5 for metering, 3 P for protection, rated burden both winding 100VA each, heremetically sealed, to eliminate breathing and prevent air & moisture, secondary terminal but should be partitioned so as to house the metering terminals separately from protection & various terminal connectors providing sufficient earth clearance complete all as specified and directed.
S & F Breather assembly for the transformer as per exisiting sizes all as specified and as directed including filling of Silica gel required for breather complete all as specified and directed.
S & F Silica gel complete all as specified and directed.
Supply & fix in replacement of lightening arrestor metal oxid type complete with all fittings transmission class discharge capacity 65 Kilo Amps suitable for 11000 volts grade complete all specified and as directed.
Supply & fix in replacement of explusion fuse unit 11 KV drop out up to 25 Amps complete all specified and as directed.
S&F cable jointing kit for 11 KV (earthed) grade cable for indoor termination Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sq mm. complete all as specified and directed. Make: Birla 3M / Raychem / Denson
S&F cable jointing kit for 11 KV (earthed) grade cable for indoor termination Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sq mm to 185 sqmm complete all as specified and directed... Make: Birla 3M / Raychem / Denson
S&F cable jointing kit for 11 KV (earthed) grade cable for outdoor termination Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sq mm complete all as specified and directed. .Make: Birla 3M / Raychem / Denson
S&F cable jointing kit for 11 KV (earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sq mm to 185 sqmm complete all as specified and directed. Make: Birla 3M / Raychem / Denson
S&F cable jointing kit for 11 KV (earthed) grade cable straight through joint cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sq mm complete all as specified and directed. Note:- Excavation, earth work, sand , Pcc cover, will be measured and paid seperately under respective items. Make: Birla 3M / Raychem / Denson
S&F cable jointing kit for 11 KV (earthed) grade cable straight through joint Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sq mm to 185 sqmm complete all as specified and directed. Note:- Excavation, earth work, sand , Pcc cover, will be measured and paid seperately under respective items. Make: Birla 3M / Raychem / Denson
M&L for finding out cable fault of HT cables of any sizes using the cable fault indicator all as specified and as directed . Note: Hiring / Providing of the HT cable fault indicator is deemed to be included in the quoted rate .
Removing old coarse stone aggregate, and supply and spraying new coarse stone aggregate at site of size 40mm grade inside the area of sub stations at various locations complete all as directed. Note:- Removed stone aggregate shall be reused .
Repair/Maintenance , cleaning, dusting and servicing agsting Vacuum Circuit Breakerin in existing make of Areva , HT 11 KV,50 Hz , 630 Amp indoor switch gear panel by Grounding of complete panel live parts, through cleaning, visual checking, tightness checking, and servicing of breaker panel including breaker carriage along with associated mechanism , metering panel, busbar/cable chambers, motorised spring charging mechanism , DC shunt trip/close coils, operation counter, manual spring charging mechanism , relays, meters , indicators , heater coil, aux supply SMPS , replacing of worn out parts and fuses , applying petroleum jelly to moving and fixed mechanical parts for its smooth functioning all as specified and directed by the Engineer in charge. Note :- All VCB/RMU/HT switch Gears & CSS are repair through OEM only.
Repair/Maintenance ,cleaning, dusting and servicing, for the smooth functioning of 3 way compact RMU, HT 11 KV , 630 Amp, 3 phase 50 cycle by Grounding of complete panel live parts, thorough cleaning, visual checking, tightness checking, and servicing of breaker panel including breaker carriage along with associated mechanism , metering panel, bushbar/cable chambers , self powered over current and earth falult relay, T-off SF6 circuit breaker module in existing make of ABB , mechanical fault/on/off indicator etc including refilling of SF6 gas and replacing worn out parts when required etc and confirming smooth reliable operation of RMU unit all as specified and directed. Note :- All VCB/RMU/HT switch Gears & CSS are repair thorugh OEM only
M & L for Repair/Maintenance , Cleaning, dusting and servicing Oil circuit Breakers HT 11 KV, 50 Hz, 400 Amps capacity by Grounding of complete panel live parts, thorough cleaning, visual checking, tightness checking, and servicing of breaker panel including breaker carriage along with associated mechanism , metering panel, bushbar/cable chambers, DC shunt trip/close coils, operation counter, manual spring charging mechanism , relays, meters , indicators , aux supply SMPS , replacing of worn out parts and fuses carefully for its smooth functioning in existing make of AEI complete all as directed by the Engineer in charge. Location : Pump House 515ABW Note :- All VCB/RMU/HT switch Gears & CSS are repair thorugh OEM only
Repair/Maintenance ,cleaning, dusting and servicing of standalone/Compact substation SF6 Circuit Breaker, HT 11 KV, up to 630 Amp , 3 phase 50 cycle totally enclosed out door type application switch gear by Grounding of complete panel live parts, thorough cleaning, visual checking, tightness checking, and servicing of breaker panel including breaker carriage along with associated mechanism , metering panel, bushbar/cable chambers, motorised spring charging mechanism , DC shunt trip/close coils, operation counter, manual spring charging mechanism , relays, meters , indicators , heater coil, aux supply SMPS , replacing of worn out parts and fuses , applying petroleum jelly to moving and fixed mechanical parts for its smooth functioning in existing make of ABB all as specified and directed by the Engineer in charge. Note :- All VCB/RMU/HT switch Gears & CSS are repair thorugh OEM only
Decarburizing/cleaning complete HT 11KV, 3 phase independent bus bar, bus bar chamber of HT panel electrification after removing the complete bus bar spout, circuit spout from the bus bar chamber, cleaning with CTC and ensure proper decarburizing, re-fixing the same after applying backtol (Red) solution to the spout, checking all the connections, tightening the nuts, bolts thimbles for incoming and outgoing system in existing make of Areva complete all as specified and directed, rate quoted is inclusive of bactol red, CTC & cotton waste provided by contractor. Note :- All VCB/RMU/HT switch Gears & CSS are repair through OEM only
Aavani BUILDERS AND CONTRACTORS
M/s Rohit Construction Co.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .