| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.4 LAccepted-AOC 12 1 FERRIGHAT ROAD P O BHATPARA DIST NORTH 24 PGS WEST BENGAL PIN 743123 | BHATPARA | NORTH 24 PARGANAS | WEST BENGAL | 743123 | L1 | Accepted-AOC lowest bidder | |
| 2 | L2₹6.7 L+₹30,228.14 (4.74%)Rejected-Finance 539 A PURBACHAL MAIN ROAD HALTU KOLKATA 700078 | KOLKATA | WEST BENGAL | 700078 | L2 | Rejected-Finance bidder is not L1 | |
| 3 | L3₹7.6 L+₹1.2 L (19.3%)Rejected-Finance 7A BENTINCK STREET KOLKATA 700 001 | KOLKATA | KOLKATA | WEST BENGAL | 700001 | L3 | Rejected-Finance bidder is not L1 | |
| 4 | L4₹9.4 L+₹3.0 L (46.7%)Rejected-Finance BASUDEBPUR BELKHALI HOWRAH PIN 711 322 | HOWRAH | HOWRAH | WEST BENGAL | 711322 | L4 | Rejected-Finance bidder is not L1 |
Tender Value
Refer Docs
EMD Value
₹18,740
Closing Date
18 Dec 2024, 2:00 pmClosed
Executive Engineer-I,CKHED,PWDte.
Central Kolkata Health Electrical Division, P.W.Dte. P-5, CIT Road, 2nd Floor, Moulali, Kolkata
SITC of Fire Detection and Alarm System at 3rd and 4th Floor of Chest Building of Calcutta National Medical College Hospital, Kolkata.
2024_WBPWD_772727_1
WBPWD/EE-I/CKHED/eNIT-84/24-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Chest Building of Calcutta National Medical Colleg
Please refer Tender documents.
3 documents required · 3 mandatory
₹18,740
Central Kolkata Health Electrical Division
11 Apr 2025
22 Nov 2024
20 Dec 2024
22 Nov 2024
18 Dec 2024
26 Nov 2024
26 Nov 2024
Amount
SITC of Microprocessor based intelligent, addressable 4 loops fire alarm control panel (VDS/UL/FM/ULC approved) fully networkable with each loop capable of taking minimum 125 devices, minimum 160 character alpha-neumeric liquid crystal display. The panel shall be able to give pinpoint location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switchs whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in in its Memory as per recommended standards.
The panel shall have in built rectifire, provision for external & internal printer (if required), Loop cards, LCD unit to indicate Fire/ Fault Signal with address analog output, complete in all respects, in built surge protection facility, integral SMF lead-acid batteries with sealed cells of 24V capable of running for 24 hours normal working & then be capable of operating the system for 30 minutes during emergency condition with integral battery charger complete as required. The panel shall have extra loop card to serve as standby in case of burnout or malfuntioning of any operating loop cards. The FACP shall be capable of being networked (future expansion) with other similar FACP located at different part of the premises through single RS485 bus. The panel should have Modbus output & ready to communicate with remote computer. The system must be preuploaded with licensed software. (Approved Make: Esser/ CerberusPro/ Secutron/ Notifier/ Edward/ Bosch/ Apollo/ Morley/ SystemSensor/ Johnson Controls/ Ravel).
SITC of Analog Addressable Intelligent multi-sensor detector (VDS/UL/FM/ULC approved) with two inbuilt optical smoke sensor as well as additional heat detector sensor with decentralised intelligence, addressable Phototharmal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard. (Note: Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices in group will be as per latest recommended standard without any additional cost). (Approved Make: Esser/ CerberusPro/ Secutron/ Notifier/ Edward/ Bosch/ Apollo/ Morley/ SystemSensor/ Johnson Controls/ Ravel).
SITC of Addressable Heat detector (Fixed temperature cum rate of rise) (VDS/UL/FM/ULC approved) with two inbuilt optical smoke sensor as well as additional heat detector sensor with decentralised intelligence, addressable Phototharmal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard. (Note: Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices in group will be as per latest recommended standard without any additional cost). (Approved Make: Esser/ CerberusPro/ Secutron/ Notifier/ Edward/ Bosch/ Apollo/ Morley/ SystemSensor/ Johnson Controls/ Ravel).
SITC of Addressable Manual Call Point (VDS/UL/FM/ULC approved) addresable type with in-built fault isolator as per NFPA style 7 wiring completed as required. (Approved Make: Esser/ CerberusPro/ Secutron/ Notifier/ Edward/ Bosch/ Apollo/ Morley/ SystemSensor/ Johnson Controls/ Ravel).
SITC of Addressable Hooter (sound output minimum 90dB) cum strobe (strength of light 10cd) complete with necessary modules if required with inbuilt isolator(Note: Devices without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices in group will be as per latest recommended standard without any additional cost) & and (VDS/UL/FM/ULC approved) and approved. (Approved Make: Esser/ CerberusPro/ Secutron/ Notifier/ Edward/ Bosch/ Apollo/ Morley/ SystemSensor/ Johnson Controls/ Ravel).
SITC of LED type Response Indicator having 2 Nos. red coloured LED lamps including connection set, etc. (Approved Make: Esser/ CerberusPro/ Secutron/ Notifier/ Edward/ Bosch/ Apollo/ Morley/ SystemSensor/ Johnson Controls/ Ravel)
Supply & Laying of 2 Core 1.5 sq. mm FRLS shielded copper Cable (For Loop) (Make: Finolex/KEI) with 20 mm NB PVC rigid conduit pipe (Make: Precision-Medium) on the surface of the wall.
Supply, Installation, Testing & Commissioning of Addressable transponder/ Monitor Modules ( VDS / UL / FM / ULC approved ) for monitoring flow switches/Fire exit doors / AHU / Lift etc complete as required. (Approved Make: Esser/ CerberusPro/ Secutron/ Notifier/ Edward/ Bosch/ Apollo/ Morley/ SystemSensor/ Johnson Controls/RAVEL)
Supply, Installation, Testing & Commissioning of Addressable Relay Modules (VDS / UL & FM approved) for switching / integration of Lift / AHU etc complete as required (Approved Make: Esser/ CerberusPro/ Secutron/ Notifier/ Edward/ Bosch/ Apollo/ Morley/ SystemSensor/ Johnson Controls/RAVEL)
NOTE: The Fire Alarm system shall comply with latest requirements of- 1. National Fire Alarm Protection Association (NFPA) Standards. 2. IS 2189. 3. NFPA 70 National Electric Code. 4. NFPA 72 National Fire Alarm Code. 5. Local Statutory Regulations. 6. Manufacturer Recommendation.
TESTS: The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system 2. Before energizing the cables and wires, check for correct connections and test for short circuits,ground faults, connectivity and insulation and other test as per above standards must be done.
Rate should be quoted incl. of all taxes and cess.
Defect Liability period : 1 year
Firemax Safety & Security Pvt.Ltd. (BID ID -5839143)
PERFECT IMAGE SOLUTIONS (BID ID -5789169)
Computer Gallery (BID ID -5876887)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .