Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.2 LAccepted-AOC 4 94D RAJA COTTAGE 1ST FLOOR KANYAKULAM PARVATHIPURAM NAGERCOIL KANNIYAKUMARI TAMILNADU 629 003 | KANNIYAKUMARI | TAMIL NADU | 629003 | ₹27.2 L Quoted ₹28.2 L | L1 | Accepted-AOC L1 |
| 2 | L2₹32.5 L+₹4.4 L (15.4%)Rejected-AOC NO 7 3RD MAIN ROAD MUNI REDDY LAYOUT HORAMAVU MAIN ROAD BANASAWADI BANGALORE 560043 | BENGALURU URBAN | KARNATAKA | 560043 | ₹32.5 L+₹4.4 L (15.4%) | L2 | Rejected-AOC L2 |
| 3 | L3₹37.9 L+₹9.7 L (34.4%)Rejected-AOC | ₹37.9 L+₹9.7 L (34.4%) | L3 | Rejected-AOC L3 |
| Sl No | Description | Qty | Unit | ARUNOTHAYA TRADERS L2 | MATA GUJRI CONSTRUCTION CO. L3 | ADR ENTERPRISES L1 |
|---|---|---|---|---|---|---|
| 1.00 | Dismantling & taking out old unserviceable earthing pits including connected materials all as specified and directed. | 77 | Each Set | 650 ₹50,050 | 90 ₹6,930 | 70 ₹5,390 Lowest |
| 2.00 | M&L for earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25 M deep below ground level) with top edge of the plate not less than 1.5 M below normal ground level connected to galvanised earth lead wire of size 4.0mm dia up to a length of 7.5 mtr long by means of nuts, bolts, check nuts, washers of galvanised iron or steel all as shown in electrical plate No. 3 of SSR Part I of 2009 connected to earthing test point or disconnecting / testing link including excavation/ earth work in any strata, removal of surplus soil, GI pipe medium grade 20mm dia for watering and funnel, GI Pipe medium grade 15mm dia for earth lead protection, PCC 1:3:6 type C2 bed and chamber in PCC 1:2:4 type B1 including necessary form work, 10mm thick CI chamber cover with hinge, etc. complete all as specified and directed. | 15 | Each Set | 5,500 ₹82,500 Lowest | 11,800 ₹1,77,000 | 5,500 ₹82,500 Lowest |
| 3.00 | M&L for earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25 M deep below ground level) with top edge of the plate not less than 1.5 M below normal ground level connected to galvanised strip of size 25x4 mm up to a length of 7.5 mtr long by means of nuts, bolts, check nuts, washers of galvanised iron or steel all as shown in electrical plate No. 3 of SSR Part I of 2009 connected to earthing test point or disconnecting / testing link including excavation/ earth work in any strata, removal of surplus soil, GI pipe medium grade 20mm dia for watering and funnel, GI Pipe medium grade 40mm dia for earth lead protection, PCC 1:3:6 type C2 bed and chamber in PCC 1:2:4 type B1 including necessary form work, 10mm thick CI chamber cover with hinge, etc. complete all as specified and directed. | 22 | Each Set | 5,500 ₹1,21,000 Lowest | 11,900 ₹2,61,800 | 5,500 ₹1,21,000 Lowest |
| 4.00 | All same as per item No 3 here-in-before but galvanised strip of size 32 x 6mm | 20 | Each Set | 5,500 ₹1,10,000 Lowest | 12,000 ₹2,40,000 | 5,500 ₹1,10,000 Lowest |
| 5.00 | Material and Labour for maintenance free earthing complete comprising of 17.2 mm dia 3 metre long Earth electrode of low carbon steel electrode with 250 micron copper bonding, 50 pounds of Ecosafe based environment friendly backfill and suitable clamp, back-fill earthing enhancing compound should strictly be a Eco Safe carbon based conductive concrete type which has a resistivity of less than 0.12 Ohm meter as per Clause 14.5D of IEEE : 80 standard. Back-fill compound should be electronically conductive (like in metals) and should not depend on moisture for conduction. Back-fill compound should be environment friendly, should solidify when mixed water and set like concrete and should not leach /diffuse into the ground. Back-fill compound shall not mix with any soil while pouring in the bore hole. Test Certificate as per IEC :62561-7 for Back-fill compound shall be submitted alongwith the material. 17.2 OD SS clamp both side, Eco friendly rust proof heavy duty weather proof Polyethylene Earth pit chamber with following dimensions : 254 mm dia (top),330 mm dia (bottom) & 260 mm (height) complete all as specified and directed. | 10 | Each Set | 6,500 ₹65,000 | 27,000 ₹2,70,000 | 6,000 ₹60,000 Lowest |
| 6.00 | M&L for earthing complete with copper earth plate electrode 600mm x 600mm x 3.15mm thick buried directly in ground (earth pit not less than 2.25 M deep below ground level) with top edge of the plate not less than 1.5 M below normal ground level connected to copper strip of 20x3 mm up to a length of 7.5 mtr long by means of nuts, bolts, check nuts, washers of galvanised iron or steel all as shown in electrical plate No. 3 of SSR Part I of 2009 connected to earthing test point or disconnecting / testing link including excavation/ earth work in any strata, removal of surplus soil, GI pipe medium grade 20mm dia for watering and funnel, GI Pipe medium grade 40mm dia for earth lead protection, PCC 1:3:6 type C2 bed and chamber in PCC 1:2:4 type B1 including necessary form work, 10mm thick CI chamber cover with hinge, etc. complete all as specified and directed.
Note for item Nos 2 to 6 :
(a) Earthing value should be less than 5 ohms for Ser item No 2 to 5 and less than 1 ohms for ser item No 6.
(b) If desired value of earth resistance not achieved during testing, the earthing work shall be redone by the contractor at free of cost to achieve the desire value of earthing resistance. The rate quoted by the contractor deemed to be inclusive of the provision. | 10 | Each Set | 16,500 ₹1,65,000 Lowest | 20,000 ₹2,00,000 | 19,500 ₹1,95,000 |
| 7.00 | Supply and fix in repairs GI strip of size 25mmx4mm as earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing using clamps & nut bolt as required complete all as specified and directed. | 400 | RM | 120 ₹48,000 Lowest | 140 ₹56,000 | 150 ₹60,000 |
| 8.00 | Supply and fix in repair earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required 4mm dia galvanised iron or steel wire complete all as specified and directed. | 200 | RM | 45 ₹9,000 | 50 ₹10,000 | 42 ₹8,400 Lowest |
| 9.00 | Supply and fix in repairs aluminium strip 25 mm x 3 mm complete with saddles and fixing screws etc for roof conductors and down conductors above ground level and fixing upto 20 mtr height including removing u/s strips complete all as specified and directed. | 300 | RM | 160 ₹48,000 | 105 ₹31,500 Lowest | 120 ₹36,000 |
| 10.00 | Supply and fix in repairs copper strip 20mm x 3 mm complete with saddles and fixing screws etc for roof conductors and down conductors above ground level and fixing upto 20 mtr height including removing u/s strips complete all as specified and directed. | 180 | RM | 650 ₹1,17,000 | 440 ₹79,200 Lowest | 1,250 ₹2,25,000 |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
10 Jun 2026, 6:00 pmClosed
GE (AF) Yelahanka
GE (AF) Yelahanka Bangalore - 63
Repair/ replacement of earthing and LT UG cable
2026_MES_766768_1
8512/E8
Open Tender
Civil Works
Item Rate
180 days
GE (AF)Yelahanka
As per NIT
9 documents required · 9 mandatory
₹500
GE (AF) Yelahanka
₹80,000
Yes
11 Sept 2026
20 May 2026
17 Jun 2026
20 May 2026
10 Jun 2026
3 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Dismantling & taking out old unserviceable earthing pits including connected materials all as specified and directed. | - | Each Set | - | - |
| 2 | M&L for earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25 M deep below ground level) with top edge of the plate not less than 1.5 M below normal ground level connected to galvanised earth lead wire of size 4.0mm dia up to a length of 7.5 mtr long by means of nuts, bolts, check nuts, washers of galvanised iron or steel all as shown in electrical plate No. 3 of SSR Part I of 2009 connected to earthing test point or disconnecting / testing link including excavation/ earth work in any strata, removal of surplus soil, GI pipe medium grade 20mm dia for watering and funnel, GI Pipe medium grade 15mm dia for earth lead protection, PCC 1:3:6 type C2 bed and chamber in PCC 1:2:4 type B1 including necessary form work, 10mm thick CI chamber cover with hinge, etc. complete all as specified and directed. | - | Each Set | - | - |
| 3 | M&L for earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25 M deep below ground level) with top edge of the plate not less than 1.5 M below normal ground level connected to galvanised strip of size 25x4 mm up to a length of 7.5 mtr long by means of nuts, bolts, check nuts, washers of galvanised iron or steel all as shown in electrical plate No. 3 of SSR Part I of 2009 connected to earthing test point or disconnecting / testing link including excavation/ earth work in any strata, removal of surplus soil, GI pipe medium grade 20mm dia for watering and funnel, GI Pipe medium grade 40mm dia for earth lead protection, PCC 1:3:6 type C2 bed and chamber in PCC 1:2:4 type B1 including necessary form work, 10mm thick CI chamber cover with hinge, etc. complete all as specified and directed. | - | Each Set | - | - |
| 4 | All same as per item No 3 here-in-before but galvanised strip of size 32 x 6mm | - | Each Set | - | - |
| 5 | Material and Labour for maintenance free earthing complete comprising of 17.2 mm dia 3 metre long Earth electrode of low carbon steel electrode with 250 micron copper bonding, 50 pounds of Ecosafe based environment friendly backfill and suitable clamp, back-fill earthing enhancing compound should strictly be a Eco Safe carbon based conductive concrete type which has a resistivity of less than 0.12 Ohm meter as per Clause 14.5D of IEEE : 80 standard. Back-fill compound should be electronically conductive (like in metals) and should not depend on moisture for conduction. Back-fill compound should be environment friendly, should solidify when mixed water and set like concrete and should not leach /diffuse into the ground. Back-fill compound shall not mix with any soil while pouring in the bore hole. Test Certificate as per IEC :62561-7 for Back-fill compound shall be submitted alongwith the material. 17.2 OD SS clamp both side, Eco friendly rust proof heavy duty weather proof Polyethylene Earth pit chamber with following dimensions : 254 mm dia (top),330 mm dia (bottom) & 260 mm (height) complete all as specified and directed. | - | Each Set | - | - |
| 6 | M&L for earthing complete with copper earth plate electrode 600mm x 600mm x 3.15mm thick buried directly in ground (earth pit not less than 2.25 M deep below ground level) with top edge of the plate not less than 1.5 M below normal ground level connected to copper strip of 20x3 mm up to a length of 7.5 mtr long by means of nuts, bolts, check nuts, washers of galvanised iron or steel all as shown in electrical plate No. 3 of SSR Part I of 2009 connected to earthing test point or disconnecting / testing link including excavation/ earth work in any strata, removal of surplus soil, GI pipe medium grade 20mm dia for watering and funnel, GI Pipe medium grade 40mm dia for earth lead protection, PCC 1:3:6 type C2 bed and chamber in PCC 1:2:4 type B1 including necessary form work, 10mm thick CI chamber cover with hinge, etc. complete all as specified and directed.
Note for item Nos 2 to 6 :
(a) Earthing value should be less than 5 ohms for Ser item No 2 to 5 and less than 1 ohms for ser item No 6.
(b) If desired value of earth resistance not achieved during testing, the earthing work shall be redone by the contractor at free of cost to achieve the desire value of earthing resistance. The rate quoted by the contractor deemed to be inclusive of the provision. | - | Each Set | - | - |
| 7 | Supply and fix in repairs GI strip of size 25mmx4mm as earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing using clamps & nut bolt as required complete all as specified and directed. | - | RM | - | - |
| 8 | Supply and fix in repair earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required 4mm dia galvanised iron or steel wire complete all as specified and directed. | - | RM | - | - |
| 9 | Supply and fix in repairs aluminium strip 25 mm x 3 mm complete with saddles and fixing screws etc for roof conductors and down conductors above ground level and fixing upto 20 mtr height including removing u/s strips complete all as specified and directed. | - | RM | - | - |
| 10 | Supply and fix in repairs copper strip 20mm x 3 mm complete with saddles and fixing screws etc for roof conductors and down conductors above ground level and fixing upto 20 mtr height including removing u/s strips complete all as specified and directed. | - | RM | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.19 MB
BOQ_858729.xls
BOQ • 0.34 MB
8512Merged.pdf
Tender Documents • 1.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .