Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L 1₹55.3 LAccepted-Finance VILLAGE DINAK P O KANAID TEHSIL SUNDERNAGAR | BILASPUR | HIMACHAL PRADESH | 174001 | L 1 | Accepted-Finance L 1 | |
| 2 | L 2₹55.6 L+₹37,558 (0.68%)Rejected-Finance SHOP NO 5 BACHAT BHAWAN UNA TEHSIL UNA HP 174303 | UNA | UNA | HP | 174303 | L 2 | Rejected-Finance L 2 | |
| 3 | L 3₹74.5 L+₹19.2 L (34.8%)Rejected-Finance H NO 199 W NO 6 NEAR OLD SDM OFFICE DISTT HAMIRPUR HP 177001 | HAMIRPUR | HAMIRPUR | HP | 177001 | L 3 | Rejected-Finance L 3 |
Tender Value
₹51.7 L
EMD Value
₹84,300
Closing Date
22 Sept 2021, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer Electrical HPPWD Division Una
Executive Engineer Electrical HPPWD Division Una
Providing E.I. therein
2021_PWD_52379_1
C/O I.T.I. building Gagret at Bhadarkali
Open Tender
Electrical Works
Item Rate
730 days
Una
Please refer Tender documents.
7 documents required · 7 mandatory
₹2,000
₹84,300
18 Oct 2021
16 Sept 2021
23 Sept 2021
16 Sept 2021
22 Sept 2021
16 Sept 2021
120 days
Amount
Wiring for light point / fan point / exhaust fan / call bell point with 1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit with modular switch, modular plates, suitable G.I. box and earthing the light point with 1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable as required.(Make:- Legrand (Myrius), L&T (Entice),Anchor(Roma plus)
(a) Group C.
Wiring for twin control light point with 1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit with 2-way, 5/6 amps. modular switch, modular plates, suitable G.I. box and earthing the light point with 1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable as required.(Make:- Legrand (Myrius), L&T (Entice),Anchor(Roma plus))
(a) Group C.
Wiring for light plug with 2x1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 1 No.4 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable for earthing as required.KEI,Anchor,L&T make)
Wiring for power plug with 2x4 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 1 No.4 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable for earthing as required.(KEI,Anchor,L&T make)
Wiring for power plug with 4x4 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 2 No.4 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable for earthing as required.(KEI,Anchor,L&T make)
Wiring for circuit/sub-main with following size PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 1 No.HRFRLS/PVC insulated single core copper conductor cable of same size for earthing as required.(,KEI,Anchor,L&T make)
(a) 2x1.5 Sq. mm.
(b) 4x1.5 Sq. mm.
(c) 2x2.5 Sq. mm.
(d) 4x2.5 Sq. mm.
(e) 2x6 Sq. mm.
(f) 2x10 sq.mm.
Wiring for circuit / sub-main with 4x10 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 2 No.10 Sq.mm. (4x10+2x10) HRFRLS/PVC insulated single core copper conductor cable for earthing as required.(,KEI,Anchor,L&T make)
Wiring for circuit / sub-main with 4x16 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 2 No.16 Sq.mm. (4x16+2x16) HRFRLS/PVC insulated single core copper conductor cable for earthing as required.(,KEI,Anchor,L&T make)
Wiring for circuit / sub-main with 3x25+1x16 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 2 No.16 Sq.mm. (3x25+3x16) HRFRLS/PVC insulated single core copper conductor cable for earthing as required.,KEI,Anchor,L&T make)
Supplying and drawing following size of PVC insulated, heat resistant, flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in existing surface / recessed, Steel/PVC conduit as required.(,KEI,Anchor,L&T make)
(a) 3x1.5 Sq. mm.
(b) 3X4 Sq.mm.
Supplying and drawing following pair of Fire Retardant, PVC insulated 0.5 sq.mm. (FR-Flexible) copper conductor, flat, unarmoured, telephone cable in existing surface / recessed, steel / PVC conduit as required.
Supplying and fixing of following sizes of PVC conduit along with the accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required:-(Diplast,Polycab make)
25 mm. dia
40 mm. dia
100 mm. dia
Supplying and fixing following rating Modular switch /socket in the existing switch box / cover plate including connections etc. as required.(Make:- Legrand (Myrius), L&T (Entice),Anchor(Roma plus)
S.P. 5/ 6 Amps one way Modular switch.
5 pin, 5/ 6 Amps Modular socket outlet.
Supplying & fixing Modular blanking plate on the existing modular metal box as required:-
Supplying and fixing G.I. Modular box of (140mmx78mmx50mm) size with modular plate and cover in recess including providing and fixing 5 pin 5/6 amps modular socket outlet and 5/6 amps, modular switch, connections etc. as required.(Make:- Legrand (Myrius), L&T (Entice),Anchor(Roma plus) .
Supplying and fixing G.I. Modular box of (140mmx78mmx50mm) size with modular plate and cover in recess including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps, modular switch, connections etc. as required..(Make:- Legrand (Myrius), L&T (Entice), Anchor(Roma plus)
Supplying and fixing Power plug socket with MCB Protection 25Amp with plug top and 4 mdoule box including making connections, testing etc. as required (Philips model no. 9137082339101 HSN Code 85369010/Anchor/ L&T make)
Supplying and fixing bakelite batten/angle holder including connections etc. as required:- (SSK,Anchor make)
Supplying and fixing call bell / buzzer, suitable for D.C./A.C.single phase,230 volts complete as required:-(SSK,Anchor make)
Supplying and fixing Ding-Dong / Electronic musical bell, suitable for D.C./A.C. single phase,230 volts complete as required:-(SSK,Anchor make)
Supplying and fixing Indicating bell Red & Green with 3 module box on the existing main door wall complete with connections etc. as required. (Goldmedal make code No.103649 or its equivalent make)
Supplying and erection of wall mounted metal boards for switch gear mounting of suitable size, with permissible variation in size of plus minus 5mm, welded frame work made of M.S. angle iron (35 mm x 35 mm x 6 mm thick) with sufficient numbers of horizontal and vertical intermediate members (25mm x 6mm thick) flat iron including painting and bonding to the existing earth as required:-
Supplying and erection of following depth sheet metal cubical pedestal of suitable dimensions with plus-minus 5 cm variation made from (50 mm x 50 mm x 6 mm thick) M.S. angle iron frame, covered with 1.6 mm thick M.S. sheet duly welded on five sides & front side hinged, complete with locking arrangement with sufficient No. vertical and horizontal intermediate switchgear supporting members each of M.S. flat 50mmx6mm thick of suitable length duly welded. The cubical pedestal shall have cable entry box at one or two sides and 4 No. legs of suitable length duly welded. The cubical pedestal shall have cable entry box at one or two sides and 4 No. legs of 50mmx50mmx6mm thick M.S. angle iron each 60 cm long including, powder coated painting and bonding to the existing earth etc., the same shall be erected in the 1:2:4 cement concrete plat-form of suitable dimensions 15 cm high from ground level and 45 cm thick. The cubical pedestal shall be 15 cm from the top of cement concrete plat-form:-(EVA,Power & control,Supertech make ). The panel should be approved/tested from the CPRI lab and should be confirmed to IS :-64139
(a) 450 mm deep (nominal)
(b) 300 mm deep (nominal)
Supplying and fixing copper strip bus-bars suitable for 100 Amp. 415 volts capacity 4 No. each of cross-sectional area (25.4mmx3.17mm),in the existing enclosure with all accessories including connections etc. as required:-
Supplying and fixing copper strip bus-bars suitable for 200 Amp. 415 volts capacity 4 No. each of cross-sectional area (25.4mmx4.75mm),in the existing enclosure with all accessories including connections etc. as required:-
Supplying and fixing copper strip bus-bars suitable for 500 Amp. 415 volts capacity 4 No. each of cross-sectional area (50.8mmx6.35mm),in the existing enclosure with all accessories including connections etc. required:-
Supplying and fixing sheet metal bus-bar chamber suitable for 63 Amp. 415 volts capacity with 4 No. copper strip bus-bars each of length 300mm & cross-sectional area (16mmx3.17mm), enclosure made from 1.6 mm thick M.S. sheet having overall dimensions (380mmx400mmx150mm) nominal with all accessories including connections, earthing the body etc. as required:-( Legrand ,Schneider,Siemens make)
Supplying and fixing sheet metal bus-bar chamber suitable for 100 Amp. 415 volts capacity with 4 No. copper strip bus-bars each of length 300mm & cross-sectional area (25.4mmx3.17mm), enclosure made from 1.6 mm thick M.S. sheet having overall dimensions (380mmx400mmx150mm) nominal with all accessories including connections, earthing the body etc. as required:-( Legrand ,Schneider,Siemens make)
Supplying and fixing 20 Amps, 240 volts, SPN industrial socket outlet, 2-pole & earth, metal enclosed plug top, sheet steel enclosure, suitable to accommodate a 20 Amp SPN-MCB/DP, on surface or in recess, with chained metal cover for the socket outlet, complete with connections, testing and commissioning etc. as required.
Providing and fixing following rating, four pole, 415 volts, On-Load change over switch unit, panel mounting, front handle operation, including drilling holes in the cubical, making connections, etc. as required.(L&T,ABB & Siemens make)
Providing and fixing following rating and breaking capacity MCCB in the existing cubical panel board including drilling holes in the cubicle panel, making connections, etc. as required.(L&T,ABB & Siemens make)
32 Amp. -30 KA
63 Amp. -30 KA
100 Amp. -16 KA
160 Amp. -16 KA
315/400 Amp. -35 KA
Providing and fixing MCCB enclosure for DU 100H/DU125H/DU100D/DU125D/DN0 following rating on the existing board complelte as required ((L&T/ABB/Legrand make)
Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.(L&T,ABB,Hagger & Siemens make)
40 Amps. Cat-A.
63 Amps. Cat-A.
Supplying and erection of 6 amps. to 32 amps. rating, 10 KA breaking capacity, 240 volts, 'C' curves, miniature circuit breaker of following poles in the existing MCB DB complete with connections etc. as required:- (Hagger,ABB,L&T make)
(a) Single pole. 6 Amps.Cat-A.
(b) Single pole. 16 Amps.Cat-A.
(c) Single pole. 25 Amps.Cat-A.
Supplying and fixing following rating, double pole (single phase & neutral) 240 volts, residual current circuit breaker (RCCB), having a sensitivity current up to 300 miliampers in the existing MCB DB complete with connections, testing and commissioning etc. as required.
40 Amps. Cat-A.
63 Amps. Cat-A.
Supplying and fixing of following way, single pole and neutral sheet steel MCB distribution board, 240 volts, on surface / recess, complete with tinned copper bus- bar, wire-set, neutral link, earth bar, din-bar, detachable gland plate, blanking plate, cable, identification labels interconnections, phosphatized and powder painted, including earthing etc. as required:- (Hagger,ABB,L&T make)
(a) Double door-4 way
(c) Double door-8 way
(d) Double door-12 way
(e) Double door-16 way
Earthing with copper earth plate 600 mmx600 mmx 3 mm thick, including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) complete as required.
Extra for using salt and charcoal for G.I. or copper plate earth electrode complete as required.
Providing and fixing 25mm x 5mm copper strip on surface or in recess for earth connections etc. as required.
Providing and fixing 8 SWG (4 mm dia.) copper wire on surface or in recess for loop earthing along with existing surface/recessed conduit/sub-main wiring/cable as required.
Providing and fixing M.V.danger notice plate of 200 mm x 150mm made of mild steel at least 2 mm thick, and vitreous enameled white on both sides and with inscription in signal red color on front side as required.
Providing and laying of one No. aluminium conductor, PVC insulated and PVC sheathed, armoured/XLPE power cable, working voltage 1100 volts grade direct in ground; to be laid 1 meter below the ground level including excavation sand cushioning, protective covering and refilling the trench etc. of the required size:-(Finolex,Haells,L&T,KEI or its equivalent make)
(a) Armoured cable 400 sq. mm (3.5 core)
(c) Armoured cable 10 sq. mm (twin core)
Providing, laying and fixing of one No. aluminium conductor, PVC insulated and PVC sheathed, armoured/XLPE power cable, working voltage 1100 volts grade on surface etc. of the required size:-(Havells,L&T,KEI)
(a) Armoured cable 400 sq. mm (3.5 core)
(b) Armoured cable 35 sq. mm (3.5 core)
(c)Unarmoured cable 35 sq. mm (3.5 core)
(d) Armoured cable 25 sq. mm (3.5 core)
(e)Unarmoured cable 25 sq. mm (four core)
(f) Unarmoured cable 16 sq. mm (four core)
(g)Unarmoured cable 10 sq. mm (twin core)
Providing, Installation, testing and commissioning of ceiling fan without step type fan regulator modular, air delivery 215m3/min power input 43 watts, speed 330RPM , including wiring the down rods of standard length (up to 30 cm) with 16/0.20 mm twin twisted flexible, cotton braided, copper cable, including providing and fixing phenolic laminated sheet cover on the fan box and earthing etc. as required:- Tech. specfications:-100-240V,50 Hz,speed 330 rpm,power consumption 43 watt
Usha Technix plus BEE 3 Star rated model/crompton/Bajaj make) (Minimum 3 star rating)
(a) Ceiling Fan 1200 mm sweep, Category-A
Supplying and fixing stepped type Modular fan regulator on the existing modular box including making connections etc. as required.
Providing and installation of exhaust fan of following sizes in the existing opening, including making the hole to suit the size of the above fan, making good the damages, connections, testing and commissioning etc. as required:- (Usha Turbo HDEF 900rpm ISI /Orient/Bajaj make) as approved by Engineer in charge
Exhaust Fan, Heavy duty, 300 mm sweep
S/F of exhaust fan louver shutter i/c covering with ply board for 300 mm.exhaust fan on the existing wall,painting etc,as required (HSBC, National make)
S/F of Exhaust fan (Plastic) with louver shutter 300mm,1000rpm,power 55 watt,air delivery1125 Cmh suitable for 240 volts A.C.supply, 50 Hz,Bajaj maxima Dxl model on the existing opening including making proper hole complete with connections etc. as required
Supplying and fixing Fan box made of M.S.sheet with iron rod Hook 12 mm.in place of Junction box complete with bakelite Round sheet as required.in/c carriage of material with in all leads and lifts.(National or its equivalent make)
S/F of Cabin/wall fan 400 mm.sweep A.C supply 240 volts 50 HZ WF Mist Air Icy blue,1280RPM,55WATT,No. of speed=3, Air flow 67 CMM including connections, testing and commissioning etc. as required:-Usha/.Crompton Greaves/ Bajaj make),
S/F Ebrit digital mounting voltmeter 0 to 500 volts 3 phase of 0.5Cl.size 96x96 sq.mm.flush mounting in existing pannel cat.No. WL132020OOOO (L&T make) or its equivalent make complete with connections etc as required.
S/F Ebrit digital mounting Ammeter 0.5 Cl. 3 phase of size 96x96 sq.mm.flush mounting in existing pannel cat.No.WL131020OOOO (L&T make) or its equivalent make complete with connections etc,as
S/F The Coolio Fuzi Led Panel Indicator Lights (R,Y & B) with 3. nos. Kit Kat (Neon type) to shown the three phase indicating in the existing pannel complete with connections etc,as required.
S/F Electic shock treatment chart size 24x18" in main pannel room on the existing wall etc as required.in/c carriage of material with in all leads and lifts.
S/F shock C.T.coil of rating 200/5 Amps.(YOKINS) In the existing pannel etc as required.in/c carriage of material with in all leads and lifts
S/F of Rubber mate 1 x 2 mtrs.long 2.5mm thick(JYOTI) in the front main pannel etc as required.in/c carriage of material with in all leads and lifts.
Providing and fixing of lightning conductor finial, made of 25 mm dia. 300 mm long copper tube, having single prong at top, with 85 mm dia 3 mm thick copper base plate including holes etc. complete as required.
Riveting, sweating and soldering of copper/ G.I. tape ( with another copper/G.I. tape, base of the finial or any other metallic object) as required.
Supplying and fixing copper tape 20mmx3mm thick on parapet or surface of wall for lightning conductor as required ( for vertical run)
Supplying and fixing copper tape 20mmx3mm thick on parapet or surface of wall for lightning conductor as required ( for horizontal run)
Supplying and drawing Lan cable,1000Mbps speed,Unshielded Cat 6, D-Link make,Twisted pair(UTP) soild copper conductor protected with PVC. Sheath in the existing surface/recessed Steel/PVC conduit as required.
Providing and fixing Rack 6 U D-Link make for net cabling of computer on the existing wall including connections etc,as required.
Supplying and fixing of D- Link DSL -2750 U wireless N 300ADSL2+Router complete with connections etc,as required.
Supplying and fixing 24 port fast Ethernet Switch D-Link make, 10/100Mbps .DES1024D Unmanaged switchas required
Providing and fixing Patch cable each 2 mtrs.long D-Link make for net cabling of of computer in the existing RJ-45 connector including connections etc,as required.
S/Fcomputer board comprising 3 no.5 Amps switch(modular) and 3 no. 5 Amps socket outlet(modular) and 1 no. 12 Modular switch board with cover plate and 1 no. computer Jack with shutter including connections etc. as required complete in all respects(Make:- Legrand (Myrius), L&T (Entice),Anchor(Roma plus)
Supplying and fixing surface LED 12 watt Philips make down lighter with high efficacy .Housing made of extruded aluminium with high translucent HET diffuser and it should be compatible with specifications i.e.Power factor >0.9,Harmonic distortion <10% & efficacy >100 Lumen per watts,CRI >80 ,6500 K suitable for input voltage 220-240 Volts,50 Hz,IP rating 20,Surge rating up to 2 KV,dimensions 178-178-25 complete with connections etc,as required. HSN CODE 94051090)SM250C LED 12S 6500 PSU WH (TIsva,Wipro or its equivalent make)(with five year warranty)
Supplying and fixing recess mounting LED 18 watt metal panel round recess down light for for soft diffuse lighting white cool and should be compatible with specifications i.e power factor>0.9Harmonic distortion<10%& efficacy>100Lumen per watts, CRI>80,6500K,suitable for input voltage 220-240 volts, 50Hz, IP rating 20,surge rating upto 3 kv, dimensions ϕ21.2 ϕ20.0 C3.0 complete with connactions etc. as required ( Tisva EZIO Series Code no. DLP181623M/Wipro/Philips make) (With five year warranty)
Supplying and fixing surface mounting LED 36 watts metal square down Light for soft diffuser lighting and white and it should be compatible with specification i.e Power factor >0.9, Harmonic distortion < 10% & efficacy> 100 Lumen per watts, CRI > 80, CCT5700 K suitable for input voltage 220-240 volts 50 HZ IP rating 20 Surge rating upto 3 KV, complete with all accessories connections, testing and commissioning etc. as required (Wipro Cat No.CRCO10S038HP57GL1/Tisva/ Philips make or its equivalent),(With five year warranty)
Supplying and fixing LED Tube fixture 32 watts surface/ suspended mounting extruded aluminium coated body and it should be compatible with specification i.e Power factor >0.9, Harmonic distortion < 10% & efficacy> 100 Lumen per watts, CRI > 80, 6500 K suitable for input voltage 220-240 volts 50 HZ IP rating 20 Surge rating upto 3 KV, diamensions 4x1'complete with all accessories connections, testing and commissioning etc. as required (Philips Smart brite cat no. SM270C LED 30S 6500 PSUWH/ Wipro/Tisva make ),(with five year warranty)
Supplying and fixing LED Tube fixture Endura LED Next 36 watts surface mounting CRCA Steel Housing and it should be compatible with specification i.e 4000 Lumen output,CRI>80, Efficacy12lm/w, 6500 K,length 4 feet Beam angle120 degree suitable for input voltage130-270 volts 50 HZ, Surge rating upto 3 KV, complete with all accessories connections, testing and commissioning etc. as required (Philips Type BN308C LED 40S-6500 PSU L120 WH/Wipro/ Tisva make ),(with five year warranty)
Supplying and fixing LED Lamp 9 watts ,825 Lumens 240 volts AC.supply 50 Hz in the existing batten holder,pendent holder,wall bracket & bulk head fitting etc, as required.Philips Ace Saver HSN CODE 85395000/Tisva/Panasonic make)
Supplying and fixing LED Batten 10 watts Mirror Light and it should be compatible with specifications i.e power factor>0.9.Harmonic distortion<10%& efficacy>100, lumen per watts,CRI>80, CCT 6500K suitable for input voltage 220-240 volts,50Hz,IP rating20,surge rating 3.0kv, and length 59.5 cm complete with connections etc. as required( Tisva code No.FT10001WT,Panasonic& Philips make)
Supplying and fixing Pendent Light LED.9 watts 3000K,240V,50Hz,0.8p.f size 272x170x170 mm.blue and metal commercial code 33389 Philips make 12NC code 919215850196/Wipro/Tisva make complete with connections etc,as required.
Supplying and fixing of bulk head fitting LED 10 watts and should be compatible with specifications i.e power factor <0.9 Harmonic distortion < 10% & efficacy > 100 Lumen per watts CRI> 80 6500 K suitable for input voltage 220-240 volts 50 HZ Length 232x Width 105x Height 50 mm size complete with connections etc. as required (Panasonic Ellipto Code No. PBHM01107,Philips & Tisva make )
Supplying and fixing Fancy wall bracket Decon make, Srilanka model Cat.No. 05OQ,GLS-60W,240V,50Hz,0.8p.f. containing GLS lamp holder (s) of all sizes and shapes, complete with all accessories but excluding CFL lamp including making connections, testing etc. as required.(Decon cat .no.0553/philips/Tisva make)
Supplying and fixing Chandlier 3 light Decon make, ventessa model Cat.No. 260Q,240V,50Hz,0.8p.f. containing GLS lamp holder (s) of all sizes and shapes, complete with all accessories but excluding CFL lamp including making connections, testing etc. as required.(Decon cat .no.0553/philips/Tisva make)
Providing and fixing LED surface/pendent mounting Tube fixture 20 watt LED batten anodised extruded aluminium housing transmussuinbility diffuser and it should be compatible with specificatiob i.e power factor >0.9 Harmonic distortion <10% & efficacy > 100 Lumens per watt CRI < 80 5700 K suitable for input voltage 220-240 volts 50 Hz Length 1175x30x36mm complete with connections and as per best satisfaction of Engineer-in-charge complete as required (Panasonic Harrowal Code No. PBTN08208/ Philips, Wipro make ) (with five year warranty)
Supplying and fixing LED Tube fixture 40 watts surface mounting extruded aluminium coated body and it should be compatible with specification i.e 4000 Lumen output,80, 6500 K,length 4 feet Beam angle120 degree suitable for input voltage130-270 volts 50 HZ, Surge rating upto 3 KV, complete with all accessories connections, testing and commissioning etc. as required (Philips Type BN100C LED 40S-6500 PSU L120 GR/Wipro /Tisva make ), (with five year warranty)
Supplying and fixing recess LED 26 watt down lighter with high efficacy .Housing made of extruded aluminium with high translucent HET diffuser and it should be compatible with specifications i.e.Power factor >0.9,Harmonic distortion <10% & efficacy >100 Lumen per watts,CRI >80 ,5700 K suitable for input voltage 220-240 Volts,50 HZ,IP rating 20,Surge rating up to 3 KV,dimensions ϕ220 . complete with connections etc,as required. (Wipro Halo CRDL11 Pro Code No.CRDL11 R033HP57/Panasonic/Philips make) (with five year warranty).
Providing and installation of stationary storage type Electric water heater (Geyser) of various sizes by means of Expansion-bolts with nuts and washers, including embedding of expansion-bolts in the wall, providing and fixing of Non-return valve, Dead weight safety valve, 2 No C.P. connection rods 18" long, making good the damages, electrical connections, safety valve connections, testing and commissioning etc. as required:-
35 Liter capacity water heater (Cat-A) Recold/Jaquar/Usha make Min. 3 star rating
Supplying and fixing of 1.5 ton Split type (Inverter type) 4 star Air conditioner hot and Cold with intelligence heating LCD operated, Advance Filter, E Saver mode, Quit mode, dual display / auto clean Anti Bacteria filter jet cool ON/OFF timer sleep mode compressor cordless remote alongwith voltage stablizer 4KVA (EM4140) 130V to 300V Microteck/APC/Numeric/Emerson make complete in all respects comprising to ISI with latest amendment suitable to operate on 130-300 volts +/- 10% A.C. supply operating ambient temperature range -7oC to 52oC, compressure type high EER rotary BLDC Refergrqant R4109, filter quadra filter protection with sleek mode capable to perform the function of cooling dehumidification Air circulation, ventilation and fitting in the size of nominal cooling capacity complete with drain pipe 20mm dia approximately 3 Mrs. Long, 2 Nos copper pipe with insulator for inlet and outlet approximately 3 mtrs. Long and M.S. power coated frame/stand for erection of outdoor unit of split type A.C. including carriage of material within all leads and lifts. Make: Voltas (Model SAC184VZS Floral(R32))/Blue star/O-General/Daikin.as approved by the Engineer-in-charge.
Supplying and fixing 4.0 mtrs.2 stepped Decorative pole made of Galvanised mild steel tubes with cast aluminium embellishments.The pole are primer coated and painted with polyurethane paint.Pole are suitable for Single/Double side drop down luminaires with double arm bracket .The pole has a service window at the bottom comprising four way 25 amps connector terminal and a MCB.Pole can be mounted with four numbers Anchor bolts as per foundation.Pole make :-Twinkle LuxMax-SP-140-400-4 mtr.or its equivalent make
Supplying and fixing Post top lantern LED 40 watts made of spun aluminium housing with sturdy bracket with power LED's are mounted directly on extruded aluminium heat sinks.A UV stabilized PC/PMMA diffuser is provided for glare free lighting with high visual comfort.input voltage AC-100-270,FREQUENCY 50~60HZ,Power factor 0.950,efficacy 100 Lum/W,CRI 80,THD 10% LIFE 50000 H.Colour temperature NW 4000K.(Twinkle LuxMax-PT-157-H-CR Post top or its equivalent make(with thre warranty).
Providing and fixing DLP U-PVC adaptable trunking system and accessories 80X50 mm.on existing wall at required height from floor level including fixing flexible cover, etc,as required.( Legrand 010412 or its equivalent make)
Providing and fixing DLP U-PVC adaptable trunking system and accessories 105x50 mm.on existing wall at required height from floor level including fixing lexible cover, etc,as required.( Legrand Cat.No.010422 or its equivalent make)
Providing and fixing DLP U-PVC adaptable trunking system and accessories 150X50 mm.on existing wall at required height from floor level including fixing ,flexible cover,, etc,as required.( Legrand 010432 or its equivalent make)
Providing and fixing External angle adjustable from 60* to 120* on the DLP U-PVC trunking for making compact joint as required.( Legrand Cat.No.010622 or its equivalent make)
Providing and fixing Internal angle adjustable from 80* to 100* on the DLP U-PVC trunking for making compact joint as required.( Legrand Cat.No.010602 or its equivalent make)
Providing and fixing Flat junction for to tap - off to a branch smaller than 50x105 mm. as required.(Legrand Cat.No.010732 or its equivalent make)
Providing and fixing joint. as required.(Legrand Cat.No.010691 or its equivalent make)
Providing and fixing separation partition . as required.(Legrand Cat.No.010732 or its equivalent make)
Providing and fixing 90* Flat angle on the corner of DLP U-PVC 80x50 mm.trunking for making compact and good looking joint as required.( Legrand Cat.No.010767 or its equivalent make)
Providing and fixing 90* Flat angle on the corner of DLP U-PVC 105x50 mm.trunking for making compact and good looking joint as required.( Legrand Cat.No.010785 or its equivalent make)
Providing and fixing 90* Flat angle on the corner of DLP U-PVC 150x50 mm.trunking for making compact and good looking joint as required.( Legrand Cat.No.010789 or its equivalent make)
Providing and fixing clip on partition plastic . as required.(Legrand Cat.No.0104 72 or its equivalent make)
KUMAR ELECTRONICS CO.
SHARMA ELECTRICAL CO.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .