Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance GROUND FLOOR ASHFAQ HUSSAIN AL ABASS A S RELIEF TRUST BUILDING KARAN NAGAR SRINAGAR 91495 SRINAGAR JAMMU AND KASHMIR 190010 | SRINAGAR | JAMMU AND KASHMIR | 190010 | Admitted-Finance |
Tender Value
₹78.3 L
EMD Value
₹1.6 L
Closing Date
18 Sept 2023, 2:00 pmClosed
Executive Engineer Electrical
SKIMS Soura
Supply, Installation, Testing and Commissioning of Fire Fighting System Fire Detection/ Alarm System with allied Civil and Electrical Works at SKIMS, Soura. (External Electrical Component)
2023_SKIMS_222566_1
eNIT NO.SIMS/HEE/E/ET/19 of 2023-24 Dt. 19-07-2023
Open Tender
Electrical Works
Item Rate
180 days
SKIMS Soura
Please refer Tender documents.
8 documents required · 8 mandatory
₹2,500
Director Finance SKIMS
₹1.6 L
Office of the Executive Engineer Electrical
6 Oct 2023
20 Jul 2023
19 Sept 2023
20 Jul 2023
18 Sept 2023
20 Jul 2023
25 Jul 2023
Amount
Sub Station with HT Line
Supplying, erection of swged type steel tubular pole conforming to IS-2713, 410 SP-33 with pole cap & base plate of 300 mm x 300 mm x 6 mm for erecting 11 KV feeder along with pole earthing , including welding, cutting, revetting, bolting and painting the entire structures with red oxide primer and two coats of synthetic Almunium paint .
Providing and Laying of cement Bottoming,1:2;4 (0.5 Cum per pole) for above pole.
Fabrication Supply and erection ofGI V-cross Arm, as per REC Standards, with clamps, complete Job
Supplying & erection of "ACSR 0.05" for 11KV HT Line.
Supplying & erection of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Supplying & erection of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Supplying, installing, structural steel tubular pole conforming to IS-2713, 410 SP-33 with pole cap & base plate of 300 mm x 300 mm x 6 mm for erecting 11 KV two pole structure comprising of 9 Mtr. pole along with pole earthing , including welding, cutting, revetting, bolting and painting the entire structures with red oxide primer and two coats of synthetic Almunium paint and necessary foundations including excavation and earth work for the steel structure with RCC 1:2:4 with 1 feet above ground level with following accessories. Supplying, installing 11 KV 9 KA discharge current single pole lightning arrestor Station Type with insulated base and necessary hardware. - 3 Nos. The job includes providing and fixing of 25x5 mm GI earthing strips as per standard from Earth pit on the insulator upto LA as per REC specfications Supplying & installing 11 KV 3 phase, 200 Amp. Vertical type gang operated switch with hot dip galvanised channels post type, insulator, tinned copper contacts, arcing horns, GI pipe gang operating handle, limit switch etc.locking arrangements etc. complete in all respects. - 1 Set. Supplying & installing 11 KV, 3 phase 200 Amp dropout fuse unit with 60 Amp fuses. Hot dip galvanished channel, post type insulator, tinned copper contacts bakelite fuse, carriers etc. complete in all respects. - 1 Set. Conitnue Below....
Supplying & installing of "ACSR 0.05" from 11KV Bus to DT. The job includeslso Fabrication supply erection of Cross arms of shape and size and made out of GI channels 75mmx40mm x 6mm with flats and fixed to poles with GI clamps, GI bolts, nuts and washers and all hardware, jumpers & thimbles etc. of required size. Providing and fixing of Anti Climbing devices on each pole made out of 2 mm barbed wire coiled alongwith pole. Danger Notice Boards with Skull & Bones in red colour made out of 14 SWG sheet in urdu & English with voltage indicated including idetification plate. . Stay assembly as per requirement, alogwith RYB phase Indicator Round Stickers.
Contruction Of foundation for 1000 KVA and 630 KVA transformer
Earth work excavation manually inculding disposal of earth as directed within SKIMS permises=8'x6'x1'-0" = 1.4x2 = 2.8
P/L of graded stone soling 40mm -50mm including Cost & carraige of material complete, 8'x6'x0'-4"=15.84cft =0.448 cum x 2
P/L of plain cement concrete 1:4:8 mixture incuding cost & carriage of material complete Qty vide part (b) = 0.448 cum x 2
P/L of R.C.C work 1:2:4 mix including cost and carriage of material 8'x6'x4' =384 cfts = 5.5 Cum x 2
P/L of steel reinforcement (TMT) 12mm dia including cost of cutting, bending ,binding including cost binding wire Qty vide item (d) = 5.5 cum @ 35 kg/cum = 192.5x2
Shuttering by steel plates/ wooden planks including removal of same after use.
Main ACB & Transformer
Supply, Installation.Testing & Commisioning of 1000KVA,11/0.433KV 50Hz,Outdoor type,Dyn-11 Distribution Transformer Energy Efficientcy Level - I (EEL I )with OLTC (OCTC+RTCC+AVR ) ,Tapping - +5% to -35% Taps on H.T. Side in steps of 2.5% each, oil immersed,CopperWound,ONAN Cooled, step down ,Distribution Transformer having C.R.G.O core ,Confirming to IS: 1180 Part-1:2014 with latest amendments dully tested,painted and Oil filled to IS: 335 of 1983 with Latest amendments.The transformer shall be complete with following fittings:- a) Manual/ Auto Control of OLTC b) Oil conservator with oil level indicator , minimum level marking and drain plugs. c) automatic on load circuit type tap changer with position indicator and locking arrangement. d) 100mm dial type /Stem type thermometer with metal gaurd. e) Lifting lugs and Bi-directional roller. f) Rating Diagram and terminal marking plate g) Explosion Vent and valves for filtration , drainage and filling e.t.c with necessaryplugs , including air release plug. h) Radiator assembly and silica gel breather. It is including all accessories like Bush Clamps etc.
Disconnecting , lifting , Carriage, Installtion , connecting , testing & Commissioning of the Spare 630KVA X-mer (available)
Earthing/Cables
Earthing with Cu. earth Plate 600mm x 600mm x 3mm thick including accesssories, and providing masonary enclosure with cover plate (CI heavy duty) having locking arrangement and watering pipe pipe of 2.7 mtr long etc. with charcoal or coke and salt) as required.
Providing and fixing 25 mm X 5 mm Copper strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Providing and laying of spans of 3.5/ 1core XLPE Al. cable Armored of various sizes as mentioned below size of 1.1KV grade as per IS :7098 (Part I ) 1988 with upto dte amendments
1000 mm sq. 1 core
Providing and making of end terminations, with Clamps using Al Alloy
1000 mm sq. 1core
Farication , supplyand erection of H- frame fabricated from angle Iron frame of size 50x50x6mm for holding cable
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, inconvenient sections, joined with connectors, including G.I. bolts & nuts, etc. as required. a) 600 mm width X 62.5 mm depth X 2.0 mm thickness
Earth work excavation manually inculding disposal of earth as directed within SKIMS permises for H- Frames
P/L of Cement concrete work 1:2:4 mix including cost and carriage of material for H- Frames
Panel
Supplying,Installation,Testing and Commissioning of Cubical Type AMF Cum Load management panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply .The L.T Panel Should be as per IEC 61439-1&2, Rated Impulse Voltage- 12 kV. IK10 Class, Form of seperation- 3b fabricated out of CRCA sheet steel with chemical wash after 7 tank process and suitable for operation on 415 volts, 50Hz, 3 Phase 4 wire AC supply. LT panels ( 1 Nos. transformers Incomers , 1 Nos. DG Incomers) of substation Building has to be remotly monitored through the Electrical distribution SCADA software with 1 Year Licence. Software has to be capable of monitoring and alarming, Electrical System capacity management, Power Quality monitoring, Breaker setting monitoring, Back up Power testing, Power Event Analysis, Energy Performance Analysis and Verification and Active Arc Flash protection. The Software Platform shall be certified of the following ISO standards: Continue Below.....
a. ISO 50001 for Energy review, Energy baseline, Energy performance indicators, Monitoring, measurement, and analysis b. ISO 50002 for Data collection, Measurement plan & Analysis and Energy audit reporting . The Software Platform shall be certified to comply with cybersecurity standard IEC62443 at the component level: IEC62443-4-1 and IEC62443-4-2 (SL1).7.
Smart Wireless Sensors (Cable Heating Detection) - 2 Nos. Switchboards, non-forced air ventilated, shall be enabled with a DIN rail wireless sensor capable of monitoring the system and generate three-levels of alerts on overheating wire connections or overheating cables depending on the severity of the detected situation. Each Cable Alley of the electrical switchboard shall include one wireless sensor at the top, to help user to prevent electrical switchboards from being damaged, by analyzing gas and particles in the air and sending alerts before any smoke or insulator browning occurs. Sensor shall be able to analyze gases and microparticles inside the switchboard, by concentrating air into the sensor (with the help of an aspiration fan), applying a smart algorithm to sort internal cable issues from overheating, and sending alerts via email or notification to a smart phone application, enabling the switchboard’s digital management. Continue Below.....
Temperature and humidity inside the switchboard should be measured by the wireless sensor and values to be communicated through the network. Wireless sensor for early detection of overheating wire connections or overheating cables, should fulfill ISO 14025 PEP ecopassport® program requirements. Sensor device should not replace any fire protection device of the installation.
Bus Coupler (BC I): 16000 Amp 415 V FP ACB (EDO Draw- out Type) having breaking capacity - Ics=Icu=Icw (1 Sec) = 65 KA, having Microprocessor based releases for O/L, S/C, Instantaneous &E/F protection with applicable time delays and inbuilt LCD Display for Current, Voltage, Energy, Power & PF metering and last 10 trip history., Under Voltage release with Rotary Handle operating Mechanism - 1 No. Electrical Interlocking Trough PLC Continue Below.....
OUTGOING (OG. I): SECTION-1 630 Amp 415 V FP MCCB Microprocessor based release with Over load and Sort Sircuit Protection of breaking capacity - 50 KA, with Ics=Icu=50 KA, with Rotary Handle operating Mechanism - 2 Nos. 630 Amp 415 V FP MCCB Microprocessor based release with Over load and Sort Sircuit Protection of breaking capacity - 50 KA, with Ics=Icu=50 KA, with Rotary Handle operating Mechanism - 2 Nos. 400 Amp 415 V FP MCCB Thermal Magnetic based realease with Overload and Short Circuit protection having breaking capacity - 50 KA, with Ics=Icu=50 KA, with Rotary Handle operating Mechanism - 2 Nos. ON/OFF/Trip Indications - 4 Sets. Continue Below.....
OUTGOING (OG. II): SECTION-2 630 Amp 415 V FP MCCB Microprocessor based release with Over load and Sort Sircuit Protection of breaking capacity - 50 KA, with Ics=Icu=50 KA, with Rotary Handle operating Mechanism - 2 Nos. 250 Amp 415 V FP MCCB Microprocessor based release with Over load and Sort Sircuit Protection of breaking capacity - 36KA, with Ics=Icu=50 KA, with Rotary Handle operating Mechanism - 2 Nos. 100 Amp 415 V FP MCCB Thermal Magnetic based realease with Overload and Short Circuit protection having breaking capacity - 36 KA, with Ics=Icu=36 KA, with Rotary Handle operating Mechanism - 4 Nos. ON/OFF/Trip Indications - 4Sets.
Ali Mohammad Baba and Sons
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .