EE ENM M6
DELHI JAL BOARD MU BLOCK PITAMPURA DELHI-34
Improvement of electrical system by replacement of old LT Panel with allied works at 180 SFS BPS Ashok Vihar in AC-17.
2022_DJB_232986_2
NIT NO. 19 (M-6)
Open Tender
Miscellaneous Works
Item Rate
30 days
EE ENM M6
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
Account No 50448339804
₹7,800
Yes
29 Dec 2022
13 Dec 2022
20 Dec 2022
13 Dec 2022
20 Dec 2022
13 Dec 2022
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1.01 | Dismantling of existing motor starting / electrical system after disconnecting incoming and outgoing connections, removing the existing material using gas cutter /other tools and tackles etc. as per site requirement. | 1 | Job | 80 | ₹80 |
| 1.02 | Supply / Fabrication of L T Panel Board cubical type, floor mounting, dust & vermin preventing construction of the minimum size 1000 X 1000 X 300 mm, suitable for indoor fixing, made out of 16 SWG CRCA sheet (frame of 14 SWG), with provisions for cable entry from bottom and having chambers as described below. The panel should have separate cable alleys and bus bar alleys. It should be suitable for operation and maintenance from the front and having doors complete with locks etc. for each chamber. The rating of main bus bars has to be 100 Ampere for three phases and half for the neutral in Aluminium construction duly sleeved with phase indicating heat shrinkable Sleeves. It should painted through powder coating process and with complete provisions suitable for all the switchgears as below to be fitted / installed properly with complete mounting accessories as per requirement with complete internal connections of switchgears and control gears with the main bus bars in the Panel through copper cable or bus bars along with making all the required wiring connections for all measuring and indicating instruments with all the accessories, thimbles, ferrules etc. complete in all respect as per requirement. The Panel should have chambers and insertions as per following details. Make for following Switchgears- L&T/ Schneider/ C&S/ DJB approved. Make for following metering instruments -L&T/ Schneider/ AE/ DJB approved.One Changeover Chamber having following insertions-100 Amp 415 V Changeover Switch - 01 No.One Incomer Chamber having following insertions-Moulded Case Circuit Breaker (MCCB) of rating 100 Amp, Triple Pole, 415V, AC of breaking capacity of 36 KA or more - 01 No. One Metering Chamber for the Incomer having following insertions-Ampere Meter 96X96 mm Digital type - 01 No. Volt Meter 96X96mm Digital type. -01 No.Ampere Meter selector switch. - 01 No. Volt meter selector switch. - 01 No. Indicating Lamp, Led type for Three Phases -03 Nos.MCB, 6 Amp, SP, ‘C’ Curve. - 03 Nos. Current Transformer 100/5 ampere. - 03 Nos. Three Outgoing Chambers with each having following insertions-Moulded Case Circuit Breaker (MCCB) of rating 60/63 Amp, Triple Pole, 415V, AC of breaking capacity of 36 KA or more - 01 No. Ampere Meter 96X96 mm Digital type - 01 No. Ampere Meter selector switch. - 01 No. Indicating Lamp, Led type for Three Phases -03 Nos.MCB, 6 Amp, SP, ‘C’ Curve. - 03 Nos. Current Transformer 60/5 ampere. - 03 Nos. One Outgoing Chamber having following insertions-Moulded Case Circuit Breaker (MCCB) of rating 30/32 Amp, Triple Pole, 415V, AC of breaking capacity of 36 KA or more - 01 No. Indicating Lamp, Led type for Three Phases -03 Nos.MCB, 6 Amp, SP, ‘C’ Curve. - 03 Nos.One Outgoing Chamber having following insertions-MCB, 63 Amp, Four Pole ‘C’ Curve. - 02 Nos. | 1 | No. | 80 | ₹80 |
| 1.03 | Loading, Unloading, Cartage and Transportation charges for the above Panel up to the site including charges of heavy labour etc. | 1 | Job | 80 | ₹80 |
| 1.04 | Fabrication and supply of base frame made out of Angle Iron of suitable size for fixing the above Panel and suitable for making outgoing /incoming cable entries in the panel. It should be duly painted and ready with provisions for installing at the site. | 1 | Job | 80 | ₹80 |
| 1.05 | Fixing of new base frame at the site with the help of fasteners / welding and grouting of nut bolts and including all other work as per site requirements and Fixing the new L T Panel at the newly fixed base frame by lifting the panel board and placing it at the base frame properly and fixing it to the frame by nut bolts as requirement. | 1 | Job | 80 | ₹80 |
| 1.06 | Making the incoming connections to the Panel by making required Cable connections between the main supply and the panel after laying and proper thimbling etc. of cable including providing & fixing of consumables as per requirement. | 1 | Job | 80 | ₹80 |
| 1.07 | Supply and installation of Star Delta Starter Panel, cubical type, Wall mounting, made out of CRCA sheet, having 32/63 Amp TP MCB as incomer, 3 nos. of 40 Amp 3 Pole contactors with Auxiliary Contacts, Overload Relay of range 22 to 30 Amp with Auto & manual resetting mode, Single Phase Preventor with LED Indications, with protections against- Phase Imbalance, Phase reversal, Single Phasing, having Ammeter & Voltmeter with voltage Selector Switch, Electronic Timer for automatic changeover – Star to Delta, On-off Trip indications, On/Off Switches, Auto/Manual mode, properly laid down wires, bunched with cable Ties with ferrules for easy identification, mounted on separate CRCA mounting plate of 2mm thickness & fitted in the Starter Panel and fixing the starter at site with all required works.Make for complete Starters- L&T/Schneider/C&S/DJB approved. | 2 | No. | 80 | ₹160 |
| 1.08 | Making the outgoing connections of MCCBs by Connecting MCCBs to the starters Through existing cables or by extending the cables as per site requirement after relaying of the cables as required, proper thimbling and tapping etc. including providing & fixing of material as per requirement. | 2 | Job | 80 | ₹160 |
| 1.09 | Making the outgoing connections of Starters by Connecting starters to the Motors Through existing cables or by extending the cables as per site requirement after relaying of the cables as required, proper thimbling and tapping etc. including providing & fixing of material as per requirement. | 2 | Job | 80 | ₹160 |
| 1.1 | Testing and Commissioning of the Panel Board and starters first at NO LOAD and then at ON LOAD and Operations as per the satisfaction of engineer in charge. | 1 | Job | 80 | ₹80 |
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
Tender Document • 1.74 MB
BOQ_302852.xls
BOQ • 0.25 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .