Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.3 LAccepted-Finance | L1 | Accepted-Finance responsive | |
| 2 | L2₹10.9 L+₹61,051 (5.95%)Accepted-Finance | L2 | Accepted-Finance responsive | |
| 3 | L3₹10.9 L+₹63,211 (6.17%)Accepted-Finance | L3 | Accepted-Finance responsive | |
| 4 | L4₹11.0 L+₹78,281 (7.63%)Accepted-Finance | L4 | Accepted-Finance responsive |
Tender Value
₹11.4 L
EMD Value
₹22,860
Closing Date
1 Feb 2024, 3:00 pmClosed
Executive Engineer ED Sumbal
Executive Engineer ED Sumbal
Contract for Installation of 100 KVA Sub-Station at Sadab Colony Asham Sonawari and Creation of 63 kVA Sub-Station at Naidbagh Trigam Under MPLADS 202324
2024_PDD_242701_1
63 of 2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
Sumbal Sonawari
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
Executive Engineer ED Sumbal
₹22,860
Yes
3 Feb 2024
11 Jan 2024
2 Feb 2024
11 Jan 2024
1 Feb 2024
11 Jan 2024
Amount
Supply ,transportation ,installation, testing and Commissioning of 100 KVA Step-down transformer 11/0.440 KV) Level -2 fitted with Silica Gel Breather,oil filled and tested,complete in all respects as per latest specifications and drawing adopted/approved by the department.
Supply ,transportation ,installation, testing ,insurance and Commissioning of 63 KVA Step-down transformer 11/0.440 KV) Level -2 fitted with Silica Gel Breather,oil filled and tested,complete in all respects as per latest specifications and drawing adopted/approved by the department.
Providing of Earthing to Sub-Station-Excavation of earth Pit f 650 mm dia.& depth 3000 mm,Installation of earthing Pipe of 40mm nominal bore and 4mm wall thickness and length 2.5 m long as per IS-1239.GI Strip for neutral earthing of size 25mmX 3mm for connection of X-mer body ,G.O Set & LA as per IS-629/85,GI Nuts and Bolts refilled with earth enhancement materials & earth Chamber made of Brick massonary with RCC Slab Cover.
Providing ,transportation ,installation and fixing of GI Channel Cross arms (100X50X6 mm) and (75X40X6 mm),transformer Belting, Clamps etc. fabricated out of Galvanised steel of different sizes to be fixed with GI Nuts and bolts and washers.(as per the latest specification and drawing approved by the department).
Providing and fixing of gapless Surge Arrestor,9kV,10kV,LA with (Polymer ) housing ,Station Type.
Providing, and fixing of 11 kV G.O AB Switch 3-Phase,3-Pole of Capacity 200A Vertical type with arrangements for pad locks and operating rod. The operating rod should be G.I Pipe (B Class) of 25 mm dia of requisite length.
Providing and installation of 11 kV Horn,Gap Fuse 3-Phase 200 A.
Providing, and fixing of un -armoured PVC Cable 185 mm Sq. Including Al. Thimbles and SL Clamps
Providing, ,transportation ,erection, testing and Commissioning of ST Poles 9 Mtr long (410-SP-33) including excavation of pit and back filling soil & consolidating each deposit layer of by ramming and watering etc. (as per the latest specification and drawing approved by the department).
Providing ,Fixing, Installation, testing and commissioning of LT Distribution Box for 100 kVA DTR with 160 MCCB 3P 16 kA for incomer & 100 Amp MCCB 3P 16 kA 2 No.s for Outgoing Circuits
Providing ,Fixing, Installation, testing and commissioning of LT Distribution Box for 63 kVA DTR with 100 Amp MCCB 3P 16 kA for incomer & 100 Amp MCCB 3P 16 kA 1 No. and 63 Amp MCCB 3P 16 kA 1 No.s for Outgoing Circuits
Providing, ,transportation ,erection, testing and Commissioning of ST Poles 8 Mtr long (410-SP-15) including excavation of pit and back filling soil & consolidating each deposit layer of by ramming and watering etc. (as per the latest specification and drawing approved by the department).
Supply and fixing of V -Shaped GI Cross Arms (75X40X6 mm) with top Bracket including Clamps, GI Nuts and Bolts.
providing and fixing of G.I barbed wire with clamps for sub-station Poles
Providing, transportation and fixing of 11 KV Pin insulators with G.I Pins (as per the latest specification and drawing approved by the department).
Providing, transportation and fixing of GI Mukey Clamp (50X6) with LT Shackle insulators including GI nuts and bolts.(GI Back Clamps to be fixed with out drilling/punching of poles).
Providing Laying, stringing of overhead 0.05 ACSR conductor (Rabbit) on cross arms through insulators including binding and twisting with soft aluminium wire both side of insulator complete in all respects (as per the latest specification and drawing approved by the department).
Providing & fixing of 11 kV Polymeric composite Disc insulator 12 kV,minimum failing load of 45 kN,lighting impulse of 75 kV positive & 80 kV negative and with creepage distance of 320 mm.
Supply, installation and commissioning of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Providing and fixing of HT/LT pole Earthing Complete by GI pipe 40mm 3 mtr long through GI Strip
providing and Painting of pole with one coat of Red-Oxide and Two coats of Aluminium paint (including cost of paint)
Providing and laying of Cement Bottoming 1:2:4 mix as per REC standards 0.48cum/pole including muffing 15 cm above ground level plaster and curing of concrete in size of 550X550X 1650mm for 9 ST poles (410,SP-33 ) (the leftover pit after concreting to be filled with soil and boulders).
Providing and laying of Cement Bottoming 1:2:4 mix as per REC standards 0 .40 cum/pole including muffing 15 cm above ground level plaster and curing of concrete in size of 500X500X 1650mm 8 Mtr ST poles (410,SP-15) (the leftover pit after concreting to be filled with soil and boulders).
Vibgyor Power and Suppliers
SHAH ELECTRICALS
M/S GM ELECTRICALS AND MECHANICAL
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .