Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹41.7 LAccepted-AOC | L1 | Accepted-AOC Being lowest tenderer | |
| 2 | L2₹43.2 L+₹6,720 (0.16%)Rejected-Finance SHOP NO 10 BMC SHOPPING CENTRE MITHA NAGAR GOREGAON WEST MUMBAI 400 104 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400104 | L2 | Rejected-Finance Being other than lowest tenderer | |
| 3 | L3₹44.0 L+₹85,945 (1.99%)Rejected-Finance A 63 ELDECO COUNTY PHASE II RAJGARH JHANSI U P 284135 | JHANSI | JHANSI | UTTAR PRADESH | 284135 | L3 | Rejected-Finance Being other than lowest tenderer | |
| 4 | L4₹48.5 L+₹5.3 L (12.4%)Rejected-Finance | L4 | Rejected-Finance Being other than lowest tenderer |
Tender Value
₹49.5 L
EMD Value
₹99,000
Closing Date
6 Sept 2021, 6:00 pmClosed
GE (NW) KUNJALI
DR HOMI BHABHA ROAD, NAVY NAGAR, COLABA, MUMBAI - 400 005
8406 REPAIR MAINTENANCE OF LT DISTRIBUTION NETWORK INCLUDING FEEDER PILLAR LT CABLES LT SWITCHGEARS AND COPE POINTS AT NAVAL DOCKYARD UNDER GE NW KUNJALI
2021_MES_466482_1
8406/E8
Open Tender
Civil Works
Item Rate
183 days
GE (NW) KUNJALI
Please refer tender documents
7 documents required · 7 mandatory
₹500
Yes
GE (NW) KUNJALI
₹99,000
Yes
27 Oct 2021
9 Aug 2021
8 Sept 2021
16 Aug 2021
6 Sept 2021
23 Aug 2021
9 Aug 2021 - 16 Aug 2021
Amount
Supply, fabrication, installation, testing & commissioning of LT Panel board / Feeder piller box, indoor type, dust and vermin proof, made out of 3.15 mm thick CRCA sheet, front & back openable doors having vertical COPPER bus bar of capacity 1000 amps for phases and for neutral including powder coated Siemens GREY painting, internal wiring with suitable size of stranded copper conductor cable, PCC foundation, supporting channels, cable termination,cable gland etc complete at Vajrabahu Fire pump house including taking down old panel all as directed and suitable to accommodate the following switch gears and meters :- INCOMING: a) MCCB 630A mps 4pole, 36 KA,Thermal magnetic - 1 Nos (Incomer) OUTGOING: b) MCCB, 4 pole 250 Amps, 25KA,Thermal magnetic - 2Nos (Out going) c) MCCB, 4 pole 100 Amps, 25KA,Thermal magnetic - 1Nos (Out going) d) ON LOAD Changeover 630A 4 pole - 01 No. e) 75hp FASD starter- 01 No. e) 15 hp FASD starter -01 No. f) VAF meter class 1with CT's - 1 No g) indication lamps (R,Y,B) LED type - 1 set MAKE of MCCB : Schinder/ Legrand/Seimens/L & T
Supply, fabrication, installation, testing & commissioning of DC supply LT Panel board / Feeder piller box, indoor type, dust and vermin proof, made out of 3.15 mm thick CRCA sheet, front & back openable doors having vertical copper bus bar of capacity 1200 amps for phases and for neutral including powder coated RED color painting, internal wiring with suitable size of stranded copper conductor cable, PCC foundation, supporting channels,cable termination,cable gland etc complete at West Wall including taking down old panel all as directed and suitable to accommodate the following switch gears and meters :- INCOMER: a) ACB 800 Amps 4pole, 36 KA EDO type - 1 Nos (Incomer) OUTGOING: b) MCCB, 4 pole 400 Amps, 36KA,Thermal magnetic - 1 Nos (Out going) c) MCCB, 4 pole 250 Amps, 25KA,Thermal magnetic - 1 Nos (Out going) d) MCCB, 4 pole 100 Amps, 16/18KA,Thermal magnetic - 1 Nos (Out going) g) VAF meter class 1with CT's - 1 No g) indication lamps (R,Y,B) LED type - 1 set MAKE of MCCB : Schinder/ Legrand/Seimens/L & T
Supply, fabrication, installation, testing & commissioning of DC supply LT Panel board / Feeder piller box, indoor type, dust and vermin proof, made out of 3.15 mm thick CRCA sheet, front & back openable doors having vertical copper bus bar of capacity 1200 amps for phases and for neutral including powder coated RED color painting, internal wiring with suitable size of stranded copper conductor cable, PCC foundation, supporting channels,cable termination,cable gland etc complete at West Wall including taking down old panel all as directed and suitable to accommodate the following switch gears and meters :- INCOMER: a) ACB 800 Amps 4pole, 36 KA EDO type - 1 Nos (Incomer) OUTGOING: b) MCCB, 4 pole 400 Amps, 36KA,Thermal magnetic - 1 Nos (Out going) c) MCCB, 4 pole 630A Amps, 36KA,Thermal magnetic - 1 Nos (Out going) d) VAF meter class 1with CT's - 1 No e) indication lamps (R,Y,B) LED type - 1 set MAKE of MCCB : Schinder/ Legrand/Seimens/L & T
Supply, fabrication, installation, testing & commissioning of DC supply LT Panel board / Feeder piller box, indoor type, dust and vermin proof, made out of 3.15 mm thick CRCA sheet, front & back openable doors having vertical copper bus bar of capacity 1200 amps for phases and for neutral including powder coated RED color painting, internal wiring with suitable size of stranded copper conductor cable, PCC foundation, supporting channels,cable termination,cable gland etc complete at North Wall including taking down old panel all as directed and suitable to accommodate the following switch gears and meters :- INCOMER: a) ACB 800 Amps 4pole,36 KA EDO type - 1 Nos (Incomer) OUTGOING: b) MCCB, 4 pole 400 Amps,36KA,Thermal magnetic - 1 Nos (Out going) c) MCCB, 4 pole 250 Amps,25KA,Thermal magnetic - 1 Nos (Out going) d) MCCB, 4 pole 100 Amps,18KA,Thermal magnetic - 1 Nos (Out going) g) VAF meter class 1with CT's - 1 No g) indication lamps (R,Y,B) LED type - 1 set MAKE of MCCB : Schinder/ Legrand/Seimens/L & T
Supply, fabrication, installation, testing & commissioning of DC supply LT Panel board / Feeder piller box, indoor type, dust and vermin proof, made out of 3.15 mm thick CRCA sheet, front & back openable doors having vertical copper bus bar of capacity 1200 amps for phases and for neutral including powder coated RED color painting, internal wiring with suitable size of stranded copper conductor cable, PCC foundation, supporting channels,cable termination,cable gland etc complete at East Wall including taking down old panel all as directed and suitable to accommodate the following switch gears and meters :- INCOMER: a) ACB 800 Amps 4pole,36 KA EDO type - 1 Nos (Incomer) OUTGOING: b) MCCB, 4 pole 400 Amps,36KA,Thermal magnetic - 1 Nos (Out going) c) MCCB, 4 pole 630A Amps,36KA,Thermal magnetic - 1 Nos (Out going) d) VAF meter class 1with CT's - 1 No e) indication lamps (R,Y,B) LED type - 1 set MAKE of MCCB : Schinder/ Legrand/Seimens/L & T
Supply, fabrication, installation, testing & commissioning of DC supply LT Panel board / Feeder piller box, indoor type, dust and vermin proof, made out of 3.15 mm thick CRCA sheet, front & back openable doors having vertical copper bus bar of capacity 1200 amps for phases and for neutral including powder coated RED color painting, internal wiring with suitable size of stranded copper conductor cable, PCC foundation, supporting channels,cable termination,cable gland etc complete at East Wall including taking down old panel all as directed and suitable to accommodate the following switch gears and meters :- INCOMER: a) ACB 800 Amps 4pole, 36 KA EDO type - 1 Nos (Incomer) OUTGOING: b) MCCB, 4 pole 400 Amps, 36KA,Thermal magnetic - 1 Nos (Out going) c) MCCB, 4 pole 250 Amps, 25KA,Thermal magnetic - 1 Nos (Out going) d) MCCB, 4 pole 100 Amps, 16/18KA,Thermal magnetic - 1 Nos (Out going) g) VAF meter class 1with CT's - 1 No g) indication lamps (R,Y,B) LED type - 1 set MAKE of MCCB : Schinder/ Legrand/Seimens/L & T
Supply, fabrication, installation, testing & commissioning of DC supply LT Panel board / Feeder piller box, indoor type, dust and vermin proof, made out of 3.15 mm thick CRCA sheet, front & back openable doors having vertical copper bus bar of capacity 1200 amps for phases and for neutral including powder coated RED color painting, internal wiring with suitable size of stranded copper conductor cable, PCC foundation, supporting channels,cable termination,cable gland etc complete at South Wall including taking down old panel all as directed and suitable to accommodate the following switch gears and meters :- INCOMER: a) ACB 800 Amps 4pole,36 KA EDO type - 1 Nos (Incomer) OUTGOING: b) MCCB, 4 pole 400 Amps,36KA,Thermal magnetic - 1 Nos (Out going) c) MCCB, 4 pole 250 Amps,25KA,Thermal magnetic - 1 Nos (Out going) d) MCCB, 4 pole 100 Amps,18KA,Thermal magnetic - 1 Nos (Out going) g) VAF meter class 1with CT's - 1 No g) indication lamps (R,Y,B) LED type - 1 set MAKE of MCCB : Schinder/ Legrand/Seimens/L & T
Supply, fabrication, installation, testing & commissioning of Feeder piller box for looping of cables, indoor type, dust and vermin proof, made out of 3.15mm thick CRCA sheet, front & back openable doors having vertical copper bus bar of capacity 2500 amps for phases and for neutral including powder coated painting, PCC foundation, supporting channels,cable termination,cable gland etc complete at jetty/casin including taking down old panel all as directed.
Supply, fabrication, installation, testing & commissioning of Feeder piller box for looping of cables, indoor type, dust and vermin proof, made out of 3.15mm thick CRCA sheet, front & back openable doors having vertical copper bus bar of capacity 800 amps for phases and for neutral including 400Amps 4 pole 36kA AC/DC MCCB powder coated painting, PCC foundation, supporting channels,cable termination,cable gland etc complete at jetty/casin including taking down old panel all as directed.
Supply, fabrication, installation, testing & commissioning of Feeder piller box for looping of cables, indoor type, dust and vermin proof, made out of 3.15mm thick CRCA sheet, front & back openable doors having vertical copper bus bar of capacity 1000 amps for phases and for neutral including 800Amps 4 pole 36kA AC/DC MCCB powder coated painting, PCC foundation, supporting channels,cable termination,cable gland etc complete at jetty/casin including taking down old panel all as directed.
S & F in repair Distribution Board double door, prewired type, made out of CRCA mild steel sheet surface with insulated material like polyester or with epoxy powder coating and IP 54 & IK 09 protection surface mounting SPN 8 way, 240 volts with bus bar rating 200 Amps, dust and vermin proof suitable for incorporation of MCB’s and isolators etc complete all as directed. Make - Legrand cat No 5076 41 or equivalent Cat part in Siemens/GE
S & F in repair Distribution Board double door, prewired type, made out of CRCA mild steel sheet surface with insulated material like polyester or with epoxy powder coating and IP 54 & IK 09 protection surface mounting SPN 6 way, 240 volts with bus bar rating 200 Amps, dust and vermin proof suitable for incorporation of MCB’s and isolators etc complete all as directed. Make - Legrand cat No 5076 41 or equivalent Cat part in Siemens/GE
S & F in repair Distribution Board double door, prewired type, made out of CRCA mild steel sheet surface with insulated material like polyester or with epoxy powder coating and IP 54 & IK 09 protection surface mounting VTPN 8 way, 440 volts with 100A Copper Busbar rating 440 Amps, for each phase, 2 Neutral bar, 2 Earth bar, dust and vermin proof with provision for FP MCB/Isolator/RCCB/RCBO as incomer and SP/TP MCB's as outgoing etc complete all as directed. Make - Legrand cat No 5077 52 or equivalent in Siemens/GE NOTE FOR ITEM No. 11 to 13 : MCB DBs shall be concealed in wall where ever posible including cost of removing old wooden box making good the surface to match with surrounding deemed to be included in quoted rates
S & F MCCB, 415 volts, four pole of capacity 125 Amps, 16 KA, ICS = 100% ICU, with fixed Thermal - Magnetic setting including spreader terminal/ thimble of suitable size and making connections complete all as directed. Make - Legrand cat No 4200 16 or equivalent in siemens/GE / C&S
S & F MCCB, 415 volts, four pole of cap 400 Amps, 36 KA, ICS = 100% ICU, with fixed Thermal - Magnetic setting including spreader terminal/ thimble of suitable size and making connections complete all as directed. Make - Legrand cat No 4220 07 or equivalent in siemens/GE / C&S
S & F in replacement of MCB 6 to 32 Amps capacity, C Curve type suitable for 240 volts AC supply, SP with over load and short circuit protection and rupturing capacity not less than 10 KA including making connection complete all as specified and directed. Make: Legrand cat No 4085 87-95 or equivalent Cat part in Seimens/C&S.
S&F MCB SPN 40-63Amps, 10KA 'C' Curve 240V complete all as specified and directed. Make: Legrand cat No 4086 18-20 or equivalent Cat part in Seimens/C&S.
S&F in repairs of 0.71mm thick powder coated aluminium sheet cover, alloy 31000 H4 in ridges, Hips vally gutter including suitable size of revits/nut bolts complete bending, shaping, drilling, cutting notching and all as specified and directed.
Supply and fixing in repair walll/surface mounted 10W LED batten fitting engineering plastic battern with white acrylic cover complete with all accessories internally pre-wired and including fixing the fitting on wall/ceiling with suitable PVC round/square block-02 Nos including connecting up with twin core copper conductor cable with suitable size and all as directed. Make : CG/wipro/C&S cat No LTTB2F10WLEDW BATTEN/Bajaj/Havells/Philips
Supply and fixing in repair walll/surface mounted 20W LED batten fitting engineering plastic battern with white acrylic cover complete with all accessories internally pre-wired and including fixing the fitting on wall/ceiling with suitable PVC round/square block-02 Nos including connecting up with twin core copper conductor cable with suitable size and all as directed. Make : CG/wipro/C&S cat No LTTB4F20WLEDEW BATTEN/Bajaj/Havells/Philips
Supply and fix cable jointing STRAIGHT THROUGH JOINT complete with jointing material (Heat srinkable) for 1100V grade cable for XLPE armoured alluminium conductor cable of size 120 to 185 sqmm 3.5 cre complete all as specified and directed. Make : Rychem/3M
Supply and fix cable jointing STRAIGHT THROUGH JOINT complete with jointing material (Heat srinkable) for 1100V grade cable for XLPE armoured alluminium conductor cable of size 240 to 400 sqmm 3.5 cre complete all as specified and directed. Make :Rychem/3M
Supply and fix cable jointing STRAIGHT THROUGH JOINT complete with jointing material (Heat srinkable) for 1100V grade cable for XLPE armoured alluminium conductor cable of size 95 to 120 sqmm 3.5 core complete all as specified and directed. Make :Rychem/3M
S & F in repair of Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20A all as specified and directed by EIC. Make: Siemens/Legrand/C&S.
Excavation in trenches n exc1.5m wide and n exc in depth for laying of cables and getting out in loose/soft soil compete all as directed.
Excavation in trenches n exc1.5m wide and n exc in depth for laying of cables and getting out in hard/dense soil compete all as directed.
Returing filling in including spreading, levelling watering and well ramming in layers not exc 25cm compete all as directed.
Removing excavated material n exc 50cm and deposting where directed at a level n exc 1.5m above the starting point compete all as directed.
M&L for GI pipe light grade 100mm dia for protection of UG cable crossing of nalha/bgrdge/road etc complete all as directed.
M&L cement concrete in 1:2:4 type B1 using 20mm grade stone aggregate for road cutting/pole couping exposed surfaced and fair and even finishing with out using any extra cement etc complete all as specified and directed
Supply and lay in repair cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240sq mm 3½ core. laid in trench/ duct / along pole/wall etc including making connection complete all as directed. MAKE : Gloster/Polycab/Finolex/Havells/Plaza Note : 1. The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply and lay in repair cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 185sq mm 3½ core. laid in trench/ duct / along pole/wall etc including making connection complete all as directed. MAKE : Gloster/Polycab/Finolex/Havells/Plaza Note : 1. The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply and laying Four Core cable of size 16.0 sq mm (heavy duty), 1100 Volts grade, as IS 694:1990, unsheathed, PVC Insulated and Multi Core PVC Insulated and PVC sheathed industrial cables with flexible bright annealed Copper Conductor, including making connection and taking out old damaged cable complete all as directed. Make of wire : Polycab/ Havells/ Gloster / Plaza Note : 1. The cost of Al thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply of JEF ECO SAFE Maintenance Free Grounding Solution set comprising of High tensile low carbon steel rod of 3 Mts length & 32 mm dia with 250 micron (average ) molecularly bonded copper on the outer surface to confirm with requirements of UL467 along with Back-fill compound strictly be a Carbon based conductive concrete type which has a resistivity of less than 0.12 Ohm Mtr as per Clause 14.5D of IEEE : 80 standard. Back-fill compound should be electronically conductive ( Like in metals ) and should not depend on moisture for conduction. JEF ECO SAFE compound shall be supplied in 50 Pound Bag. ( 1 Bag required per earthing set). Back-fill comound should be environment friendly, should solidify when mixed with water and set like concrete and should not leach / diffuse into the ground. A suitable earth terminaton clamp should also be supplied alongwith weatherproof chamber. Note : Back-fill compund shall not be mixed with any soil while pouring in the bore hole.
S&F galvanised iron strip 25 x 4 mm or main earthing lead fixed to wall with clamps or recess or croses or buried in ground or drawn in conduits/pipe or fixed to poles or any other indicated situation for loop earthing etc as required all as specified and directed by Engr-in-Charge.
SRISHTI CONSTRUCTIONS
Rohit Enterprises
Shree Ayyappa Engineering
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .