Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.6 CrAccepted-AOC | ₹6.6 Cr | L1 | Accepted-AOC Technically and Financially accepted |
| 2 | L2₹7.1 Cr+₹47.2 L (7.14%)Rejected-Finance A 3 332 SECTOR 08 ROHINI DELHI 110085 | DELHI | NORTH WEST DELHI | DELHI | 110085 | ₹7.1 Cr+₹47.2 L (7.14%) | L2 | Rejected-Finance Second lowest |
| 3 | L3₹7.6 Cr+₹95.9 L (14.5%)Rejected-Finance H NO 351 F NEAR SHANTADURGA TEMPLE SHANTINAGAR AQUEM BAIXO NAVELIM GOA 403707 | NAVELIM | SOUTH GOA | GOA | 403707 | ₹7.6 Cr+₹95.9 L (14.5%) | L3 | Rejected-Finance Third Lowest |
Tender Value
₹5.6 Cr
EMD Value
₹11.3 L
Closing Date
9 Aug 2022, 5:00 pmClosed
Executive Engineer
Div III, Ponda
SETC of 33KV 3Core 185 Sqmm underground cable from Opa Water Works Opa to the treatment plant at Keriya Curti for a load of 400KVA for providing reliable supply
2022_ED_4729_1
Tender-03/22-23
Open Tender
Electrical Works
Item Rate
365 days
Opa Khandepar
Pl refer tender document
2 documents required · 2 mandatory
₹1,500
₹11.3 L
Yes
7 Mar 2024
14 Jul 2022
11 Aug 2022
14 Jul 2022
9 Aug 2022
15 Jul 2022
Amount
COST OF MATERIAL
Supply and laying of Kadappa of size 600mm length X 250mm width and 37mm thick as protective cover for underground cables
Supply of RCC Hume pipes for road crossings of 250 mm inner diameter, alongwith required no of collars, PCC and Masonary work, and as per technical specifications in the N.I.T.
Supply of Heavy duty, HDGI Class B pipe of inner diameter 150 mm (alongwith HDGI bends wherever required) for crossing of Nullahs and culverts etc as per technical specifications.
Supply and laying of river sand (except in sandy soil)/ for cushioning of 33 KV XLPE underground cable, as per technical specifications & as per direction of the Engineer-in-charge. (0.7X0.3X2200)
Supply of Cable route marker, as per technical specifications.
Supply and laying of Plastic / PVC Warning tape (for entire route length) as per technical specifications
Steel work welded (SAIL, TATA. VIZAG & using electrodes of Ador or ES4B or Deh Secheron make only)in built up sections trusses and framed work including cutting, hoisting, fixing in position and applying priming coat of red lead paint.
Supply and erection of HDGI RSJ Beam of 250x100mm 10mtrs long.
Supply and erection of HDGI RSJ Beam of 200x100mm 10mtrs long.
Supply and erection of Steel work(SAIL, TATA. VIZAG only) riveted or bolted in built up sections, trusses and framed work including cutting, hoisting, fixing in position and applying a priming coat of red lead paint.(Supply and Erection of MS steel for construction of beam for laying 33KV cable over the supporting structure for crossing the culvert and etc.)
Supply of HDGI steel structure for AB switches & LAs & Cable support.
Supply & laying of Rubble packing with hard laterite stone under floors including watering, ramming and consolidating etc. in pipeline trenches and other foundations complete.
Supply & laying of Concreate 1:2:4 for route marker, foundation for bridges at culvert and gutter and for RMU foundation
Reinstatement of roads
Supply of 33KV, 3 Core, 185 Sq.mm. Aluminium Conductor, screened, XLPE insulated Galvanized flat strip armoured, PVC sheathed cable Type A2XFY, FR, conforming to IS: 7098/Part-2 as amended up to date, from the place of manufacturing up to the site location.
Supply of 33KV XLPE 3X185 sq.mm cable straight joints through Pre-moulded type or heat shrinkable type jointing kit complete with all accessories, of reputed make preferably Rachem/3M jointing kit by qualified jointers. as per technical specifications.
Supply of 33KV outdoor, anti-fog, Pre-moulded type or heat shrinkable type end termination kit complete with all accessories, suitable for cable as per technical specifications . The kit shall have total creepage distance of 31mm per KV and protected creepage distance of not more than 50% of the total creepage distance, suitable for heavily polluted atmospheric conditions for connecting to the existing line bus / AB switch , complete by qualified jointers.
Supply of electrode type earthing material with 40mm, 2.5 mts long G.I pipe alongwith 20 Kgs Salt, 20 Kgs Charcoal and 5 mts of H.D.G.I flat of size 50 x 6 mm for earthing connection including material for brick masonary work and as per technical specifications.
Supply of GI Flat 25 x 5 mm.
Supply of ACSR wolf conductor
Supply of 33 KV, 800A GOAB Switch along with pad connectors suitable for ACSR Wolf conductor (wedge type paddle & Connectors) motorized
Supply of 33KV, 400A ,Horn gap fuse unit(set of 3)
Supply of 30KV, 10KA Lightning arrestor with insulating base and with counter
Supply of 33KV, 4way, 630Amps,25KA/1Sec, SF6 insulated RH side extensible , outdoor , motorized, comprizing 4 Vacuum Circuit breaker free standing type for bottom entry 3core cable of size 400Sq.mm. with overcurrent earth fault relay, Master trip with remote operation & SCADA compatibility & including termination kit.
Supply of 33KV, 8way, 630Amps,25KA/1Sec, SF6 insulated RH side extensible , outdoor , motorized, comprizing 8 Vacuum Circuit breaker plus metering free standing type for bottom entry 3core cable of size 400Sq.mm. with overcurrent earth fault relay, Master trip with remote operation & SCADA compatibility & including termination kit. (VCB)+VVVV+VVVV+M
Supply and erection of Detuned Reactor protected APFC Panel- Thyristor Based,250KVA rating on LT complete.
Supply of BIS approved 500KVA 33/0.433KV Hermeticaly sealed virtually Maintenance Free Mineral oil filled Non- Gas Cushion Type copper wound Distribution Transformer with (OLTC) ON LOAD TAP changer of +5% to -15% in step of 2.5, Dyn11, losses as per IS 1180:Energy Effeciency Level 2, Impedance:4.5%
Supply of XLPE Armoured cable 31/2 core X 70 Sq.mm, 1.1KV Grade Power cable
Supply of XLPE Armoured cable 31/2 core X 185 Sq.mm, 1.1KV Grade Power cable
Supply of XLPE Armoured cable 31/2 core X 240 Sq.mm, 1.1KV Grade Power cable
Supply of FRTU panel for 4 way RMU.
ERECTION OF MATERIALS
Carrying out detailed physical survey of the area and to furnish optimal and economical route and design for laying of 33KV, 3 core , 185 sq.mm XLPE round cable and accessories, including plotting on the scald map of size 1:1000 including all features. The detalied documents as well as write up shall be furnished in 2nos. of hard copies and soft copies for approval. Upon approval & after carrying out the cable laying work the GIS co-ordinates of entire route may be furnished along with 6nos. of hard and soft copies of map duly updated.
Excavation of trench in any type of soil (after clearing of site of all bushes, shrubs, trees, roots and other obstacles and after installing barricades, glow signboards, etc) including trenching along & across the roads, paddy fields, water logged areas, sandy, hard soil, hard rock, for laying underground two runs of 33 KV, 3 core, 185 sq.mm, XLPE cable.(0.7m X 1.3m X 700m)
Excavation of Hard rock including all types of laterite rock, blasting prohibited)(0.7m X 1.3m X 1500m)
Back filling of available excavated earth (excluding rock/stones) in trench, in layers not exceeding 0.2 mts depth, consolidating each deposited layer by ramming and watering lead up to 40 mts. (0.7 m X 1m X 2200m)
Disposal of surplus excavated soil / material by mechanical transportation and including loading and unloading, stacking, levelling as directed within a distance of 2500 mts.(0.7m X 0.3m X 2200m)
Erection of RCC Hume pipes for road crossings of 250 mm inner diameter, alongwith required no of collars, PCC and Masonary work, and as per technical specifications in the N.I.T.
Erection of Heavy duty, HDGI Class B pipe of inner diameter 150 mm (alongwith HDGI bends wherever required) for crossing of Nullahs and culverts etc as per technical specifications.
Erection of Cable route marker, as per technical specifications.
Erection of HDGI steel structure for AB switches & LAs & Cable support.
Erection, testing & commissioning of 33KV, 3 Core, 185 Sq.mm. Aluminium Conductor, screened, XLPE insulated Galvanized flat strip armoured, PVC sheathed cable Type A2XFY, FR, conforming to IS: 7098/Part-2 as amended up to date, from the place of manufacturing up to the site location.
Erection of 33KV XLPE 3X185 sq.mm cable straight joints through Pre-moulded type or heat shrinkable type jointing kit complete with all accessories, of reputed make preferably Rachem/3M jointing kit by qualified jointers. as per technical specifications.
Erection of 33KV outdoor, anti-fog, Pre-moulded type or heat shrinkable type end termination kit complete with all accessories, suitable for cable as per technical specifications . The kit shall have total creepage distance of 31mm per KV and protected creepage distance of not more than 50% of the total creepage distance, suitable for heavily polluted atmospheric conditions for connecting to the existing line bus / AB switch , complete by qualified jointers.
Erection of electrode type earthing material with 40mm, 2.5 mts long G.I pipe alongwith 20 Kgs Salt, 20 Kgs Charcoal and 5 mts of H.D.G.I flat of size 50 x 6 mm for earthing connection including material for brick masonary work and as per technical specifications.
Erection of GI Flat 25 x 5 mm.
Erection of ACSR wolf conductor
Erection of 33 KV, 800A GOAB Switch along with pad connectors suitable for ACSR Wolf conductor (wedge type paddle & Connectors) motorized
Erection of 33KV, 400A ,Horn gap fuse unit(set of 3)
Erection of 30KV, 10KA Lightning arrestor with insulating base and with counter
Erection of 33KV, 4way, 630Amps,25KA/1Sec, SF6 insulated RH side extensible , outdoor , motorized, comprizing 4 Vacuum Circuit breaker free standing type for bottom entry 3core cable of size 400Sq.mm. with overcurrent earth fault relay, Master trip with remote operation & SCADA compatibility & including termination kit.
Erection of 33KV, 8way, 630Amps,25KA/1Sec, SF6 insulated RH side extensible , outdoor , motorized, comprizing 8 Vacuum Circuit breaker plus metering free standing type for bottom entry 3core cable of size 400Sq.mm. with overcurrent earth fault relay, Master trip with remote operation & SCADA compatibility & including termination kit. (VCB)+VVVV+VVVV+M
Testing & comissioning of the entire cable, terminations and RMU. Entire scheme including meggering, Hipot tests and furnishing required docoments for approval for energizing the scheme and Electrical Inspector approval.
Erection of BIS approved 500KVA 33/0.433KV Hermeticaly sealed virtually Maintenance Free Mineral oil filled Non- Gas Cushion Type copper wound Distribution Transformer with (OLTC) ON LOAD TAP changer of +5% to -15% in step of 2.5, Dyn11, losses as per IS 1180:Energy Effeciency Level 2, Impedance:4.5%
Erection of 500KVA transformer synchronisation panel, with outgoing feeder complete.
Laying of XLPE Armoured cable 31/2 core X 70 Sq.mm, 1.1KV Grade Power cable
Laying of XLPE Armoured cable 31/2 core X 185 Sq.mm, 1.1KV Grade Power cable
Laying of XLPE Armoured cable 31/2 core X 240 Sq.mm, 1.1KV Grade Power cable
Erection of FRTU panel for 4 way RMU.
B) CIVIL COMPONENTS
Earthwork in excavation by mechanical means (hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10sq.m on plan) including disposal of excavated earth lead upto 50 m and lift upto 1.5m disposed earth to be leveled and neatly dressed including providing barricading, danger lighting guarding as directed
(a) Hard rock where blasting prohibited
Rubble packing with hard laterite stone under floors including watering ramming and consolidating etc. in pipeline trenches and other foundations complete.
Providing & laying cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded granitic or basaltic stone aggrt. 40 mm. nominal size) excluding cost of centering, shuttering and finishing in:
(a) All works upto plinth level
Laterite masonry in neatly dressed stones of size as specified in cement mortar 1: 5 (1 cement : 5 coarse sand) in foundation and basement.
Laterite masonry in neatly dressed stones of size as specified in cement mortar 1: 4 (1 cement : 4 coarse sand) in foundation and basement. Extra for laterite masonary in all sizes in superstructure from I level upto floor V level.
Providing and laying upto floor five level cement concrete 1:2:4 (1 cement: 2 coarse sand: 4 graded granitic or basaltic stone aggregate 20 mm nominal size) including smooth finishing to exposed surfaces, with cement mortar 1:3 (1 cement: 3 fine sand) including centering and shuttering etc.
(a) String courses, copings, bedplates, anchor blocks, plain window sills and the like.
Providing and fixing M.S. grill of required pattern in wooden frames of Windows etc. with M.S. flats square or round bars with round headed bolts and nuts or by screws.
(a) Ornamental grill
Surface dressing of ground including removing vegetation in equalities not exceeding 15 cm deep and disposal of rubbish lead upto 50 m and lift upto 1.5 m.
(a) Ordinary Soil
Supplying and stacking 40mm Granitic / Basaltic Aggregates at site including loading, unloading and transportaion etc. complete.
Uniformally laying and spreading of 40mm aggregates 100mm thick inside 33KVA Substation at Opa water works. Including manpower, tools & Equipments etc complete.
Providing and fixing prefabricated compound gate of G.I. pipes 40 – 50 mm dia (medium) with 12mm M.S. square bars of G.I. pipes grill work as per drawing including providing & fixing locking arrangements, pintals, hold fast embedded in cement concrete 1:2:4 (1 cement: 2 coarse sand : 4 granitic or basaltic aggregate 20mm nominal size) including applying priming coat with ready mixed red lead paint and painting 2 or more coats with superior ready mixed paint of approved brand and manufacture in all shades as per direction complete.
12mm cement plaster 1:3 (1 cement : 3 fine sand)
18mm cement plaster in two coats under layer 12mm thick cement plaster 1:5 ( 1 cement : 5 coarse sand) and top layer 6mm thick with cement plaster 1: 3 (1 cement : 3 coarse sand) finished with sponge.
Distempering two or more coats with oil bound washable distemper of approved brand and manufacture and of required shade on new work over and including a priming coat with distemper primer of approved brand and manufacture to give an even shade.
Painting three or more coats with acryllic exterior paint of approved brand and manufacture (such as weather shield,APEX) including applying one coat of cement primer and one coat of surface treatment etc. complete.
Applying priming coat with ready mixed primer of approved brand and manufacture on steel work.
Centering & shuttering including Strutting, Propping & removal of forms for :
(a) Foundations, Footings, Bases for columns
Sides and Soffits of beams, Beam Haunchings, Cantilever, Girders, Bressumers and Lintels plinth beams not exceeding 1m in depth
Columns, Piers, Pillars, Abutments, Posts and struts (square rectangle polygon in plan)
Providing TMT steel reinforcement bars of SAIL, TATA. VIZAG made only (Confirming to IS 1786 of 1986) for RCC work (conforming to I.S. 1786 of 1986) including bending, binding & placing in position in all the floors along with the factory made precast concrete cover blocks of specified sizes whose compressive strength is not less than that of surrounding concrete in the structural member.
Providing and laying in position (1:11/2:3) Reinforced cement concrete excluding the cost of centering, shuttering, finishing and reinforcement (1 cement: 1½ coarse sand:3 graded stone aggregate 20mm nominal size)
(a) All works upto plinth level
Providing and laying in position (1:11/2:3) Reinforced cement concrete excluding the cost of centering, shuttering, finishing and reinforcement (1 cement: 1½ coarse sand:3 graded stone aggregate 20mm nominal size)
(a) in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. upto floor five level
Painting two or more coats (excluding priming coat) with superior quality ready mixed paint for steel work of approved brand & manufacture in all shades on new work to give an even shade.
Steel work welded (SAIL, TATA. VIZAG & using electrodes of Ador or ES4B or Deh Secheron make only)in built up sections trusses and framed work including cutting, hoisting, fixing in position and applying priming coat of red lead paint
(a) In tees, angles, flats and channels
Providing and fixing colour coated galvulium roofing sheets of 0.5mm thickness including all the accessories (TATA make) but excluding the cost of purlins, rafters, trusses, flashings etc. complete as per the directions of the Engineer in charge.
Providing and fixing anodized aluminium shutters in accordance with the specification annexed with Goa schedule of Rates (2004) Vol & II including all taxes, transportation, scaffolding and handling etc. complete as per direction of the Engineer-in-charge: windows with two sliding shutters using 18 mm series shutters section.
(a) Plain glass
Providing and fixing anodized aluminium shutters in accordance with the specification annexed with Goa schedule of Rates (2004) Vol & II including all taxes, transportation, scaffolding and handling etc. complete as per direction of the Engineer-in-charge: Single or double leaf door shutters.
(a) Plain plate glass
Providing and fixing vitrified matt finished (600x600) and 10mm thick tiles in floor, treads of steps, landing on 25mm thick bed of cement mortar 1:3 and jointed with cement slurry complete.
CREATIVE ENTREPRENEURS LLP
Putusatya Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .